Control Panel
RPS Menu Location
Output Parameters > Panel Wide Outputs > Summary Trouble
8.2.11
Summary Supervisory Burg
Default: 0
Selections:
–
–
This parameter enables the output to activate when any non-fire supervisory point on the
control panel is in a supervisory condition. A steady output is provided until all Burg points are
restored to a normal condition and the event message is cleared by the user at the keypad.
Notice!
To ensure proper operation, do not assign more than one function to the output associated
with this summary function.
Notice!
Fire/gas trouble points must be restored to normal before summary outputs can be cleared.
RPS Menu Location
Output Parameters > Panel Wide Outputs > Summary Supervisory Burg
8.2.12
Summary Gas Output
Default: 0
Selections:
–
–
This parameter sets the number of the output that activates when any gas point in the system
goes into alarm. A steady output is provided until all gas points in the system are returned to
normal and the event message is cleared by the user at the keypad.
Notice!
To ensure proper operation, do not assign more than one function to the output associated
with this summary function.
Notice!
Fire/gas trouble points must be restored to normal before summary outputs can be cleared.
RPS Menu Location
Output Parameters > Panel Wide Outputs > Summary Gas Output
8.2.13
Summary Gas Supervisory Output
Default: 0
Selections:
–
–
Bosch Security Systems, Inc.
B9512G: 0 to 599
B8512G: 0 to 99
B9512G: 0 to 599
B8512G: 0 to 99
B9512G: 0 to 599
B8512G: 0 to 99
Program Entry Guide
Output Parameters | en 141
2017.03 | 09 | F.01U.303.998