194 en | Points
–
–
This parameter allows a controlled point to generate a watch tone as long as the area is
disarmed and not being faulted into a trouble or alarm event.
Notice!
You can only hear the watch tone on a keypad where the current area is the point's assigned
area.
You can only hear the watch tone on a keypad where the current area is the point's assigned
area.
RPS Menu Location
Points > Point Indexes > Watch Point
10.3.14
Output Response Type
Default: 0
Selections:
–
–
–
This parameter causes an output to respond when a corresponding point with the same
number is faulted.
Outputs used for this function must not be shared with any other point, keypad, sked, area, or
panel output functions. Sharing can cause errors in output operation.
RPS Menu Location
Points > Point Indexes > Output Response Type
10.3.15
Display as Device
Default: No
Selections:
–
–
Use this parameter to cause the to display CHECK DEVICE once a point is off normal or is
acknowledged after going into alarm.
This parameter can be used for devices that have a dry contact output which faults a point
once the device is in a trouble event.
RPS Menu Location
Points > Point Indexes > Display as Device
10.3.16
Local While Disarmed
Default:
–
–
Selections:
2017.03 | 09 | F.01U.303.998
Yes: This point activates Watch Mode responses if it is faulted when the control panel is
in Watch Mode.
No: Do not activate Watch Mode responses for this point.
0- Point state does not affect the operation of the corresponding output.
1- The output corresponding with this point activates when the point is faulted to any off
normal state, even if the point is bypassed. The output automatically resets when the
point is returned to normal.
2- The output corresponding with this point latches when the point goes into an alarm
condition. This output remains on steady output until the alarm is cleared from the
keypad display.
Yes. Display [CHECK DEVICE] when this point is off normal.
No. Do not display [CHECK DEVICE] when this point is off normal.
Point Index 9, 12: Yes
All other Point Indexes: No