Control Panel
8.2.6
Summary Fire
Default: 0
Selections:
–
–
This parameter sets the number of the output that activates when any fire point in the system
(Point type = Fire) goes into alarm. A steady output is provided until all fire points in the
system are returned to normal, and all fire alarm events are cleared from keypad displays.
Notice!
This parameter only functions as described when Fire Summary Sustain, page 77 is set to No.
Notice!
To ensure proper operation, do not assign more than one function to the output associated
with this summary function.
RPS Menu Location
Output Parameters > Panel Wide Outputs > Summary Fire
8.2.7
Summary Alarm
Default: 0
Selections:
–
–
This parameter sets the number of the output that activates when a non-fire point goes into
alarm.
A steady output is provided until the alarm is silenced and the alarm event is cleared form the
keypads' display.
This output does not activate for silent alarms.
Notice!
To ensure proper operation, do not assign more than one function to the output associated
with this summary function.
RPS Menu Location
Output Parameters > Panel Wide Outputs > Summary Alarm
8.2.8
Summary Fire Trouble
Default: 0
Selections:
–
–
This parameter enables the output to activate when any fire point on the control panel is in
trouble. A steady output is provided until all fire points have restored to a normal event and
the event message is cleared by the user at the keypad.
Bosch Security Systems, Inc.
B9512G: 0 to 599
B8512G: 0 to 99
B9512G: 0 to 599
B8512G: 0 to 99
B9512G: 0 to 599
B8512G: 0 to 99
Program Entry Guide