Notice!
After system installation and any control panel programming, perform a complete system test.
A complete system test includes testing the control panel, all devices, and communication
destinations for proper operation.
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER
INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply
with the requirements in the Standard for Control Units and Accessories for Fire Alarm
Systems, UL 864, you must limit certain programming features or options to specific values.
RPS Menu Location:
Compliance Settings > UL864 Fire Application
2.4

Supervision configuration

Optimizing data used for supervision:
Installation
Type
Required
Supervision
Interval
Recommen
ded Service
Plan
Panel Programming
Receiver
Supervision
Time
Panel Poll
Rate (sec)
Panel ACK
Wait (sec)
Panel Retry
Count
Bosch Security Systems, Inc.
Commercial
Commercial
Burg
Burg (ULC
(UL1610)
S304)
200 sec
180 sec
Extended
Extended
200 sec
Custom
n/a
89 sec
n/a
15
n/a
5
Program Entry Guide
High
Hourly
Supervision
300 sec
1 hr
High
Standard
Supervision
300 sec
1 hr – NFPA 4 hr –
n/a
n/a
n/a
n/a
n/a
n/a
Compliance Settings | en
Medium
Daily
Security or
Supervision
Household
Fire
4 hr
25 hr
Standard
Backup
25 hr
Medium
Security
n/a
n/a
n/a
n/a
n/a
n/a
2017.03 | 09 | F.01U.303.998