244 en | SDI2 modules
14.4.14

Firmware Upgrade Enable

Default: No
Selections:
Yes - modify the firmware through the web interface.
No -modify the firmware through the control panel.
This parameter allow the B42x modules's firmware to be modified via the external Web
interface.
RPS Menu Location
SDI2 Modules > IP Communicator > Firmware Upgrade Enable
14.4.15

Module Hostname

Default: Blank
Selections: Up to sixty-three characters (letters, numbers, and dashes)
The hostname indentifies the ip communicator (onboard or SDI2 module) on the network. Use
this parameter to create a custom hostname.
Notice!
Leave this parameter blank to use factory default hostname
The factory default hostname begins with the letter B, followed by the last six digits of the
modules MAC address.
Use RPS diagnostics or installer (keypad) diagnostics to view the hostname.
Use the hostname on a local network using DHCP. To use the hostname externally, you must
enter the hostname in the DNS server.
You can use the hostname to connect to the control panel with RPS or RSC (Remote Security
Control), or for module web configuration and diagnostics.
The parameter has no effect on B450 Plug-in Communicator Interface operation.
RPS Menu Location
SDI2 > B42x IP Communicator > Module Hostname
14.4.16

Unit Description

Default: Blank
Selections: Up to twenty alphanumeric characters.
This parameter describes the B42xmodule (location, attributes, etc.).
The description can be programmed with up to twenty alphanumeric characters, including: A
to Z, 0 to 9, ?, &, @, -, *, +, $, #, /
Characters not listed are invalid and cannot be used for text.
RPS Menu Location
SDI2 Modules > IP Communicator > Unit Description.
14.4.17

TCP/UDP Port Number

Default: 7700
Selections: 0 - 65535
This parameter sets the local port number that the IP communicator listens to in-coming
network traffic. It also uses this port for outgoing communications.
The TCP/UDP Port is typically left at the default, 7700, for control panel communications with
a central station receiver, RPS, automation, or Remote Security Control (RSC).
Port numbers are categorized into three ranges:
System ports
2017.03 | 09 | F.01U.303.998
0-1023
Program Entry Guide
Control Panel
Bosch Security Systems, Inc.

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the B9512G and is the answer not in the manual?

This manual is also suitable for:

B8512gB8512g-eB9512g-e

Table of Contents

Save PDF