22
en | Compliance Settings
Point 1
Set Point Assignments > Text to: Fire Panel Alarm.
Set Point Assignments > Profile to: 4 - Fire Panel Alarm
Point 2
Set Point Assignments > Text to: Fire Panel Trouble.
Set Point Assignments > Profile to: 1 - Fire Panel Trouble
Point 3
Set Point Assignments > Text to: Fire Panel Supervisory.
Set Point Assignments > Profile to: 6 - Fire Panel Supervisory
Figure 2.4: Fire Panel Supervisory
2.2.3

CAN/ULC-S559, Recommended Programming

Control panel silencing of fire alarm panel alarm, trouble, and supervisory events
When control panels are configured as described below, they automatically silence keypads
connected to the control panel for fire, trouble, and supervisory events from the fire panel.
Notice!
Automatic silence not available for B3512 control panels
Automatic silencing of fire alarm panel alarm, trouble, and supervisory events is not available
for the B3512 control panel. Users must silence these events at the keypad.
CUSTOM FUNCTIONS > Custom Function 128
Set Custom Function 128 > Custom Function Text to: Silence.
Set Custom Function 128 > Function 1 to: Trouble Silence (set Parameter 1 to: Area 1).
Set Custom Function 128 > Function 2 to: Alarm Silence (set Parameter 1 to: Area 1).
2017.03 | 09 | F.01U.303.998
Program Entry Guide
Control Panel
Bosch Security Systems, Inc.