Safety 1.2.1 Lightning 1.2.2 Earth ground 1.2.3 Power Introduction About documentation 2.1.1 Related documentation Bosch Security Systems, Inc. product manufacturing dates System overview Parts list Control panel capacities Features 3.3.1 SDI2 interconnect wiring 3.3.2 Points 3.3.3 Areas and accounts 3.3.4 Digital communication 3.3.5...
Page 4
Shortcuts and custom functions 9.1.4 Address settings 9.1.5 Supervision 9.1.6 Installation and control panel wiring (keypads) 9.1.7 Sensor loops overview and wiring (B921C/B942/B942W only) 9.1.8 Output wiring (B942/B942W only) 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
Page 5
Off-board points test 13.5 Extra Point events 13.6 Missing point conditions Wireless modules 14.1 B810 receiver 14.1.1 SDI2 address settings 14.1.2 Supervision 14.1.3 Installation and control panel wiring (B810) Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
Page 6
Required values to achieve 180s (ULC)/200s (UL) supervision interval 19.9 Keypad Installer menu 20.1 [1] Program menu (Programming) 20.1.1 [1] Reporting > [1] Phone menu parameters 20.1.2 [1] Reporting > [2] Network menu parameters 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
1.1.6 National Institute of Standards and Technology (NIST) When communicating via a network, listed for Advanced Encryption Standard (AES), Federal Information Processing Standards Publication 197 (FIPS 197). Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
Part 68 The B430 module by Bosch Security Systems, Inc. is registered with the Federal Communication Commission (FCC) under Part 68, for connection to the public telephone system using an RJ31X or RJ38X phone line connection jack installed by the local telephone company.
Do not use telephone or electrical ground for the earth ground connection. Do not connect other control panel terminals to earth ground. Caution! Avoid electrostatic discharge Always touch the earth ground connection with the icon first, before beginning work on the control panel. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
Routine heavy discharges can lead to premature battery failure. Notice! Use sealed lead acid batteries only The charging circuit is calibrated for lead-acid batteries. Do not use gel-cell or NiCad batteries. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
These indicate a hazardous situation which, if not avoided, could result in death or serious injury. Copyright This document is the intellectual property of Bosch Security Systems, Inc. and is protected by copyright. All rights reserved. Trademarks All hardware and software product names used in this document are likely to be registered trademarks and must be treated accordingly.
Page 14
Control Panels Click on the Documents tab, and then click the desired language listed to the right of the desired document. Call Bosch Security Systems, Inc., Technical Support (1-800-289-0096) if you need additional assistance. Control panel documents Control Panels (B9512G/B8512G) Release Notes*...
Located on the documentation CD shipped with the module. Bosch Security Systems, Inc. product manufacturing dates Use the serial number located on the product label and refer to the Bosch Security Systems, Inc. website at http://www.boschsecurity.com/datecodes/. The following image shows an example of a product label and highlights where to find the manufacturing date within the serial number.
Number of octo-output modules (B308) Number of on-board Ethernet ports (“E” control panel variants do not include an Ethernet port) Number of B426 or B450 modules Number of plug-in telephone communication modules (B430) 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
8 doors using the optional D9210C Access Control Interface Module. The control panel supports up to 16 of the keypads as SDI keypads. Bosch IP cameras use is supplementary in UL Listed systems. Features This section explains the control panel's notable features.
The control panel retains point alarm and trouble events for each area in event memory. You can view event memory on a keypad. Turning an area on clears the event memory for that area. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
Communication Module, or telephone module), or locally using the control panel’s on-board Ethernet port or USB port. (To program with the USB port connection, use the B99 USB 2.0 Type A Male to Type A Male cable by Bosch.) You can also use a keypad for select programming.
Where the fire alarm transmitter is sharing on-premise communications equipment, the shared equipment must be UL Listed (ITE or fire protective signaling). Model number Keypads B915/B915I* B920* B921C* B925F* B926F* B930* B942/B942W* 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
Page 21
Suitable for use on approved applications in the USA. D1640-CA Suitable for use on approved applications in Canada. Enclosures BATB-40/ BATB-80 B8103 D8103 D8109 D8108A D8004 Expansion modules B208 B299 B308 B600 D125B D129 Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
Page 22
Communicators B426 B430 B440 B441 B442 B443 B444 B450 Accessories D113 D130 D132A D133 D134 D161 Suitable for use on approved applications. D162 Suitable for use on approved applications. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
Page 23
PIR Motion Sensor [18 m (60 ft)] with POPIT ZX970 PIR/Microwave Motion Sensor [+1.7°C (+35°F)] with POPIT 5110/4001-42 Rothenbuhler High Security Bell B810 wireless receiver compatible accessories Refer to RADION receiver SD (B810) Installation Guide. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
Page 24
Multiple-Condition On/Off Pendant Transmitter EN1233D Necklace Pendant Transmitter (Double-button) EN1233S Necklace Pendant Transmitter (Single-button) EN1235D Beltclip Pendant Transmitter (Double-button) EN1235DF Fixed-location Transmitter (Double-button) EN1235S Beltclip Pendant Transmitter (Single-button) EN1235SF Fixed-location Transmitter (Single-button) 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
Wheelock 24 VDC external powered devices System Sensor control panel powered devices System Sensor 12 VDC external powered devices System Sensor 24 VDC external powered devices High current settings reduces the quantity. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
Page 26
24 VDC, 15/75 cd, Red NS-24MCW-FR 24 VDC, Variable cd, Mini, Wall-mount, Red NS-24MCW-FW 24 VDC, Variable cd, Mini, Wall-mount, White RSS Series Strobes RSS-241575W-FR 24 VDC, 15/75 cd, Synchronized, Red 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
Page 27
LED LF HN RED,2W,WALL,24V,NO LTR LLFHNW-N LED LF HN WHT,2W,WALL,24V,NO LTR LLFHSR LED LF HN STR,RED,2W,WALL,24V,110CD, FIRE LLFHSW LED LF HN STR,WHT,2W,WALL,24V,110CD, FIRE LLFHSR-AL LED LF HN STR,RED,2W,WALL,24V,110CD, ALERT Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
Page 28
24 VDC, Selectable 135/185 cd, Wall, White ZRS-MCC-FR 24 VDC, Selectable 15/30/75/95 cd, Red ZRS-MCC-FW 24 VDC, Selectable 15/30/75/95 cd, White ZRS-MCCH-FR 24 VDC, Selectable 115/177 cd, Red ZRS-MCCH-FW 24 VDC, Selectable 115/177 cd, White 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
Page 29
UL requirement If you use 24 V devices, you must use a UL 1481 regulated power-limited power supply and a D130 Relay Module. Refer to the D130 Installation Instructions. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
Install, operate, test, and maintain this device according to the control panel Installation and System Reference Guide. Failure to follow these procedures may cause the device not to function properly. Bosch Security Systems Inc. is not responsible for any devices that are improperly installed, tested, or maintained.
Align the Holes to attach the mounting skirt to hooks with the hooks. Slide the control panel down so that it hangs on the hooks. Secure the mounting skirt screw. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
Set your digital voltmeter (DVM) to measure VDC. Connect the red DVM lead to control panel Terminal 10, and the black DVM lead to Terminal 9. Compare this voltage to the following table. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
If SDIx is configured for SDI2, use either SDI2 bus. Using terminal wiring in parallel Notice! Wire size For terminal wiring, use 18 AWG to 22 AWG (1.0 mm to 0.6 mm) wire. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
Page 34
COM/B COM/B ZONEX ZONEX TAMPER TAMPER RESET RESET ZONEX TMPR Using interconnect wiring Notice! More information For more information on interconnect wiring, refer to SDI2 interconnect wiring, page 17. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
Maintain a 0.250 in (6.4 mm) space between the battery terminals, battery wiring, and all other wiring. Battery wiring cannot share the same conduit, conduit fittings, or conduit knockouts with other wiring. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
Allow the control panel to charge the battery while you complete the installation. 6.1.2 BATTERY STATUS LED The control panel includes one BATTERY STATUS LED with 4 LED patterns to indicate the battery status. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
Control Panel Battery Restored to Normal (302) report in the Contact ID format. 6.1.5 Battery charging circuit float charge The float voltage for the battery charging circuit is 13.65 VDC when operating within load range. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
B8512G. 4 The power supply draws approximately 15 mA (+/- 1 mA) from the control panel. For detailed instructions, refer to the corresponding document listed in Related documentation, page 13. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
16 AWG (1.5 mm) wire when making the connection Use a grounding rod or a cold water pipe. Run wire as close as possible to grounding device. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
When you wire the output of a B520 to a SDI2 module, the B520 provides power to the module while passing through data between the control panel and the module. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
Page 42
You must wire BATT 1. You must wire BATT 2 if you configure the B520 for two batteries. When you use BATT 2, both batteries must have the same rating. Maximum standby power cannot exceed 36 Ah. Callout ᅳ Description 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
Page 43
1 ᅳ B520 Auxiliary Power Supply Module 2 ᅳ Battery 2 (BATT 2) - (12 V nominal lead acid) 3 ᅳ Battery 1 (BATT 1) - (12 V nominal lead acid) Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
13. Notification The B430 module by Bosch Security Systems, Inc. is registered with the Federal Communication Commission (FCC) under Part 68, for connection to the public telephone system using an RJ31X or RJ38X phone line connection jack installed by the local telephone company.
After installation, make sure that the control panel: – Seizes the line – Gets a dial tone – Reports correctly to the receiver – Releases the telephone line to the in-house telephone system Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
The called party must go on hook (hang up) for a fixed interval before a dial tone is available for a new call. This interval varies with telephone company equipment. Control panel 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
One hour after a COMM FAIL event, the control panel attempts to send a COMM RSTL event. If a communication failure still occurs, the keypad trouble sounds again. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
3. If the control panel does use the Ethernet for IP communication, power down the control panel and remove the Ethernet cable that connects the control panel to the network. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
Flash pattern Function Communicating at 100 Mb. On Steady Communicating at 10 Mb. Tab. 8.2: 100BASE-T LED descriptions Flash pattern Function Plugged into an Ethernet network. On Steady Communication in progress. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
Communication supervision. The control panel supervises the communication path by polling the central station receiver. If the poll is missed from either side, a communication fault is declared both at the control panel and the central station receiver. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
Use either the terminal strip wiring or interconnect wiring to the control panel. Do not use both. When you connect multiple modules, you can combine terminal strip and interconnect wiring connectors in parallel. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
Communication error state. Indicates a bus communication error. The module is not receiving commands from the 3 quick flashes every 1 sec control panel. Trouble state. Indicates a trouble condition exists. On Steady 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
If the module does not use the Ethernet for IP communication, skip to the next step. If the module does use the Ethernet for IP communication, power down the module and remove the Ethernet cable that connects it to the network. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
Inserting the cellular module Install a SIM card, if required by the cellular module. Push the plug-in cellular module into the B450 until you hear the module “click” into position. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
Flash pattern Indication Normal state. Flashes once every 1 second Communication error state. Error on the bus between the module and the control panel. 3 quick flashes every 1 second Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
The keypad is a fully supervised SDI2 device for fire applications. The keypad display and sounder alert to a fire alarm, a fire trouble, or fire supervisory events as they occur. The keypad includes fire status indicators and fire function keys. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
Shortcut so that the users can easily run the function from the keypad. The user must have the appropriate authority level enabled to use the custom function. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
Connect SDI keypads to the SDIx bus by parallel wire run from the control panel to each keypad, wire from keypad to keypad, or a combination of the two. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
COM, and 1, 2, 3, or 4. Wire resistance on each sensor loop must be less than 100 Ω with the detection devices connected. The terminal strip supports 12 to 22 AWG (0.65 to 2 mm) wires. Bosch Security Systems, Inc. Installation Manual...
LEDs. Refer to Outputs in RPS Help or in the Installer Services Portal programming tool (available in Europe, Middle East, Africa, and China) Help. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
3 ᅳ Common 7 ᅳ Momentary short on the circuit toggles the arming state 4 ᅳ Point input Notice! UL requirement Keyswitches are not intended for use in UL listed systems. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
Africa, and China), you can assign two custom functions to a RADION keyfob FB, allowing a user to initiate the functions wirelessly. For more information, refer to RPS Help or the Installer Services Portal programming tool Help. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
Programmable output normally closed, switches power off when the Sensor Reset command is executed. SDIx Power+ / R Powers serial device interface (SDI) keypads, or use to power serial device interface 2 (SDI2) devices, such as keypads and expansion modules. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
Nominal power output. Use the power at Terminals 6 and 7 to power bells, siren drivers, piezoelectric sounders, electronic horns, or other devices. Programming determines the format of the output and the conditions that activate it. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
The USB POWER STATUS LED lights when power to the USB is turned on. You can disable USB at any time. Use the Installer menu or press the control panel RESET button 3 times. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
With any failure to receive an expected response from the module, all keypads show a system fault. The control panel sends a module trouble report to the central station (if configured for module trouble reports). 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
The B600 Retrofit (ZONEX) module enables the use of ZONEX devices on the B9512G/ B8512G. The B600 module connects to the control panel through a proprietary connection (cable provided with module). The control panel supports one B600. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
For more information, refer to D8129 address settings, page 168. Installation For detailed instructions, refer to the corresponding document listed in Related documentation, page 13. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
The total resistance for the wire length and contacts, excluding the end-of-line (EOL) resistor, must not exceed 100 Ω. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
(B901 or D9210C) set to an SDI address. Set Debounce to 1.64 seconds for these points. Debounce does not apply to points with the Point Source configured as Wireless, Output, or IP Camera. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
Installation and control panel wiring (B208) Calculate power consumption Make sure that there is enough power for the module and the other powered devices that you want to connect to the system. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
Page 76
PWR A B COM PWR+/R PWR+/R PWR+/R PWR+/R olice olice olice olice PWR A B COM ting ting ting ting COM/B COM/B COM/B COM/B PWR+/R PWR+/R PWR+/R PWR+/R COM/B COM/B COM/B COM/B 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
UL does not permit normally closed loops for commercial fire applications. Notice! Optionally use these points for household fire applications. You can connect four-wire detectors to these points, for example. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
For valid point numbers, refer to B299 address settings, page 165. 13.2.2 Supervision The control panel automatically supervises any B299 on the SDI2 bus when an associated point has its source programmed for POPEX. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
Wire resistance on each sensor loop must be less than 100 Ω with the detection devices connected. The terminal strip supports 12 to 22 AWG (2.0 to 0.6 mm) wires. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
Hold the module mounting brackets onto the inside of the enclosure. Match the bracket holes to a 3-hole mounting pattern on the enclosure Use the supplied mounting screws to secure the module. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
Refer to On-board outputs, page 65. Caution! Remove all power (AC and battery) before making any connections. Failure to do so might result in personal injury and/or equipment damage. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
Requirements for Fire Initiation applications You can connect the D125B Dual Powered Loop Interface Module outputs directly to the point inputs on the D8128D. Use the D125B to connect two-wire smoke detectors. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
An interior motion detector point is missing and the area is turned on (armed). The control panel makes a Missing Alarm event. Non-fire, 24-hour points always make a Missing Alarm event. Fire points always make a Missing Fire Trouble event. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
Use the address switch to set the module to address 1. Use the provided anchors and screws to mount the module base on the wall. Pull the wiring through the mounting plate. Put the module on the base. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
Make sure that there is enough power for the module and the other powered devices that you want to connect to the system. Refer to On-board outputs, page 65. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
B901 door controller The B901 Access Control Interface Module is a fully supervised, addressable SDI/SDI2 bus device that allows access control integration for Bosch compatible control panels. This module offers 14 programmable levels of access authority. Authority for access is controlled by the user level, the group of the user, the time of day, the door state, and the area armed state.
The D9210C is a four-wire SDI powered device providing connections for an access door point and door strike. Each D9210C supports one door to control access. You can independently configure each access door. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
13. 15.3 Card reader wiring To wire the access control module to a card reader, refer to the card reader instructions printed on or shipped with the reader. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
The Panel Communication window opens. Click Connect and send the configuration programming to the control panel. Click Disconnect when the programming is complete. For more information, refer to RPS Help. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
Have a point profile not set to Disabled (must be non-zero) – Are not service bypassed – Are not invisible points – Have a point type of Keyswitch maintained, Keyswitch momentary, Open/Close Point, Fire, Aux AC Supervision, or Gas 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
– The test does not log any Extra Point events. Performing a service walk test Choose a keypad to conduct the test. Ensure that all areas are off (disarmed). Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
To view the list of points, press Enter or View untested points. To scroll through the list of points, use /Previous or /Next. When you fault a point (open a door for example), the keypad emits a brief tone and shows the name. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
Installing the enclosure, page 31 10 ᅳ Zonex module connector location SDI and ZONEX wiring, page 100 11 ᅳ Sensor loop terminals for points 1 to 8 On-board points, page 72 Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
Page 96
On-board Ethernet connection, page 48 13 ᅳ On-board Ethernet connector 14 ᅳ LINK LED (yellow) 15 ᅳ USB connector USB power, page 67 16 ᅳ USB POWER STATUS LED 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
All terminals except Outputs A (1), B (2), and C (3) (Terminals 6, 7, and 8) are supervised. For proper supervision, do not loop wire under terminals. Break the wire run to provide supervision of connections. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
12 ᅳ Listed audible signaling devices rated at 12.0 VDC nominal (do not use vibrating type horns) 6 ᅳ B520 Auxiliary Power Supply Module 13 ᅳ To earth ground 7 ᅳ To powered devices 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
18.3 Input points wiring with or without EOL resistors Notice! EOL resistors For the dual EOL resistor circuit style order ICP-1K22AWG-10, package of 10 1.0 kΩ EOL resistors. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
SDI and ZONEX wiring Notice! Install Fire and Intrusion devices only on separate circuits. Refer to the ICP-SDI-9114 Installation Instructions. All external connections except Terminal 5 (battery positive) are power limited. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
Page 101
*The number of D8129 Octo-relay modules allowed for each ZONEX terminal on the B600 is limited by the number of D8128D OctoPOPITs connected to the same terminal. Refer to the D8128D Installation Guide or the D8129 Operation and Installation Guide for detailed instructions. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
SDI2 modules use the SDI2 bus to communicate with one another. You can wire modules via home run, daisy chain, or single level T-tap anywhere on the SDI2 bus. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
Page 103
– Refer to the SDI2 device or keypad documentation for the allowable maximum distance from the control panel. – Maximum overall cable lengths are listed in the following table: Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
6 ᅳ Supervised smoke detector to B LOOP negative panel 2 ᅳ Supervised connection to Zone B power from an on- 7 ᅳ Supervised smoke detector to A LOOP negative board point of the control panel 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
Page 105
8 ᅳ Supervised smoke detector to B LOOP positive board point of the panel 4/5 ᅳ Connection to common the control panel (one 9 ᅳ Supervised smoke detector to A LOOP positive connection only) Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
Do not install the EVD sensor within 6.4 mm (0.25 in) of the components or traces of the printed circuit assembly. Battery connections – Using a D122 Dual Battery Harness, connect two 12 V 7 Ah batteries in the control panel enclosure. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
Page 107
15 ᅳ End-of-line (EOL) resistor 8 ᅳ Alarm input point 16 ᅳ Safe Use Terminals 1 through 8. (Select only one.) Use a D113 Battery Lead Supervision Module to supervise the battery connections Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
Page 108
Systems. Refer to RPS Help, the Installer Services Portal programming tool (available in Europe, Middle East, Africa, and China) Help, or the control panel’s Program Entry Guide for programming information. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
Consult the individual component specification and installation documents to determine suitability. Notice! UL requires that the control panel supervises any device powered from a power output. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
For battery calculations, refer to Standby battery requirements and calculations, page 114. Notice! Test weekly Perform a fire test once each week. 19.1.4 Enclosures Mount the control panel assembly in any of the Bosch Security Systems, Inc. enclosures listed: – D2203 Enclosure – B8103 Universal Enclosure/D8103 Universal Enclosure –...
Page 112
Suitable for use on approved applications. D1640 Required for all UL applications. D1640-CA Required for all cUL applications. Enclosures BATB-40/ BATB-80 D8004 B8103/D8103/ D8109 Enclosure D8108A Enclosure Expansion modules B208 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
Page 113
Required for MUX devices. D8128D D8129 Optional. For remote annunciation of system functions. D8130 D9127U/T Wireless B810 B820 Communicators B426 B430 B440 B441 B442 B443 B444 B450 Accessories D113 D130 D132A Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
Current (mA) Current (mA) Model Number Each Total Each Total Each Total Used Unit Unit Unit B9512G/ ______ =190 =190 =265 B8512G B299 ______ xQty =______ xQty =______ xQty =______ 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
Page 116
One D1218 Battery=17.2 or 18 Ah – Two D1218 Batteries=34.4 or 36 Ah Application Standby time (in hours) Alarm time (in minutes) minimum minimum Residential Burglary Proprietary Burglary Central Station (Bank) Central Station (Mercantile) 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
_________ Refer to previous table. Value = Minutes of alarm operation/60 Total Ah requirements must not exceed the Ah capacity of batteries: – One D126 Battery = 7 Ah Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
Area # Delay Restorals = No (Restoral report is sent when point restores.) 19.7 Required programming to meet UL 864 This section identifies the programming requirements you must make in order to comply with UL 864 Commercial Fire applications. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
Page 119
Enter 1:00 AC Fail Display 10 to 300 seconds 10 to 200 seconds AC Tag Along Yes / No Set to Yes AC/Battery Buzz Yes / No Set to Yes Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
Page 120
Sked## Date mm/dd Set to No Sked## Sunday Yes / No Set to Yes Sked## Monday Yes / No Set to Yes Sked## Tuesday Yes / No Set to Yes 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
Page 121
Do not program No Keypad Wide, Custom, No Keypad Function Lock (within the Yes / No Keypads section Reset Sensors Disable/Enable/Passcode Protect Enable Fire Test Disable / Enable / Passcode Protect Enable Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
Supervision Time set to Custom, Poll Rate set to 89, ACK Wait Time set to 15, and Retry Count set to 5 19.9 Conduct testing monthly, with the primary de-energized. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
Press and hold the control panel RESET button until the Heartbeat LED flashes fast. The keypad shows SERVICE MODE and prompts for the installer passcode. Enter your installer passcode and press Enter. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
Page 124
Press [2] Enhanced Comm Parms. – Go to [1] Programming Menu > [1] Reporting > [2] Network > [2] Enhanced Comm Parms. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
Page 125
Srvc Byp menu Versions menu Cloud menu USB Power menu Exit User menu trees Menu tree The following graphics show the menu tree for the B94x / B93x keypads. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
Page 126
Turn Off Select Area Call Via Phone Go to Area Extend Close Bypass Firmware Points Bypass Unbypass Points Cycle Door Srv Bypass Unlock Door Access Lock Door Secure Door 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
Page 127
View Log Set Date/ Time Format Schedule Brightness Volume Keypad Keypress Dflt Text Nightlight Presence Menu tree The following graphics show the menu tree for the B92x / B91x keypads. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
Page 128
6: Update Firmware 1: Bypass Points 5: Bypass 1: Cycle Door 7: View Serv 2: Unbypass Bypassed Points 2: Unlock Door 8: Access 3: Lock Door 4: Secure Door 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
Page 129
– Save. B91x/B92x keypads typically use Enter to save. The B93x/B94x keypads typically use Save to save. The B94x keypad uses the key to save from the Qwerty keyboard. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
Go to [1] Programming Menu > [1] Reporting > [1] Phone. The keypad shows the phone number and phone format for the phone destination. /Previous or /Next to go to the destination you want to edit. Depending on keypad model: 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
Depending on keypad model: Press Enter and then press Disable or Enable. -or- Press Enter. Press Save or Enter. The keypad shows Parameter saved. Escape from the menu. Network Address Port Number Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
Use routing to program primary and backup destinations over standard telephone lines, local area network (LAN) or wide area network (WAN). In this menu, you can designate the primary and backup destinations for up to four routes. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
In this menu, you can add a phone number or email address to each personal notification identifier (1 through 32). Notification Phone number or email address Number Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
Page 134
______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ Personal Note Enter the installer passcode, and then open the [1] Installer Menu. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
Go to [1] Programming Menu > [2] Network > [1] Ethernet > (choose the bus module or on-board) > [1] Module Parameters > [2] UPnP Enable. The keypad shows the UPnP current configuration. Depending on the keypad model: Press Yes or No. -or- Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
Press Edit or Enter to edit the port number. Delete the existing number, if necessary, and then enter the new number. Press Save or Enter. The keypad shows Parameter saved. Escape from the menu. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
Press Edit or Enter to edit the RPS passcode. Delete the existing number, if necessary, and enter the new number. Press Save or Enter. The keypad shows Parameter saved. Escape from the menu. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
Press Edit or Enter to edit the RPS port number. Delete the existing number, if necessary, and then enter the new number. Press Save or Enter. The keypad shows Parameter saved. Escape from the menu. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
______________ ______________ Area 29* Area 30* Area 31* Area 32* Area On Yes/No Yes/No Yes/No Yes/No Account Number ______________ ______________ ______________ ______________ *Supported by the B9512G only. Area State 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
Keypad 1 No keypad / B91x / B92x / B93x / No Device / Area Wide / Acct Wide / B94x / D1255 / D125xRB / D126x Panel Wide Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
Page 142
Keypad 19* No keypad / B91x / B92x / B93x / B94x No Device / Area Wide / Acct Wide / Panel Wide Keypad 20* No keypad / B91x / B92x / B93x / B94x No Device / Area Wide / Acct Wide / Panel Wide 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
Page 143
Press Save or Enter. The keypad shows Parameter saved and then asks if you would like to edit the scope. Press Edit or Enter to edit the type. Depending on keypad model: Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
Point Profile. You must use RPS or the Installer Services Portal programming tool (available in Europe, Middle East, Africa, and China) to configure the Point Profile parameters. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
Page 145
Output Response Type __(0)__ __(0)__ __(0)__ __(0)__ __(0)__ __(0)__ __(0)__ __(0)__ Display as Device Local While Disarmed Local While Armed Disable Restorals Force Arm Returnable Bypass Returnable Bypassable Swinger Bypass Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
Page 147
Point Profile Text defaults (the second language text defaults are blank): Point Profile 17 Point Profile 18 Gas: Supervisory Point Profile 19 Aux AC Supervision Point Profile 20 Part On: Watch Off Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
Page 148
Display as Device Local While Disarmed Local While Armed Disable Restorals FA Returnable Bypass Returnable Bypassable Swinger Bypass Report Bypass at Occurrence Defer Bypass Report Cross Point Alarm Verify Resettable 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
Page 149
_(30)__ _(30)__ _(30)__ _(30)__ Entry Tone Off Silent Bell Ring Until Restored Audible After Two Fails Invisible Point Buzz on Fault ______ ______ ______ ______ ______ ______ ______ ______ Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
Page 151
Enter the point number and press Enter, or use /Previous or /Next to go to the desired point. Press Edit or Enter to edit the profile for the selected point. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
/Previous or /Next to scroll through the list of wireless points, and go to the point for which you want to enroll a device, or simply enter the point number. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
Start with address 8 before adding additional repeaters. Press Enter to add the repeater. The keypad instructs you to tamper the repeater. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
Go to [2] Wireless > [3] RF Diagnostic Menu > [1] RF Point Diagnostic > [2] Point Signal. /Previous or /Next to scroll through the list, and go to the point for which you want to view diagnostic information, or enter the point number. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
Name:, IPv4 Source IP:, IPv6 Source IP:, MAC Addr:. (Use /Next to scroll through, if necessary.) When finished viewing the information, escape from the menu. Connection Enter the installer passcode, and then open the [1] Installer Menu. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
/Next. The keypad shows the Cloud configuration, which is one of the following: – Not Available – Enabled on Ethernet – Enabled on Cellular – Enabled on Ethernet and Cellular 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
Press the icon or softkey for the item for which you want view the version. -or- /Previous or /Next to scroll through the list of items for which you can view the version. Press Enter to view the version. Escape from the menu. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
Go to [7] USB Power. The keypad shows the current status, USB Power is on or USB Power is off. Depending on keypad model: Press the icon or softkey for the desired option. -or- Press Enter to change the status. Escape from the menu. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
SDI bus A: 9 VDC 4572 m (15000 ft) maximum SDI bus B: 9 VDC 4572 m (15000 ft) maximum SDI2 bus SDI2 bus A: 12 VDC nominal (7500 ft) maximum Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
< 200 mA 21.1 Wire requirements Terminal label Terminal description Requirements 18 AWG to 14 AWG (1.02 mm to 1.8 mm) 18 AWG to 14 AWG (1.02 mm to 1.8 mm) 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
Page 161
Terminal accommodates 22 AWG to 14 AWG (0.65 mm to 1.8 mm), use appropriate wire size based on current BATTERY - Bosch supplied wire lead, included with control panel. BATTERY + Output A (1) Terminal accommodates 22 AWG to 14 AWG (0.65 mm to 1.8 mm), use appropriate wire size based on current...
Page 162
1.8 mm), use appropriate wire size based on loop resistance less than 100 Ω ZONEX ZONEX Bosch supplied wire, included with the optional B600 SDIx COMMON Terminal accommodates 22 AWG to 14 AWG (0.65 mm to 1.8 mm), use appropriate wire size based on peripheral...
Switch 8 to the OPEN position. The B9512G uses Points 9 to 127 on ZONEX 1 and Points 129 to 247 on ZONEX 2. B8512G uses only Points 9 to 99 on ZONEX 1. Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
D1255VFD Keypad / D125xRB Fire Keypad / D126x LCD Keypad address switch settings. Notice! D126x keypads only use addresses 1-8. To access the switch settings, press and hold [0] until the menu changes. Address Switches Encoding Tone ON/ 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
(Assign Card Event) Alarm Aspppp NriaBApppp Burglary 1 130 aa ppp Alarm Cross Point Aspppp NriaBMpppp Burglary 1 130 aa ppp Alarm Exit Error Aspppp Nria/idiiiiEApppp Entry/Exit 1 134 aa ppp Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
Page 172
Towers Cellular Fewer than Two RssssD NpiddddER System Peripheral Trouble 3 330 00 zzz Towers Restoral Restore Cellular Low Signal TssssD NpiddddET System Peripheral Trouble 1 330 00 zzz 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
Page 173
1 302 00 000 Control panel battery missing Tsss9 Battery Missing/Dead 1 311 00 000 Control panel battery Rsss9 Low System Battery 3 302 00 000 restored to normal Restore Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
Page 174
Fire Trouble Restore 3 373 aa ppp Fire Supervision Espppp NriaaFSpppp Fire Supervisory 1 200 aa ppp Fire Supervision from Restore Espppp NriaaFVpppp Fire Supervisory Restore 3 200 aa ppp 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
Page 179
Expanded Status D6600 CIM for Trouble Present Status Items Test Report - System Off- RsssE Periodic Test - System 1 608 00 000 normal, Non-expanded Status Trouble Present Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...
IT department before changing the registry. Adding a new registry key, if required Open Notepad. Copy and paste or type the text shown below the instructions. 2018.07 | 10 | F.01U.303.996 Installation Manual Bosch Security Systems, Inc.
Page 183
Use Windows Explorer to find the saved file. Double-click the file to add it to the computer registry. Restart the RPS or Installer Services Portal programming tool computer. Text for the AutoIP.reg file: Windows Registry Editor Version 5.00 [HKEY_LOCAL_MACHINE\SYSTEM\CurrentControlSet\Services\Tcpip\Parameters] "IPAutoconfigurationEnabled"=dword:00000001 Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996...