Circuit Style; Normal State - Bosch B9512G Program Entry Manual

Security system
Hide thumbs Also See for B9512G:
Table of Contents

Advertisement

202 en | Points
Use this feature to delay the effect of the following parameters:
Notice!
Point Response (D) Delay Alarm is not supported by Delay Response feature. So, when a
Delay Alarm results in an instant alarm, that alarm is not delayed by this feature.
RPS Menu Location
Points > Point Indexes (point profiles) > Delay Response Armed
10.3.34

Circuit Style

Default: Single EOL (1KΩ)
Selections:
This parameter sets the circuit style for a point index.
Notice!
Circuit Style control panel firmware requirements
The Circuit Style Parameter is not available for control panel firmware v2.xx.
The Dual EOL resistor configuration is available only for control panel firmwarev3.01 and
higher.
The Single EOK (2KΩ) selection is only for control panel firmware v3.03 and higher.
The No EOL selection is only for control panel firmware v3.03 and higher.
Single EOL (1KΩ) – valid with all point sources.
Single EOL (2KΩ), Dual EOL, No EOL – valid with On-board and B208 point sources.
RPS Menu Location
Points > Point Indexes (point profiles) > Point Type/Response/Circuit Style
Further information
Point Type, page 184
Point Response, page 184
10.3.35

Normal State

(Not available on version 2.xx control panels.)
Default: Open
Selections:
2017.03 | 09 | F.01U.303.998
24-Hour, page 203
Part On, page 203
Interior, page 204
Interior Follower, page 204
Point Response, page 184
Instant Alarm
Supervisory
Output Response Type, page 194
Display as Device, page 194
Output, page 179
Single EOL (1KΩ)
Single EOL (2KΩ)
Dual EOL
No EOL
Open – an open point circuit is the Normal state.
Short – a short on point circuit is the Normal state.
Program Entry Guide
Control Panel
Bosch Security Systems, Inc.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

B8512gB8512g-eB9512g-e

Table of Contents