Control Panel
The battery must be discharged below 12.1 VDC for 16 seconds before the control panel
responds to a low battery. It takes between 10 and 60 seconds for a missing battery to be
detected.
Modem reports: Missing or shorted  BATTERY MISSING; discharged below 12.1 VDC BATTERY
LOW
Contact ID reports: Missing or shorted BATTERY MISSING/DEAD; discharged below 12.1 VDC
LOW SYSTEM BATTERY
RPS Menu Location
Panel Wide Parameters > Power Supervision > Battery Fail/Restoral Report.
3.14

RPS Parameters

3.14.1

RPS Passcode

Default: 999999
Selections: 6 - 24 alphanumeric characters in length
This parameter verifies that the RPS operator has valid access to connect to the control panel.
Enter a minimum of six characters. Do not use spaces in the passcode. Passcode is case-
sensitive.
The control panel provides an RPS passcode configuration option. This option accepts up to
24 characters, but will allow shorter passcodes. When RPS connects to the control panel, the
correct passcode must be supplied before the control panel will allow RPS to access any
configuration data or control functions.
The RPS passcode defaults to "999999" in the control panel. In an RPS default account, the
passcode is also "999999". A default RPS account can connect to a default control panel
without modifying the RPS passcode in either the RPS account or in the control panel.
RPS Menu Location
Panel Wide Parameters > RPS Parameters > RPS Passcode
3.14.2

Log % Full

Default: 0
Selections: 0 to 99
0 (zero)-    This setting disables the LOG THRESHOLD and LOG OVERFLOW events. These
events are not put in the log nor reported to the central station receiver. The control panel
continues to log events after the LOG THRESHOLD report is sent. When it reaches 100%
capacity (memory logger is full and previously stored events will be overwritten), the control
panel generates a local LOG OVERFLOW event.
This parameter determines how full the memory log should be before initiating a call to RPS at
the central station. This allows the central station to call the control panel and copy the
memory log before messages could be overwritten.
The control panel does not call RPS again until it downloads the log and the Log % Full
percentage is again reached. These events are also sent to the control panel's event log.
RPS Menu Location
Panel Wide Parameters > RPS Parameters > Log % Full.
3.14.3

Contact RPS if Log % Full

Default: No
Selections:
Yes - the control panel automatically contacts RPS when the "Log % Full" threshold is
reached.
Bosch Security Systems, Inc.
Program Entry Guide
Panel Wide Parameters | en
2017.03 | 09 | F.01U.303.998
71