142 en | Output Parameters
This parameter enables the output to activate when any gas supervisory point on the control
panel is in a supervisory event (off normal). A steady output is provided until all gas
supervisory points are restored to a normal condition and the event message is cleared by the
user at the keypad.
Notice!
To ensure proper operation, do not assign more than one function to the output associated
with this summary function.
Notice!
Fire/gas trouble points must be restored to normal before summary outputs can be cleared.
RPS Menu Location
Output Parameters > Panel Wide Outputs > Summary Gas Supervisory Output
8.2.14

Summary Gas Trouble Output

Default:  0
Selections:
This parameter sets the output to activate when any gas point on the control panel is in
trouble. A steady output is provided until all gas points have restored to a normal condition
and the event message is cleared by the user at the keypad.
Notice!
To ensure proper operation, do not assign more than one function to the output associated
with this summary function.
Notice!
Fire/gas trouble points must be restored to normal before summary outputs can be cleared.
RPS Menu Location
Output Parameters > Panel Wide Outputs > Summary Gas Trouble Output
8.3

Output Configuration

8.3.1

Output Source

Default:
Selections:
2017.03 | 09 | F.01U.303.998
B9512G: 0 to 599
B8512G: 0 to 99
Output A(1): On-board A
Output B(2): On-board B
Output C(3): On-board C
All other Outputs: Unassigned
On-board
Unassigned
Octo-output
IP Camera
Program Entry Guide
Control Panel
Bosch Security Systems, Inc.

Hide quick links: