B9512G/B8512G (B9512G‑E/B8512G‑E)
en
Installation Manual

Advertisement

Table of Contents
loading

Summary of Contents for Bosch B9512G-E

  • Page 1 Control Panels B9512G/B8512G (B9512G‑E/B8512G‑E) Installation Manual...
  • Page 3: Table Of Contents

    Safety 1.2.1 Lightning 1.2.2 Earth ground 1.2.3 Power Introduction About documentation 2.1.1 Related documentation Bosch Security Systems, Inc. product manufacturing dates System overview Parts list Control panel capacities Features 3.3.1 SDI2 interconnect wiring 3.3.2 Points 3.3.3 Areas and accounts 3.3.4 Digital communication 3.3.5...
  • Page 4 Shortcuts and custom functions 9.1.4 Address settings 9.1.5 Supervision 9.1.6 Installation and control panel wiring (keypads) 9.1.7 Sensor loops overview and wiring (B921C/B942/B942W only) 9.1.8 Output wiring (B942/B942W only) 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 5 Off-board points test 13.5 Extra Point events 13.6 Missing point conditions Wireless modules 14.1 B810 receiver 14.1.1 SDI2 address settings 14.1.2 Supervision 14.1.3 Installation and control panel wiring (B810) Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 6 Required values to achieve 180s (ULC)/200s (UL) supervision interval 19.9 Keypad Installer menu 20.1 [1] Program menu (Programming) 20.1.1 [1] Reporting > [1] Phone menu parameters 20.1.2 [1] Reporting > [2] Network menu parameters 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 7 B208 address settings 22.1.2 B299 address settings 22.1.3 B308 address settings 22.1.4 D8128D address settings 22.1.5 D8129 address settings 22.1.6 B901 address settings 22.1.7 B91x address settings 22.1.8 D9210C address settings Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 8 Report format definitions 22.2.2 Device numbers (zzz, dddd) 22.2.3 Communication Trouble device numbers (zzzz) 22.2.4 Special User IDs (uuuu, iiii) 22.2.5 Keypad alarm virtual point numbers (ppp, pppp) 22.3 AutoIP 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 9: Certifications, Approvals, Listings, And Safety

    1.1.6 National Institute of Standards and Technology (NIST) When communicating via a network, listed for Advanced Encryption Standard (AES), Federal Information Processing Standards Publication 197 (FIPS 197). Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 10: Federal Communications Commission (Fcc) Rules

    Part 68 The B430 module by Bosch Security Systems, Inc. is registered with the Federal Communication Commission (FCC) under Part 68, for connection to the public telephone system using an RJ31X or RJ38X phone line connection jack installed by the local telephone company.
  • Page 11: Safety

    Do not use telephone or electrical ground for the earth ground connection. Do not connect other control panel terminals to earth ground. Caution! Avoid electrostatic discharge Always touch the earth ground connection with the icon first, before beginning work on the control panel. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 12: Power

    Routine heavy discharges can lead to premature battery failure. Notice! Use sealed lead acid batteries only The charging circuit is calibrated for lead-acid batteries. Do not use gel-cell or NiCad batteries. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 13: Introduction

    These indicate a hazardous situation which, if not avoided, could result in death or serious injury. Copyright This document is the intellectual property of Bosch Security Systems, Inc. and is protected by copyright. All rights reserved. Trademarks All hardware and software product names used in this document are likely to be registered trademarks and must be treated accordingly.
  • Page 14 Control Panels Click on the Documents tab, and then click the desired language listed to the right of the desired document. Call Bosch Security Systems, Inc., Technical Support (1-800-289-0096) if you need additional assistance. Control panel documents Control Panels (B9512G/B8512G) Release Notes*...
  • Page 15: Bosch Security Systems, Inc. Product Manufacturing Dates

    Located on the documentation CD shipped with the module. Bosch Security Systems, Inc. product manufacturing dates Use the serial number located on the product label and refer to the Bosch Security Systems, Inc. website at http://www.boschsecurity.com/datecodes/. The following image shows an example of a product label and highlights where to find the manufacturing date within the serial number.
  • Page 16: System Overview

    Number of octo-output modules (B308) Number of on-board Ethernet ports (“E” control panel variants do not include an Ethernet port) Number of B426 or B450 modules Number of plug-in telephone communication modules (B430) 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 17: Features

    8 doors using the optional D9210C Access Control Interface Module. The control panel supports up to 16 of the keypads as SDI keypads. Bosch IP cameras use is supplementary in UL Listed systems. Features This section explains the control panel's notable features.
  • Page 18: Digital Communication

    The control panel retains point alarm and trouble events for each area in event memory. You can view event memory on a keypad. Turning an area on clears the event memory for that area. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 19: Programming

    Communication Module, or telephone module), or locally using the control panel’s on-board Ethernet port or USB port. (To program with the USB port connection, use the B99 USB 2.0 Type A Male to Type A Male cable by Bosch.) You can also use a keypad for select programming.
  • Page 20: Recent Closing

    Where the fire alarm transmitter is sharing on-premise communications equipment, the shared equipment must be UL Listed (ITE or fire protective signaling). Model number Keypads B915/B915I* B920* B921C* B925F* B926F* B930* B942/B942W* 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 21 Suitable for use on approved applications in the USA. D1640-CA Suitable for use on approved applications in Canada. Enclosures BATB-40/ BATB-80 B8103 D8103 D8109 D8108A D8004 Expansion modules B208 B299 B308 B600 D125B D129 Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 22 Communicators B426 B430 B440 B441 B442 B443 B444 B450 Accessories D113 D130 D132A D133 D134 D161 Suitable for use on approved applications. D162 Suitable for use on approved applications. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 23 PIR Motion Sensor [18 m (60 ft)] with POPIT ZX970 PIR/Microwave Motion Sensor [+1.7°C (+35°F)] with POPIT 5110/4001-42 Rothenbuhler High Security Bell B810 wireless receiver compatible accessories Refer to RADION receiver SD (B810) Installation Guide. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 24 Multiple-Condition On/Off Pendant Transmitter EN1233D Necklace Pendant Transmitter (Double-button) EN1233S Necklace Pendant Transmitter (Single-button) EN1235D Beltclip Pendant Transmitter (Double-button) EN1235DF Fixed-location Transmitter (Double-button) EN1235S Beltclip Pendant Transmitter (Single-button) EN1235SF Fixed-location Transmitter (Single-button) 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 25: Compatible Ul Listed Synchronization (Sync) Modules And Strobes

    Wheelock 24 VDC external powered devices System Sensor control panel powered devices System Sensor 12 VDC external powered devices System Sensor 24 VDC external powered devices High current settings reduces the quantity. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 26 24 VDC, 15/75 cd, Red NS-24MCW-FR 24 VDC, Variable cd, Mini, Wall-mount, Red NS-24MCW-FW 24 VDC, Variable cd, Mini, Wall-mount, White RSS Series Strobes RSS-241575W-FR 24 VDC, 15/75 cd, Synchronized, Red 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 27 LED LF HN RED,2W,WALL,24V,NO LTR LLFHNW-N LED LF HN WHT,2W,WALL,24V,NO LTR LLFHSR LED LF HN STR,RED,2W,WALL,24V,110CD, FIRE LLFHSW LED LF HN STR,WHT,2W,WALL,24V,110CD, FIRE LLFHSR-AL LED LF HN STR,RED,2W,WALL,24V,110CD, ALERT Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 28 24 VDC, Selectable 135/185 cd, Wall, White ZRS-MCC-FR 24 VDC, Selectable 15/30/75/95 cd, Red ZRS-MCC-FW 24 VDC, Selectable 15/30/75/95 cd, White ZRS-MCCH-FR 24 VDC, Selectable 115/177 cd, Red ZRS-MCCH-FW 24 VDC, Selectable 115/177 cd, White 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 29 UL requirement If you use 24 V devices, you must use a UL 1481 regulated power-limited power supply and a D130 Relay Module. Refer to the D130 Installation Instructions. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 30: Installation Checklist

    Install, operate, test, and maintain this device according to the control panel Installation and System Reference Guide. Failure to follow these procedures may cause the device not to function properly. Bosch Security Systems Inc. is not responsible for any devices that are improperly installed, tested, or maintained.
  • Page 31: Control Panel Installation

    Align the Holes to attach the mounting skirt to hooks with the hooks. Slide the control panel down so that it hangs on the hooks. Secure the mounting skirt screw. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 32: Earth Ground

    Set your digital voltmeter (DVM) to measure VDC. Connect the red DVM lead to control panel Terminal 10, and the black DVM lead to Terminal 9. Compare this voltage to the following table. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 33: Control Panel To Module Wiring Overview

    If SDIx is configured for SDI2, use either SDI2 bus. Using terminal wiring in parallel Notice! Wire size For terminal wiring, use 18 AWG to 22 AWG (1.0 mm to 0.6 mm) wire. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 34 COM/B COM/B ZONEX ZONEX TAMPER TAMPER RESET RESET ZONEX TMPR Using interconnect wiring Notice! More information For more information on interconnect wiring, refer to SDI2 interconnect wiring, page 17. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 35 SDI2 devices daisy chained with interconnect wiring MOD-2 MODULE RELEASE MOD-1 PWR+/R PWR+/R olice olice ting ting COM/B COM/B PWR+/R PWR+/R COM/B COM/B ZONEX ZONEX TAMPER TAMPER RESET RESET ZONEX TMPR Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 36: Power Supply

    Maintain a 0.250 in (6.4 mm) space between the battery terminals, battery wiring, and all other wiring. Battery wiring cannot share the same conduit, conduit fittings, or conduit knockouts with other wiring. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 37: Battery Status Led

    Allow the control panel to charge the battery while you complete the installation. 6.1.2 BATTERY STATUS LED The control panel includes one BATTERY STATUS LED with 4 LED patterns to indicate the battery status. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 38: Battery Maintenance

    Control Panel Battery Restored to Normal (302) report in the Contact ID format. 6.1.5 Battery charging circuit float charge The float voltage for the battery charging circuit is 13.65 VDC when operating within load range. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 39: Battery Discharge And Recharge Schedule

    B8512G. 4 The power supply draws approximately 15 mA (+/- 1 mA) from the control panel. For detailed instructions, refer to the corresponding document listed in Related documentation, page 13. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 40: Sdi2 Address Settings

    16 AWG (1.5 mm) wire when making the connection Use a grounding rod or a cold water pipe. Run wire as close as possible to grounding device. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 41: Powered Device And Battery Wiring

    When you wire the output of a B520 to a SDI2 module, the B520 provides power to the module while passing through data between the control panel and the module. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 42 You must wire BATT 1. You must wire BATT 2 if you configure the B520 for two batteries. When you use BATT 2, both batteries must have the same rating. Maximum standby power cannot exceed 36 Ah. Callout ᅳ Description 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 43 1 ᅳ B520 Auxiliary Power Supply Module 2 ᅳ Battery 2 (BATT 2) - (12 V nominal lead acid) 3 ᅳ Battery 1 (BATT 1) - (12 V nominal lead acid) Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 44: Telephone Communications

    13. Notification The B430 module by Bosch Security Systems, Inc. is registered with the Federal Communication Commission (FCC) under Part 68, for connection to the public telephone system using an RJ31X or RJ38X phone line connection jack installed by the local telephone company.
  • Page 45: Diagnostic Leds

    After installation, make sure that the control panel: – Seizes the line – Gets a dial tone – Reports correctly to the receiver – Releases the telephone line to the in-house telephone system Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 46: Telephone Line Monitor

    The called party must go on hook (hang up) for a fixed interval before a dial tone is available for a new call. This interval varies with telephone company equipment. Control panel 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 47: Communication Failure

    One hour after a COMM FAIL event, the control panel attempts to send a COMM RSTL event. If a communication failure still occurs, the keypad trouble sounds again. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 48: Ip Communications

    3. If the control panel does use the Ethernet for IP communication, power down the control panel and remove the Ethernet cable that connects the control panel to the network. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 49: On-Board Ethernet Diagnostic Leds

    Flash pattern Function Communicating at 100 Mb. On Steady Communicating at 10 Mb. Tab. 8.2: 100BASE-T LED descriptions Flash pattern Function Plugged into an Ethernet network. On Steady Communication in progress. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 50: Conettix Plug-In Cellular Modules

    Communication supervision. The control panel supervises the communication path by polling the central station receiver. If the poll is missed from either side, a communication fault is declared both at the control panel and the central station receiver. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 51: B426 Module Faults

    Use either the terminal strip wiring or interconnect wiring to the control panel. Do not use both. When you connect multiple modules, you can combine terminal strip and interconnect wiring connectors in parallel. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 52: Diagnostic Leds

    Communication error state. Indicates a bus communication error. The module is not receiving commands from the 3 quick flashes every 1 sec control panel. Trouble state. Indicates a trouble condition exists. On Steady 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 53: Local Programming

    If the module does not use the Ethernet for IP communication, skip to the next step. If the module does use the Ethernet for IP communication, power down the module and remove the Ethernet cable that connects it to the network. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 54: B450 Conettix Plug-In Communicator Interface

    Inserting the cellular module Install a SIM card, if required by the cellular module. Push the plug-in cellular module into the B450 until you hear the module “click” into position. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 55: Diagnostic Leds

    Flash pattern Indication Normal state. Flashes once every 1 second Communication error state. Error on the bus between the module and the control panel. 3 quick flashes every 1 second Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 56: Compatible Receivers For Ip Communication

    Receiver/Gateway CPU version D6200 version Conettix D6600 Communications Receiver/Gateway 01.03.02 1.35 (with D6641 line cards installed only) Conettix D6100IPv6 Communications Receiver/Gateway 61.10.00 2.10 Conettix D6100i Communications Receiver/Gateway 61.04.00 1.35 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 57 Receiver/Gateway CPU version D6200 version Conettix D6600 Communications Receiver/Gateway 01.11.00 2.20 (with D6641 line cards installed only) Conettix D6100IPv6 Communications Receiver/Gateway 61.11.00 2.20 Conettix D6100i Communications Receiver/Gateway 61.11.00 2.20 Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 58: Keypads, Keyswitches, Keyfobs And Transmitters

    The keypad is a fully supervised SDI2 device for fire applications. The keypad display and sounder alert to a fire alarm, a fire trouble, or fire supervisory events as they occur. The keypad includes fire status indicators and fire function keys. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 59: B921C Two-Line Capacitive Keypad With Inputs

    Shortcut so that the users can easily run the function from the keypad. The user must have the appropriate authority level enabled to use the custom function. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 60: Address Settings

    Connect SDI keypads to the SDIx bus by parallel wire run from the control panel to each keypad, wire from keypad to keypad, or a combination of the two. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 61: Sensor Loops Overview And Wiring (B921C/B942/B942W Only)

    COM, and 1, 2, 3, or 4. Wire resistance on each sensor loop must be less than 100 Ω with the detection devices connected. The terminal strip supports 12 to 22 AWG (0.65 to 2 mm) wires. Bosch Security Systems, Inc. Installation Manual...
  • Page 62: Output Wiring (B942/B942W Only)

    LEDs. Refer to Outputs in RPS Help or in the Installer Services Portal programming tool (available in Europe, Middle East, Africa, and China) Help. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 63: Operation

    3 ᅳ Common 7 ᅳ Momentary short on the circuit toggles the arming state 4 ᅳ Point input Notice! UL requirement Keyswitches are not intended for use in UL listed systems. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 64: Radion Keyfobs And Inovonics Pendant Transmitters

    Africa, and China), you can assign two custom functions to a RADION keyfob FB, allowing a user to initiate the functions wirelessly. For more information, refer to RPS Help or the Installer Services Portal programming tool Help. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 65: On-Board Outputs

    Programmable output normally closed, switches power off when the Sensor Reset command is executed. SDIx Power+ / R Powers serial device interface (SDI) keypads, or use to power serial device interface 2 (SDI2) devices, such as keypads and expansion modules. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 66: Continuous Power Outputs

    Nominal power output. Use the power at Terminals 6 and 7 to power bells, siren drivers, piezoelectric sounders, electronic horns, or other devices. Programming determines the format of the output and the conditions that activate it. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 67: Terminal 8

    The USB POWER STATUS LED lights when power to the USB is turned on. You can disable USB at any time. Use the Installer menu or press the control panel RESET button 3 times. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 68: Off-Board Outputs

    With any failure to receive an expected response from the module, all keypads show a system fault. The control panel sends a module trouble report to the central station (if configured for module trouble reports). 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 69: Installation And Control Panel Wiring (B308)

    The B600 Retrofit (ZONEX) module enables the use of ZONEX devices on the B9512G/ B8512G. The B600 module connects to the control panel through a proprietary connection (cable provided with module). The control panel supports one B600. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 70: Installation And Control Panel Wiring (B600)

    Use the supplied mounting screws to secure the module. Wiring the module to the control panel PWR+/R COM/B PWR+/R COM/B ZONEX TAMPER RESET Callout ᅳ Description 1 ᅳ ZONEX connection cable 2 ᅳ SDI interconnect cable 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 71: D8129 Octo-Relay Module

    For more information, refer to D8129 address settings, page 168. Installation For detailed instructions, refer to the corresponding document listed in Related documentation, page 13. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 72: On-Board Points

    The total resistance for the wire length and contacts, excluding the end-of-line (EOL) resistor, must not exceed 100 Ω. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 73: Dual Eol Resistor Circuit Style

    For the dual EOL resistor circuit style order ICP-1K22AWG-10, package of 10 1.0 kΩ EOL resistors. Point Callout - Description 1 - Point sensor loop terminals 2 - Normally closed device (contact) Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 74: Point Response Time

    (B901 or D9210C) set to an SDI address. Set Debounce to 1.64 seconds for these points. Debounce does not apply to points with the Point Source configured as Wireless, Output, or IP Camera. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 75: Off-Board Points

    Installation and control panel wiring (B208) Calculate power consumption Make sure that there is enough power for the module and the other powered devices that you want to connect to the system. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 76 PWR A B COM PWR+/R PWR+/R PWR+/R PWR+/R olice olice olice olice PWR A B COM ting ting ting ting COM/B COM/B COM/B COM/B PWR+/R PWR+/R PWR+/R PWR+/R COM/B COM/B COM/B COM/B 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 77: Sensor Loops Overview And Wiring

    UL does not permit normally closed loops for commercial fire applications. Notice! Optionally use these points for household fire applications. You can connect four-wire detectors to these points, for example. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 78 Callout ᅳ Description 1 ᅳ Module 2 ᅳ Sensor loop 3 ᅳ EOL Resistor – 1.0 kΩ (2.0 kΩ and No EOL optional) 4 ᅳ Wiring to additional sensor loops 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 79: B299 Popex Module

    For valid point numbers, refer to B299 address settings, page 165. 13.2.2 Supervision The control panel automatically supervises any B299 on the SDI2 bus when an associated point has its source programmed for POPEX. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 80: Installation And Control Panel Wiring (B299)

    Wire resistance on each sensor loop must be less than 100 Ω with the detection devices connected. The terminal strip supports 12 to 22 AWG (2.0 to 0.6 mm) wires. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 81: B600 Retrofit Zonex Module

    Hold the module mounting brackets onto the inside of the enclosure. Match the bracket holes to a 3-hole mounting pattern on the enclosure Use the supplied mounting screws to secure the module. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 82: D8125 Expansion

    Refer to On-board outputs, page 65. Caution! Remove all power (AC and battery) before making any connections. Failure to do so might result in personal injury and/or equipment damage. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 83: D8128D Octopopit Eight-Point Expander

    Requirements for Fire Initiation applications You can connect the D125B Dual Powered Loop Interface Module outputs directly to the point inputs on the D8128D. Use the D125B to connect two-wire smoke detectors. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 84: Off-Board Points Test

    An interior motion detector point is missing and the area is turned on (armed). The control panel makes a Missing Alarm event. Non-fire, 24-hour points always make a Missing Alarm event. Fire points always make a Missing Fire Trouble event. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 85: Wireless Modules

    Use the address switch to set the module to address 1. Use the provided anchors and screws to mount the module base on the wall. Pull the wiring through the mounting plate. Put the module on the base. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 86: B820 Sdi2 Inovonics Interface Module

    Make sure that there is enough power for the module and the other powered devices that you want to connect to the system. Refer to On-board outputs, page 65. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 87 MODULE RELEASE MOD-1 PWR+/R PWR+/R olice olice ting ting COM/B COM/B PWR+/R PWR+/R COM/B COM/B Callout ᅳ Description 1 ᅳ Control panel 2 ᅳ Module 3 ᅳ Terminal strip wiring Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 88: Access Control

    B901 door controller The B901 Access Control Interface Module is a fully supervised, addressable SDI/SDI2 bus device that allows access control integration for Bosch compatible control panels. This module offers 14 programmable levels of access authority. Authority for access is controlled by the user level, the group of the user, the time of day, the door state, and the area armed state.
  • Page 89: Installation And Control Panel Wiring (B901)

    The D9210C is a four-wire SDI powered device providing connections for an access door point and door strike. Each D9210C supports one door to control access. You can independently configure each access door. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 90: Card Reader Wiring

    13. 15.3 Card reader wiring To wire the access control module to a card reader, refer to the card reader instructions printed on or shipped with the reader. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 91: Program And Test The Control Panel

    The Panel Communication window opens. Click Connect and send the configuration programming to the control panel. Click Disconnect when the programming is complete. For more information, refer to RPS Help. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 92: Program The Control Panel With The Installer Services Portal Programming Tool

    Have a point profile not set to Disabled (must be non-zero) – Are not service bypassed – Are not invisible points – Have a point type of Keyswitch maintained, Keyswitch momentary, Open/Close Point, Fire, Aux AC Supervision, or Gas 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 93: Intrusion Walk Test

    – The test does not log any Extra Point events. Performing a service walk test Choose a keypad to conduct the test. Ensure that all areas are off (disarmed). Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 94: Invisible Walk Test

    To view the list of points, press Enter or View untested points. To scroll through the list of points, use /Previous or /Next. When you fault a point (open a door for example), the keypad emits a brief tone and shows the name. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 95: Control Panel Board Overview

    Installing the enclosure, page 31 10 ᅳ Zonex module connector location SDI and ZONEX wiring, page 100 11 ᅳ Sensor loop terminals for points 1 to 8 On-board points, page 72 Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 96 On-board Ethernet connection, page 48 13 ᅳ On-board Ethernet connector 14 ᅳ LINK LED (yellow) 15 ᅳ USB connector USB power, page 67 16 ᅳ USB POWER STATUS LED 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 97: System Wiring Diagrams

    All terminals except Outputs A (1), B (2), and C (3) (Terminals 6, 7, and 8) are supervised. For proper supervision, do not loop wire under terminals. Break the wire run to provide supervision of connections. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 98: Power Supply Side Wiring

    12 ᅳ Listed audible signaling devices rated at 12.0 VDC nominal (do not use vibrating type horns) 6 ᅳ B520 Auxiliary Power Supply Module 13 ᅳ To earth ground 7 ᅳ To powered devices 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 99: Input Points Wiring With D125B, D130, Or D129

    18.3 Input points wiring with or without EOL resistors Notice! EOL resistors For the dual EOL resistor circuit style order ICP-1K22AWG-10, package of 10 1.0 kΩ EOL resistors. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 100: Sdi And Zonex Wiring

    SDI and ZONEX wiring Notice! Install Fire and Intrusion devices only on separate circuits. Refer to the ICP-SDI-9114 Installation Instructions. All external connections except Terminal 5 (battery positive) are power limited. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 101 *The number of D8129 Octo-relay modules allowed for each ZONEX terminal on the B600 is limited by the number of D8128D OctoPOPITs connected to the same terminal. Refer to the D8128D Installation Guide or the D8129 Operation and Installation Guide for detailed instructions. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 102: Sdi2 Devices General System Wiring

    SDI2 modules use the SDI2 bus to communicate with one another. You can wire modules via home run, daisy chain, or single level T-tap anywhere on the SDI2 bus. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 103 – Refer to the SDI2 device or keypad documentation for the allowable maximum distance from the control panel. – Maximum overall cable lengths are listed in the following table: Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 104: 2-Wire Smoke Wiring (D125B)

    6 ᅳ Supervised smoke detector to B LOOP negative panel 2 ᅳ Supervised connection to Zone B power from an on- 7 ᅳ Supervised smoke detector to A LOOP negative board point of the control panel 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 105 8 ᅳ Supervised smoke detector to B LOOP positive board point of the panel 4/5 ᅳ Connection to common the control panel (one 9 ᅳ Supervised smoke detector to A LOOP positive connection only) Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 106: Approved Applications

    Do not install the EVD sensor within 6.4 mm (0.25 in) of the components or traces of the printed circuit assembly. Battery connections – Using a D122 Dual Battery Harness, connect two 12 V 7 Ah batteries in the control panel enclosure. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 107 15 ᅳ End-of-line (EOL) resistor 8 ᅳ Alarm input point 16 ᅳ Safe Use Terminals 1 through 8. (Select only one.) Use a D113 Battery Lead Supervision Module to supervise the battery connections Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 108 Systems. Refer to RPS Help, the Installer Services Portal programming tool (available in Europe, Middle East, Africa, and China) Help, or the control panel’s Program Entry Guide for programming information. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 109: Fire Applications

    Consult the individual component specification and installation documents to determine suitability. Notice! UL requires that the control panel supervises any device powered from a power output. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 110 B308 Octo-output Module – D125B Powered Loop Interface Module (2-wire smoke detector module) – D129 Dual “Class A” Initiation Circuit Module (4-wire smoke detector) – D9127T/U POPITs – On-board points 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 111: Enclosures

    For battery calculations, refer to Standby battery requirements and calculations, page 114. Notice! Test weekly Perform a fire test once each week. 19.1.4 Enclosures Mount the control panel assembly in any of the Bosch Security Systems, Inc. enclosures listed: – D2203 Enclosure – B8103 Universal Enclosure/D8103 Universal Enclosure –...
  • Page 112 Suitable for use on approved applications. D1640 Required for all UL applications. D1640-CA Required for all cUL applications. Enclosures BATB-40/ BATB-80 D8004 B8103/D8103/ D8109 Enclosure D8108A Enclosure Expansion modules B208 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 113 Required for MUX devices. D8128D D8129 Optional. For remote annunciation of system functions. D8130 D9127U/T Wireless B810 B820 Communicators B426 B430 B440 B441 B442 B443 B444 B450 Accessories D113 D130 D132A Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 114: Standby Battery Requirements And Calculations

    Current (mA) Current (mA) Model Number Each Total Each Total Each Total Used Unit Unit Unit B9512G/ ______ =190 =190 =265 B8512G B299 ______ xQty =______ xQty =______ xQty =______ 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 115 =______ xQty =______ D192G ______ xQty =______ xQty =______ xQty =______ D1255RB/ ______ xQty =______ xQty =______ xQty =______ D1255 D1256RB/ ______ xQty =______ xQty =______ xQty =______ D1256 Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 116 One D1218 Battery=17.2 or 18 Ah – Two D1218 Batteries=34.4 or 36 Ah Application Standby time (in hours) Alarm time (in minutes) minimum minimum Residential Burglary Proprietary Burglary Central Station (Bank) Central Station (Mercantile) 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 117: Household Fire Warning Equipment

    _________ Refer to previous table. Value = Minutes of alarm operation/60 Total Ah requirements must not exceed the Ah capacity of batteries: – One D126 Battery = 7 Ah Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 118: Ul 365 - Police Station Connected Burglar Alarm Units And Systems

    Area # Delay Restorals = No (Restoral report is sent when point restores.) 19.7 Required programming to meet UL 864 This section identifies the programming requirements you must make in order to comply with UL 864 Commercial Fire applications. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 119 Enter 1:00 AC Fail Display 10 to 300 seconds 10 to 200 seconds AC Tag Along Yes / No Set to Yes AC/Battery Buzz Yes / No Set to Yes Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 120 Sked## Date mm/dd Set to No Sked## Sunday Yes / No Set to Yes Sked## Monday Yes / No Set to Yes Sked## Tuesday Yes / No Set to Yes 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 121 Do not program No Keypad Wide, Custom, No Keypad Function Lock (within the Yes / No Keypads section Reset Sensors Disable/Enable/Passcode Protect Enable Fire Test Disable / Enable / Passcode Protect Enable Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 122: Required Values To Achieve 180S (Ulc)/200S (Ul) Supervision Interval

    Supervision Time set to Custom, Poll Rate set to 89, ACK Wait Time set to 15, and Retry Count set to 5 19.9 Conduct testing monthly, with the primary de-energized. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 123: Keypad Installer Menu

    Press and hold the control panel RESET button until the Heartbeat LED flashes fast. The keypad shows SERVICE MODE and prompts for the installer passcode. Enter your installer passcode and press Enter. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 124 Press [2] Enhanced Comm Parms. – Go to [1] Programming Menu > [1] Reporting > [2] Network > [2] Enhanced Comm Parms. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 125 Srvc Byp menu Versions menu Cloud menu USB Power menu Exit User menu trees Menu tree The following graphics show the menu tree for the B94x / B93x keypads. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 126 Turn Off Select Area Call Via Phone Go to Area Extend Close Bypass Firmware Points Bypass Unbypass Points Cycle Door Srv Bypass Unlock Door Access Lock Door Secure Door 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 127 View Log Set Date/ Time Format Schedule Brightness Volume Keypad Keypress Dflt Text Nightlight Presence Menu tree The following graphics show the menu tree for the B92x / B91x keypads. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 128 6: Update Firmware 1: Bypass Points 5: Bypass 1: Cycle Door 7: View Serv 2: Unbypass Bypassed Points 2: Unlock Door 8: Access 3: Lock Door 4: Secure Door 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 129 – Save. B91x/B92x keypads typically use Enter to save. The B93x/B94x keypads typically use Save to save. The B94x keypad uses the key to save from the Qwerty keyboard. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 130: Program Menu (Programming)

    Go to [1] Programming Menu > [1] Reporting > [1] Phone. The keypad shows the phone number and phone format for the phone destination. /Previous or /Next to go to the destination you want to edit. Depending on keypad model: 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 131: Reporting > [2] Network Menu Parameters

    Depending on keypad model: Press Enter and then press Disable or Enable. -or- Press Enter. Press Save or Enter. The keypad shows Parameter saved. Escape from the menu. Network Address Port Number Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 132: Reporting > [3] Routing Menu Parameters

    Use routing to program primary and backup destinations over standard telephone lines, local area network (LAN) or wide area network (WAN). In this menu, you can designate the primary and backup destinations for up to four routes. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 133: Reporting > [4] Personal Note Menu Parameters

    In this menu, you can add a phone number or email address to each personal notification identifier (1 through 32). Notification Phone number or email address Number Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 134 ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ Personal Note Enter the installer passcode, and then open the [1] Installer Menu. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 135: Network > [1] Ethernet > (Choose The Bus Module Or On-Board) > [1] Module

    Go to [1] Programming Menu > [2] Network > [1] Ethernet > (choose the bus module or on-board) > [1] Module Parameters > [2] UPnP Enable. The keypad shows the UPnP current configuration. Depending on the keypad model: Press Yes or No. -or- Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 136: Network > [1] Ethernet > (Choose The Bus Module Or On-Board) > [2] Address

    Press Edit or Enter to edit the port number. Delete the existing number, if necessary, and then enter the new number. Press Save or Enter. The keypad shows Parameter saved. Escape from the menu. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 137: Network > [1] Ethernet > (Choose The Bus Module Or On-Board) > [3] Dns

    B450 module. Module 1 settings Module 2 settings Access Point Name _______________________________ _______________________________ Access Pt Username _______________________________ _______________________________ Access Pt Passcode _______________________________ _______________________________ SIM PIN _______________________________ _______________________________ Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 138: Rps > [1] Rps Passcode Menu Parameters

    Press Edit or Enter to edit the RPS passcode. Delete the existing number, if necessary, and enter the new number. Press Save or Enter. The keypad shows Parameter saved. Escape from the menu. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 139: Rps > [2] Rps Phone Number Menu Parameters

    Press Edit or Enter to edit the RPS port number. Delete the existing number, if necessary, and then enter the new number. Press Save or Enter. The keypad shows Parameter saved. Escape from the menu. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 140: Area Options Menu Parameters

    ______________ ______________ Area 29* Area 30* Area 31* Area 32* Area On Yes/No Yes/No Yes/No Yes/No Account Number ______________ ______________ ______________ ______________ *Supported by the B9512G only. Area State 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 141: Keypad Menu Parameters

    Keypad 1 No keypad / B91x / B92x / B93x / No Device / Area Wide / Acct Wide / B94x / D1255 / D125xRB / D126x Panel Wide Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 142 Keypad 19* No keypad / B91x / B92x / B93x / B94x No Device / Area Wide / Acct Wide / Panel Wide Keypad 20* No keypad / B91x / B92x / B93x / B94x No Device / Area Wide / Acct Wide / Panel Wide 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 143 Press Save or Enter. The keypad shows Parameter saved and then asks if you would like to edit the scope. Press Edit or Enter to edit the type. Depending on keypad model: Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 144: Users Menu Parameters

    Point Profile. You must use RPS or the Installer Services Portal programming tool (available in Europe, Middle East, Africa, and China) to configure the Point Profile parameters. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 145 Output Response Type __(0)__ __(0)__ __(0)__ __(0)__ __(0)__ __(0)__ __(0)__ __(0)__ Display as Device Local While Disarmed Local While Armed Disable Restorals Force Arm Returnable Bypass Returnable Bypassable Swinger Bypass Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 146 Keyswitc Keyswitc Open/ Circuit Style Follower Close Maintain Momenta Entry Delay _ (30)_ _ (30)_ _ (30)_ _ (30)_ _ (30)_ _ (30)_ _ (30)_ _(30)_ Entry Tone Off 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 147 Point Profile Text defaults (the second language text defaults are blank): Point Profile 17 Point Profile 18 Gas: Supervisory Point Profile 19 Aux AC Supervision Point Profile 20 Part On: Watch Off Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 148 Display as Device Local While Disarmed Local While Armed Disable Restorals FA Returnable Bypass Returnable Bypassable Swinger Bypass Report Bypass at Occurrence Defer Bypass Report Cross Point Alarm Verify Resettable 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 149 _(30)__ _(30)__ _(30)__ _(30)__ Entry Tone Off Silent Bell Ring Until Restored Audible After Two Fails Invisible Point Buzz on Fault ______ ______ ______ ______ ______ ______ ______ ______ Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 150 (25) ____ _____ ____ Onboard (13) ____ _____ ____ Onboard (7) ____ _____ ____ Onboard (7) ____ _____ ____ Onboard (7) ____ _____ ____ Onboard (7) ____ _____ ____ 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 151 Enter the point number and press Enter, or use /Previous or /Next to go to the desired point. Press Edit or Enter to edit the profile for the selected point. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 152: Disable Programming Menu

    /Previous or /Next to scroll through the list of wireless points, and go to the point for which you want to enroll a device, or simply enter the point number. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 153: Rf Point Menu> [2] Replace Point Rfid

    Start with address 8 before adding additional repeaters. Press Enter to add the repeater. The keypad instructs you to tamper the repeater. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 154: Rf Repeater Menu > [2] Replace Repeater

    Go to [2] Wireless > [3] RF Diagnostic Menu > [1] RF Point Diagnostic > [2] Point Signal. /Previous or /Next to scroll through the list, and go to the point for which you want to view diagnostic information, or enter the point number. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 155: Rf Diagnostic Menu > [2] Rf Repeater Menu

    Name:, IPv4 Source IP:, IPv6 Source IP:, MAC Addr:. (Use /Next to scroll through, if necessary.) When finished viewing the information, escape from the menu. Connection Enter the installer passcode, and then open the [1] Installer Menu. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 156: Cellular Menu

    /Next. The keypad shows the Cloud configuration, which is one of the following: – Not Available – Enabled on Ethernet – Enabled on Cellular – Enabled on Ethernet and Cellular 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 157: Service Bypass (Serv Byp) Menu

    Press the icon or softkey for the item for which you want view the version. -or- /Previous or /Next to scroll through the list of items for which you can view the version. Press Enter to view the version. Escape from the menu. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 158: Cloud Menu

    Go to [7] USB Power. The keypad shows the current status, USB Power is on or USB Power is off. Depending on keypad model: Press the icon or softkey for the desired option. -or- Press Enter to change the status. Escape from the menu. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 159: Specifications

    SDI bus A: 9 VDC 4572 m (15000 ft) maximum SDI bus B: 9 VDC 4572 m (15000 ft) maximum SDI2 bus SDI2 bus A: 12 VDC nominal (7500 ft) maximum Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 160: Wire Requirements

    < 200 mA 21.1 Wire requirements Terminal label Terminal description Requirements 18 AWG to 14 AWG (1.02 mm to 1.8 mm) 18 AWG to 14 AWG (1.02 mm to 1.8 mm) 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 161 Terminal accommodates 22 AWG to 14 AWG (0.65 mm to 1.8 mm), use appropriate wire size based on current BATTERY - Bosch supplied wire lead, included with control panel. BATTERY + Output A (1) Terminal accommodates 22 AWG to 14 AWG (0.65 mm to 1.8 mm), use appropriate wire size based on current...
  • Page 162 1.8 mm), use appropriate wire size based on loop resistance less than 100 Ω ZONEX ZONEX Bosch supplied wire, included with the optional B600 SDIx COMMON Terminal accommodates 22 AWG to 14 AWG (0.65 mm to 1.8 mm), use appropriate wire size based on peripheral...
  • Page 163: Appendix

    151 - 158 161 - 168 171 - 178 181 - 188 191 - 198 201 - 208 211 - 208 221 - 228 231 - 238 241 - 248 Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 164 481 - 488 491 - 498 501 - 508 511 - 508 521 - 528 531 - 538 541 - 548 551 - 558 561 - 568 571 - 578 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 165: B299 Address Settings

    91 - 98 101 – 108 111 – 118 121 – 128 131 – 138 141 – 148 151 – 158 161 – 168 171 – 178 181 – 188 Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 166 421 – 428 431 – 438 441 – 448 451 – 458 461 – 468 471 – 478 481 – 488 491 – 498 501 – 508 511 – 508 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 167: D8128D Address Settings

    Switch 8 to the OPEN position. The B9512G uses Points 9 to 127 on ZONEX 1 and Points 129 to 247 on ZONEX 2. B8512G uses only Points 9 to 99 on ZONEX 1. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 168: D8129 Address Settings

    (D9210C with Fail Safe Unlock) 9,1 to 9,8 Doors 1 through 8 on SDIx bus in Legacy SDI mode (D9210C with Fail Safe Lock) 22.1.7 B91x address settings Address Switches 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 169: D9210C Address Settings

    SDI address setting Keypad display Modem4 UNLOCKED SDI #33 Door #1 UNLOCKED SDI #34 Door #2 UNLOCKED SDI #35 Door #3 UNLOCKED SDI #36 Door #4 UNLOCKED SDI #37 Door #5 Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 170: Sdi Keypad Address Settings

    D1255VFD Keypad / D125xRB Fire Keypad / D126x LCD Keypad address switch settings. Notice! D126x keypads only use addresses 1-8. To access the switch settings, press and hold [0] until the menu changes. Address Switches Encoding Tone ON/ 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 171: Reporting And Device Number Information

    (Assign Card Event) Alarm Aspppp NriaBApppp Burglary 1 130 aa ppp Alarm Cross Point Aspppp NriaBMpppp Burglary 1 130 aa ppp Alarm Exit Error Aspppp Nria/idiiiiEApppp Entry/Exit 1 134 aa ppp Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 172 Towers Cellular Fewer than Two RssssD NpiddddER System Peripheral Trouble 3 330 00 zzz Towers Restoral Restore Cellular Low Signal TssssD NpiddddET System Peripheral Trouble 1 330 00 zzz 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 173 1 302 00 000 Control panel battery missing Tsss9 Battery Missing/Dead 1 311 00 000 Control panel battery Rsss9 Low System Battery 3 302 00 000 restored to normal Restore Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 174 Fire Trouble Restore 3 373 aa ppp Fire Supervision Espppp NriaaFSpppp Fire Supervisory 1 200 aa ppp Fire Supervision from Restore Espppp NriaaFVpppp Fire Supervisory Restore 3 200 aa ppp 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 175 System Peripheral Trouble 3 330 00 Restore Key fob Missing VsD10 NidiiiiUY Latch-Key Supervision 1 642 00 iii Key fob Missing Restoral RsD10 NidiiiiUR Latch-Key Supervision 3 642 00 iii Rest. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 176 PS Over Current 1 312 00 ZZZ Popex Bus Fault Restore RsssD PS Over Current Restore 3 312 00 ZZZ Popex Invalid Popit TsssD PS Over Current 1 312 00 ZZZ 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 177 3 393 aa ppp RF Transmitter Low Battery Tspppp NriaaXTpppp RF Low Battery 1 384 aa ppp RF Transmitter Low Battery TsD10 NidiiiiXT Battery Test Failure 1 309 00 uuu (Key Fob) Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 178 3 333 00 000 missing SDI2 Open Trouble TsssD NpiiddddET Expansion Module Failure 1 333 00 SDI2 Open Trouble Restoral RsssD NpiddddER Expansion Module Failure 3 333 00 Restore 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 179 Expanded Status D6600 CIM for Trouble Present Status Items Test Report - System Off- RsssE Periodic Test - System 1 608 00 000 normal, Non-expanded Status Trouble Present Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 180: Device Numbers (Zzz, Dddd)

    SDI2 Keypads 1-32 01-06 155-160 SDI2 POPEX Modules 1-6 01-08 33-40 SDI Access Modules 1-8 01-32 601-632 SDI2 Access Modules 1-32 516-531 IP Cameras 1-16 OnBrd Control Panel Enclosure 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 181: Communication Trouble Device Numbers (Zzzz)

    RPS or Installer 5002 5002/none “BY RPS” Services Portal programming tool (available in Europe, Middle East, Africa, and China) User Automation User 5003 5003/none “BY AUTOMATION” Keyswitch 5004 5004 “BY KEYSWITCH” Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 182: Keypad Alarm Virtual Point Numbers (Ppp, Pppp)

    IT department before changing the registry. Adding a new registry key, if required Open Notepad. Copy and paste or type the text shown below the instructions. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
  • Page 183 Use Windows Explorer to find the saved file. Double-click the file to add it to the computer registry. Restart the RPS or Installer Services Portal programming tool computer. Text for the AutoIP.reg file: Windows Registry Editor Version 5.00 [HKEY_LOCAL_MACHINE\SYSTEM\CurrentControlSet\Services\Tcpip\Parameters] "IPAutoconfigurationEnabled"=dword:00000001 Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
  • Page 185 Bosch Security Systems, Inc. Bosch Sicherheitssysteme GmbH 130 Perinton Parkway Robert-Bosch-Ring 5 Fairport, NY 14450 85630 Grasbrunn Germany www.boschsecurity.com © Bosch Security Systems, Inc., 2018...

This manual is also suitable for:

B9512gB8512g-eB8512g