en | Panel Wide Parameters
Off by 30 Minutes or Less
When the control panel time is off by 30 minutes or less, it adjusts its timekeeping to make up
the difference. If the control panel's time is slow, the control panel counts seconds faster than
once per second. If the control panel's time is fast, the control panel counts seconds slower
than once per second. The modified counting of seconds remains in effect until the control
panel time is in synchronization with the central station receiver time. Since every second
occurs, there are no skips in time. No Skeds scheduled to be run are skipped.
Off by More than 30 Minutes
When the control panel time is off by more than 30 minutes, it checks its date. If the day,
month, or year is different from the central station receiver, the control panel sets its date and
time to the central station receiver date. The control panel then sets its time to the Central
Station receiver time. Due to a forward change in time, scheduled Skeds might not run. Due to
a backward change in time, scheduled Skeds might be repeated.
RPS Menu Location:
Panel Wide Parameters > Communicator > Time Synchronization
3.11

Enhanced Communication

3.11.1

Reporting Format

Default: Modem4
Selections:
This parameter sets the central station receiver format for transmission of reports.
When using telephone or network reporting, event reports can be routed to a central station
receiver using either Contact ID or Modem4 format. Contact ID and Modem4 reports identify
points and passcode User ID codes at the receiver. When reporting point events, Modem4 also
sends point text as programmed in Point Assignments.
Notice!
When using Contact ID, you must disable Time Synchronization, page 61
RPS Menu Location:
Panel Wide Parameters > Enhanced Communications > Reporting Format
3.11.2

Network Address

Default: Blank
Selections: IPv4 Address (0.0.0.0 to 255.255.255.255) or Hostname (Up to 255 Characters)
This parameter sets the IP address for Destinations 1-4.
There are four available Destinations to route events to.
If events are going to be routed to an IP Address (in a Private Local or Wide Area Network
application), you need to determine which Destination to use (Destination 1 – Destination 4)
and enter the appropriate IP Address for that Destination.
Whenever the central station requests a change to the Network Address, page 62 or Port
Number, page 63 configured in the control panel, the central station receiver might
resynchronize the control panel's anti-replay/anti-substitution static key.
2017.03 | 09 | F.01U.303.998
Contact ID - Use this format when the central station receiver only supports contact ID.
Modem4 - The control panel sends expanded Modem4 Communication Format reports to
the central station receiver.
Program Entry Guide