248 en | SDI2 modules
Notice!
UL Requirement
To meet UL requirements, the entry for this parameter should not exceed 200 seconds.
The control panel creates a Cellular Low Signal event when the signal strength is below the
"unacceptable" threshold (indicated by the red LED) for the number of seconds specified in
this Reporting Delay for Low Signal Strength parameter. (Low signal is defined as 80% of the
measurements taken during the time period are below the threshold).
The control panel creates a Cellular Low Signal Restoral event when the signal strength is
above the "good" threshold (indicated by the green LED) for the number of seconds specified
in this Reporting Delay for Low Signal Strength parameter. (Good signal is defined as 80% of
the measurements taken during the time period are above the threshold).
RPS menu location
SDI2 modules > IP Communicator > B450 Cellular > Reporting delay for low signal strength
14.5.5

Reporting Delay for No Towers (sec.)

Notice!
Important configuration information for cellular communication
Refer to Configuring for Cellular Service, page 280 for an overview and configuration
information.
Default: 0
Selections: 0-3600 (seconds)
When there are no towers present the control panel starts two timers, one for a
No Towers event, one for a No IP Address event. The control panel uses the duration set by
this Reporting Delay for No Tower parameter for both timers. If the cellular plug-in module
does not find a tower before the end of the delay, the control panel creates a No Towers event
and a No IP Address event at the same time.
The control panel creates a No Tower restoral event when one or more towers are available for
the duration set by this Reporting Delay for No Tower parameter.
The contro panel creates a No IP Address restoral event when the cellular plug-in module
successfully registers with one or more towers and receives an IP address.
Notice!
When one or more towers are available, 60 second delay for No IP Address event
If the cellular plug-in module successfully registers with one or more towers, but does not
receive an IP address within 60 seconds, the control panel creates a No IP Address event.
RPS menu location
SDI2 modules > IP Communicator > B450 Cellular > Reporting delay for no towers
14.5.6

Outgoing SMS Length

Notice!
Important configuration information for cellular communication
Refer to Configuring for Cellular Service, page 280 for an overview and configuration
information.
2017.03 | 09 | F.01U.303.998
0 - Disabled.
1 to 3600 - Enabled.