92
en | Area Wide Parameters
RPS Menu Location
Area Wide Parameters > Area/Bell Parameters, Open/Close Options > Area Name Text
(Second Language)
4.1.3
Area On
Default:
–
–
Selections:
–
–
This parameter enables or disables the specified area.
Notice!
To comply with UL 864 requirements for Commercial Fire Systems, set this parameter to Yes.
When an area is set to No:
–
–
–
–
RPS Menu Location
Area Wide Parameters > Area/Bell Parameters, Open/Close Options > Area On
4.1.4
Account Number
Default: 0000
Selections: 4 or 10 digit numbers, 0-9, B-F
This parameter determines the account number reported for this area. An account number
must be assigned to each active area.
If 5 or more digits are used in the account number, RPS automatically pads the number with
leading zeros to make it a ten-digit number.
Notice!
Make sure the central station automation software is compatible with 10-digit account
numbers before programming a 10-digit account number into the control panel.
Notice!
Account numbers must not include 'A' for any digit.
Account numbers are used to group areas together. Each area can have a different account
number, or several areas might share the same account number. The control panel uses the
account number as a reference for arming and keypad text displays.
2017.03 | 09 | F.01U.303.998
B9512G:
–
Area 1: Yes
–
Areas 2 to 32: No
B8512G:
–
Area 1: Yes
–
Areas 2 to 8: No
Yes Area is enabled.
No Area is disabled.
Points assigned to this area do not generate events.
When arming and disarming, this area number is not displayed at keypads with the scope
to view this area.
Status for this area is not reported with status reports.
All user authority in this area is turned off while the area is disabled.
Program Entry Guide
Control Panel
Bosch Security Systems, Inc.