Control Panel
3 - Communicator parameters,
The parameters under the Communicator, overview, page 58 heading assign a Primary
Destination Device and a Backup Destination Device to each Route Group. The control panel
uses the Route Group's Primary Destination Device first to send reports. If the Primary
Destination Device fails to send the report, the control panel creates a Comm Trouble Event
and switches to the Backup Destination Device.
The control panel makes up to ten communication attempts switching between the primary
and backup destination devices to send reports from a Route Group. If unsuccessful after 10
attempts, it creates a Comm Fail Event.
4 - Destinations
The control panel sends reports from each Route Group using their Primary and Secondary
Destination Devices to the Destinations configured for the device.
Configure for Onboard IP Destinations here: On Board Ethernet (IP) Communicator, page 31,
and here: Enhanced Communication, page 62.
Configure for Plug -in Cellular IP Destinations here: Cellular Plug-in Module, page 36, and here
Enhanced Communication, page 62. Refer to Configuring for Cellular Service, page 280 for more
information.
Configure for Plug-in Phone Destinations here: Phone and Phone Parameters, page 28.
Configure for SDI2 Address Destinations here: (B42x) IP Communicator, page 239 or here:
B450 cellular, page 246, and here: Enhanced Communication, page 62.
Route Group priority
Route Group 1 has the highest priority. Route Group 4 has the lowest priority. When there are
reports in more than one Report Group to be sent at the same time, the control panel sends
the report in the highest priority Route Group first. For example if there are reports in
Route Group 2 and Route Group 3, the control panel sends the report in Route Group 2 first.
Priority within a Route Group
Within a Route Group, reports to be sent are prioritized as shown in the list below. The
control panel sends the highest priority report first. 1 is the highest priority.
1.
2.
3.
4.
5.
6.
7.
Bosch Security Systems, Inc.
Diagnostic Reports: Watchdog Reset, Reboot.
RPS Reports: Remote Reset.
Fire Reports: Fire Alarm.
Gas Reports: Gas Alarm.
Personal Emergency Reports: Medical Alarm, Silent / Hold-up Alarm, Panic Alarm,
Duress.
Burglar Reports: Alarm Report.
Fire Reports: Fire Cancel.
Gas Reports: Gas Cancel.
Burglar Reports: Non-Fire Cancel.
Diagnostic Reports: SDI2 Device Failure, Parameter Checksum Fail, Phone Line Fail, AC
Failure, Battery Missing, Battery Low, Battery Restoral, Route Comm Fail, Route Comm
Fail Restore.
Fire Reports: Fire Restoral (after Alarm), Fire Missing, Fire Trouble, Fire Supervision, Fire
Restoral (after Trouble), Fire Supervision Missing, Fire Supervision Restoral.
Gas Reports: Gas Restoral from Alarm, Gas Missing, Gas Trouble, Gas Supervision, Gas
Restoral from Trouble, Gas Supervision Missing, Gas Supervision.
Burglar Reports: Non-Fire Supervision.
Personal Emergency Reports: Medical Alarm Restoral, Silent / Hold-up Alarm Restoral,
Panic Alarm Restoral.
Program Entry Guide
Panel Wide Parameters | en
2017.03 | 09 | F.01U.303.998
45