258 en | Hardware switch settings
B94x Touch Screen Keypad address switch settings
To set the address, use the up and down arrows on the right of the switches image to change
the ones digit, and the arrows on the left to change the tens digit. Press the diagonal arrow
under the switches to save the setting and return to the power up screen.
15.2

B208 Octo-input Module switch settings

This table describes the relationship between the module switch settings and the point
address range that corresponds to the setting. The values of point range listed in this table
references back to POINTS > Point Assignments.
The B9512G supports up to 59 B208 Octo-input modules.
The B8512G supports up to 9 modules.
Terminate unused B208 inputs with an EOL resistor.
B208 address number
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
2017.03 | 09 | F.01U.303.998
B9512G point numbers
11 - 18
21 - 28
31 - 38
41 - 48
51 - 58
61 - 68
71 - 78
81 - 88
91 - 98
101 - 108
111 - 118
121 - 128
131 - 138
141 - 148
151 - 158
161 - 168
171 - 178
181 - 188
191 - 198
201 - 208
211 - 208
221 - 228
Program Entry Guide
Control Panel
B8512G point numbers
11 - 18
21 - 28
31 - 38
41 - 48
51 - 58
61 - 68
71 - 78
81 - 88
91 - 98