Associated Keypad; Custom Function - Bosch B9512G Program Entry Manual

Security system
Hide thumbs Also See for B9512G:
Table of Contents

Advertisement

Control Panel
Selections:
Assign an area to the door controller. This is the area a user exit when initiating a request to
exit (REX).
RPS Menu Location
Access > Doors > Entry
12.1.5

Associated Keypad #

Default: No Keypad
Selections: 0 to 32
This parameter sets the door controller to SDI2 keypad associated for KP# Dual
Authentication. A Setting of Disabled also disables Dual Authentication operation.
Enter the Keypad number (KP#) which determines the scope of the user ID's disarming rights.
Areas disarm on the basis of this Keypad's scope and the Authority Level of.
No Keypad: Only the area assigned to the Entry Area, page 226 disarms for this door.
Notice!
The B9512G supports Keypads 1 to 32 on an SDI2 bus, or 1 to 16 on an SDI bus. The B8512G
supports Keypads 1 to 8.
RPS Menu Location
Access > Doors > Associated Keypad #
12.1.6

Custom Function

Default: Disabled
Selections:
Disabled: Custom function is disabled.
CF###: The custom function number that activates when a valid ID is entered, given the
appropriate user access level and area arm state.
Use this parameter to program a custom function that activates at the keypad programmed for
Scope, page 111.
This custom function only activates for users with a function level authority that allows a valid
ID to perform a custom function during the armed or disarmed state.
The user to which the card or token is assigned must have an assigned passcode.
The following table shows how this programming affects custom function activation:
Function level
A (armed)
D (disarmed)
Bosch Security Systems, Inc.
B9512: 1-32
B8512: 1-8
B9512G: Disabled, CF128 to CF159
B8512G: Disabled, CF128 to CF135
Custom function activation
User token activates the custom function
assigned to the door controller only when the
entry area for the door controller is All On or
Part On.
User token activates the custom function
assigned to the door controller only when the
entry area for the door controller is disarmed.
Program Entry Guide
Access | en 227
2017.03 | 09 | F.01U.303.998

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

B8512gB8512g-eB9512g-e

Table of Contents