Idle Scroll Lock; Function Lock; Abort Display - Bosch B9512G Program Entry Manual

Security system
Hide thumbs Also See for B9512G:
Table of Contents

Advertisement

Control Panel
Use this parameter to determine whether this keypad sounds an audible tone and displays the
CLOSE DOOR # warning on the keypad when the door is physically held open past the Shunt
Time, and Extend Time has a value greater than zero for the door assigned to this area in
Assign Door, page 114.
RPS Menu Location
Keypads > Keypad Assignments > Close Door Warning Tone
5.1.19

Idle Scroll Lock

Default: No
Selections:
This parameter prevents auto-scrolling of the keypad's text displaying existing control panel
conditions, such as troubles.
Notice!
UL 864 requirement for commercial fire
To comply with UL864 requirements for commercial fire systems, set this parameter to No.
RPS Menu Location
Keypads > Keypad Assignments > Idle Scroll Lock
5.1.20

Function Lock

Default: No (for all KP addresses)
Selections:
This parameter determines if the Function Lock requires a passcode when pressed to access
the functions.
The user is prompted to enter a passcode after pressing the Bypass, Menu, or Shortcuts key
on the keypad. The items programmed in the function list for this specific keypad are filtered
by the user's authority level. Only those items in the function list for which the user has
authority appear.
If set to No, when the user presses the Bypass, Menu, or Shortcuts key, all items that are
programmed in the Menu List for the keypad address appear, regardless of the user's
authority level.
RPS Menu Location
Keypads > Keypad Assignments > Function Lock
5.1.21

Abort Display

Default: Yes (for all KP addresses)
Selections:
Select whether or not the keypad shows ALARM NOT SENT if the alarm is aborted before an
event report is sent to the central station.
RPS Menu Location
Keypads > Keypad Assignments > Abort Display
Bosch Security Systems, Inc.
Yes - enable Idle Scroll Lock.
No - allow the control panel's text to auto-scroll.
Yes - pressing the Bypass, Menu, or Shortcuts key requires a passcode before proceeding.
 No - pressing the Bypass, Menu, or Shortcuts key does not require a passcode until a
function requiring one is selected.
Yes - this keypad displays a message for all aborted alarms within its scope.
No - this keypad does not display a message for aborted alarms within its scope.
Program Entry Guide
Keypads | en 117
2017.03 | 09 | F.01U.303.998

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

B8512gB8512g-eB9512g-e