100 en | Area Wide Parameters
Notice!
To comply with UL 864 requirements for Commercial Fire Systems, set this parameter to 5
minutes.
Notice!
Check with your Authority Having Jurisdiction (AHJ) to determine the appropriate bell time
for your geographical area.
The output activated for this time is programmed in A# Fire Bell. The A## Gas Bell is
completely independent of the A## Fire Bell, but also follows the time programmed in this
prompt. The bell output starts as soon as the fire alarm occurs. It shuts off the bell when the
programmed number of minutes expires. Set this parameter for two minutes or more to
ensure you have ample output time.
RPS Menu Location
Area Wide Parameters > Area/Bell Parameters, Open/Close Options > Fire Time
4.1.16

Fire Pattern

Default: Pulsed
Selections:
This parameter selects the bell pattern this area uses to signal an alarm on a fire point.
Notice!
When two fire points sharing the same output go into alarm, the bell pattern of the most
recent fire event takes precedence.
RPS Menu location
Area Wide Parameters > Area/Bell Parameters, Open/Close Options > Fire Pattern
4.1.17

Burg Time

Default: 6
Selections: 1 to 90 (minutes) (in one minute increments)
This parameter sets the number of minutes the bell rings for burglary alarm points.
Notice!
Check with your Authority Having Jurisdiction (AHJ) to determine the appropriate bell time
for your geographical area.
2017.03 | 09 | F.01U.303.998
Steady -steady output.
Pulsed - pulsed march time. 60 beats per minute at an even tempo (0.5 seconds on and
0.5 seconds off).
California Standard - 10 seconds audible + 5 seconds silent + 10 seconds audible + 5
seconds silent. This sequence repeats until bell time expires.
Temporal Code 3 - 0.5 seconds On, 0.5 seconds Off, 0.5 seconds On, 0.5 seconds Off, 0.5
seconds On, 1.5 seconds Off; pattern repeats. This sequence repeats for a minimum of 3
minutes with ± 10% timing tolerance. (1999 NFPA standards allow automatic silencing as
permitted by the Authority Having Jurisdiction (AHJ), and carry a minimum ring time of 5
minutes.)