The output activates when a controlled perimeter point (Type 1) assigned to the specified
area is faulted. This output activates regardless of the areas armed state.
This output provides a steady output until all perimeter points in the area return to normal.
This output does not activate on interior faults. To detect all area point faults, program all
points as perimeter points in the area to which this output is assigned.
Assign a unique output number for each area.
RPS Menu Location
Output Parameters > Area Wide Outputs > Part On Fault
8.1.12

Silent Alarm

Default: 0
Selections:
This output activates when a point assigned to the specified area and programmed for Silent
Bell, page 191 goes into alarm.
Use this output for invisible/silent bell 24-hour panic/hold up applications.
RPS Menu Location
Output Parameters > Area Wide Outputs > Silent Alarm
8.1.13

Gas Bell

Default: 1
Selections:
This output activates when a gas point assigned to this area goes into alarm.
The area-wide Gas alarm bell uses the time in Fire Time, page 99 and output cadence defined
in Gas Pattern, page 101. This output activates according to the bell pattern and remains active
until the bell time expires or is manually silenced.
Each area can be assigned a unique output number for each of the events listed in this
section.
RPS Menu Location
Output Parameters > Area Wide Outputs > Gas Bell
8.2

Panel Wide Outputs

8.2.1

AC Failure

Default: 0
Selections:
This parameter enables the output to activate when the control panel responds to an AC
power failure as programmed in AC Fail Time, page 69. The output automatically resets when
AC power is restored.
Connect a separate sounder to this output to create an audible annunciation from the keypads
for all applications excluding commercial fire systems.
RPS Menu Location
Output Parameters > Panel Wide Outputs > AC Failure
Bosch Security Systems, Inc.
B9512G: 0 to 599
B8512G: 0 to 99
B9512G: 0 to 599
B8512G: 0 to 99
B9512G: 0 to 599
B8512G: 0 to 99
Program Entry Guide
Output Parameters | en 137