Buzz Time; Extend Time; Deactivate On Open - Bosch B9512G Program Entry Manual

Security system
Hide thumbs Also See for B9512G:
Table of Contents

Advertisement

Control Panel
Selections:
0 – the shunt does not activate for this door.
1 to 240 – the shunt activates for the seconds entered.
Enter the number of seconds the door is shunted to allow a user to open the door without
causing the point to go into Trouble, Alarm, or a faulted condition.
RPS Menu Location
Access > Doors > Shunt Time
12.1.15

Buzz Time

Default: 2
Selections: 0, 1 - 240 seconds
0: no buzz time for this door.
1 - 240: The buzzer sounds for seconds programmed.
Enter the seconds that the buzzer output activates to notify the user that the strike is
activated and the door is ready to open. The buzzer stops when the door is opened.
A separate buzzer is required.
Many readers have an internal buzzer that is not affected by Buzz Time.
RPS Menu Location
Access > Doors > Buzz Time
12.1.16

Extend Time

Default: 10
Selections: 0, 1 - 30 seconds
Enter the amount of time (1 to 30) to prolong strike, buzz, and shunt activation when the
shunt time expires and a door remains open. At the end of the programmed Extend Time, the
buzzer continues to buzz until the door closes. In addition, if programmed, the point assigned
to the door indicates a Trouble, Alarm, or Fault at the keypad.
Regardless of the door point programming, the system generates a Trouble Door Left Open
event while the system is disarmed, and an Alarm Door Left Open event when the system is
armed and the door is held open beyond Extend Time. "Door Closed - Restoral" events are
generated after the door is held open past Extend Time and the door has returned to normal.
Enter 0 to disable Extend Time. The Trouble Door Left Open event, the Alarm Door Left Open
event, and the warning at the keypad are all disabled.
RPS Menu Location
Access > Doors > Extend Time
12.1.17

Deactivate on Open

Default: Yes
Selections:
Yes: Strike deactivates when the door point is faulted (door is opened) after access is granted.
No: Strike remains activated for the amount of the programmed strike time whether the door
is opened or closed.
This parameter determines whether the strike deactivates immediately upon physically
opening the door (door point is faulted).
In order for this function to work, a point needs to be assigned in the Door Point, page 228
parameter.
Bosch Security Systems, Inc.
Program Entry Guide
Access | en 231
2017.03 | 09 | F.01U.303.998