Control Panel
Notice!
To comply with UL 864 requirements for Commercial Fire Systems, set this parameter to 5
seconds.
Notice!
Do not enable the Cross Point Feature in Point Indexes that are designated for fire points.
Notice!
Check the sensor's datasheet for the stabilization time and enter a value at least 5 seconds
higher than the longest time specified by any sensor in the loop.
Notice!
Check with your Authority Having Jurisdiction (AHJ) to determine the maximum verification
time allowed.
Alarm verification points are programmed individually to activate the verification feature. Refer
to Point Index. Any resettable fire point can activate alarm verification for the area to which it
is assigned. Bosch recommends using separate area alarm verification outputs.
To enable alarm verification on a point, set Point Type to Fire, and Alarm Verify and Resettable
to Yes.
When an alarm verification point is faulted, the control panel automatically removes power to
all resettable points connected to the areas Reset Sensors output. Power is removed for 4.5
seconds. When power is reapplied, the control panel ignores alarms from the resettable points
for the amount of time programmed in Restart Time. After Restart Time has expired, a 65
second confirmation window begins. If the alarm verification point is still in alarm, or faults
again during the confirmation window, or if a different alarm verification point in the area
faults, an alarm is generated.
Callout - Description
1 - Sensor detects possible event.
2 - Power removed from resettable points.
3 - Power reapplied to resettable points. Restart Time begins.
4 - Confirmation window begins. Any alarm during this period will be annunciated.
5 - Confirmation window ends. The sequence is re-initiated the next time an alarm
verification point is faulted.
RPS Menu Location
Area Wide Parameters > Area/Bell Parameters, Open/Close Options > Restart Time
Bosch Security Systems, Inc.
4.5 sec
10-60 sec
Program Entry Guide
65 sec
Area Wide Parameters | en
2017.03 | 09 | F.01U.303.998
95