Module Enclosure Tamper; System (Repeater) Supervision Time; Low Battery Resound; Enable Jamming Detection - Bosch B9512G Program Entry Manual

Security system
Hide thumbs Also See for B9512G:
Table of Contents

Advertisement

Control Panel
14.7.2

Module Enclosure Tamper

Default: No - Disable
Selections:
Yes - Enable enclosure tamper input
No - Disable enclosure tamper input
This parameter enables the enclosure tamper switch input on the SDI2 module.
When the input is enabled and connected to a Bosch ICP-EZTS tamper switch installed in the
module enclosure, the control panel can create a tamper event when the enclosure door is
opened, or when the enclosure is removed from the wall.
RPS Menu Location
SDI2 > Wireless Receiver > Enclosure Tamper
14.7.3

System (Repeater) Supervision Time

Default: 12 hours
Selections:
This parameter sets the supervision time for all configured wireless repeaters. If the wireless
receiver does not hear from a repeater within the number of hours set by this parameter, the
control panel creates a missing repeater event.
Notice!
Wireless Point Supervision Time
Configure the wireless supervision time for non-fire points using the parameter Point
Profiles / Wireless Point Supervision Time, page 200. The wireless point supervision time for
fire points is fixed at 4 hours.
Notice!
Wireless Keyfob Supervision Time
Enable or disable wireless supervision time for wireless keyfobs using the parameter User
Assignments / Supervised, page 148. When supervision is enabled, the wireless keyfob
supervision time is fixed at 4 hours.
RPS Menu Location
SDI2 > Wireless Receiver > System Supervision Time
14.7.4

Low Battery Resound

Default: Never Resound
Selections: Never Resound, 4 hours, 24 hours
This parameter is global for all non-fire points. The control panel automatically fixes the Low
Battery Resound at 24 hours for fire points.
RPS Menu Location
SDI2 Modules > Wireless Receiver > Low Battery Resound
14.7.5

Enable Jamming Detection

Default: Yes
Selections: Yes / No
This parameter setting turns on or off the reporting of interference to the control panel.
Bosch Security Systems, Inc.
None - Disable wireless repeater supervision.
4, 12, 24, 48, 72 hours
Program Entry Guide
SDI2 modules | en 253
2017.03 | 09 | F.01U.303.998

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

B8512gB8512g-eB9512g-e

Table of Contents