en | System Informations 2
8.1.4

Zone Bypass

If this option is selected, the zone can be automatically isolated when the system is armed. If
this option is not selected, the zone cannot be manually isolated. When a zone is manually
isolated, a Zone Bypass Report is sent. When isolating 24-Hour Zone, the system automatically
sends a Zone Bypass Report when the zone is seleted to be isolated. All non-24-Hour zones
send a Bypass Report only when the system is armed. When the zone bypass is restored, a
Bypass Restore Report will be sent to the system.Zone Bypass is only effective per armed
period and automatically fails after disarmed. The isolated zones ignore all the events
triggered and restored before the system disarmed.Key-switch Zone cannot be bypassed.
8.1.5

Forced Arming

If this option is selected, the system can be armed with the zone unsealed. If this option is not
selected, the system does not allow the User Code holder to arm the system until the zone is
sealed or manually isolated.Arming the system when a zone is triggered is known as forced
arming: When arming the system:
1.
2.
3.
Exception case for force arming; Telephone and RPS remote arming. If using telephone and
RPS remote arming as arm operation, the system will ignore the force arm programming. It
will ARM without checking the characters of force arming.
8.1.6

Silent Alarm

Select this option to program a zone as silent. A silent zone does not activate the siren output.
The dialer and all other programmable outputs function according to the parameters
programmed for the zone
8.1.7

Zone Lockout

1. No Lockout
Programming the zone lockout option as 0 will disable the lockout function.
2. 1 Time Alarm Lockout
A zone can only alarm (output for Siren and alarm event) up to 1 time per armed period by
programming the lockout option as 1. Lockout is activated per arming cycle (that is, a zone
programmed for Lockout can activate sirens/report only 1 time). After the system disarm/ arm
again, the lockout counting will be reset.The AMAX panel 2000 / AMAX panel 2000 EN Control
Panel performs lockout:
1.
2.
3.
4.
5.
F.01U.241.127 | V4 | 2011.12
The system will automatically check the triggered zone when Arming by keypads, keyfob
command and keyswitch operation. If the zone is triggered and force arm is disabled and
not bypassed, it can't arm successfully and no trouble event will be sent.
The system will automatically check the triggered zone when Arming by keypads, keyfob
command and keyswitch operation. If force arm is enabled, it can be armed successfully,
if the zone is still triggered after the exit time is up , a trouble event will be sent.
The zone restore report will be sent when the trouble zone is restored.
When the zone is triggered an alarm is created and the siren is activated in an alarm
(output for siren run) time. During the alarm time, the system will ignore triggered status
of this zone.
Total of 1 time, the zone will be locked out.
During the system alarm time, if any zone alarmed is restored, it will not send out the
alarm restore report until the system alarm time is up.
If any zone is not programmed as a lockout zone, it will not be limited by the lockout
time, even other zones are lockout, if this zone is triggered, it will still occure an alarm.
When the zone is triggered 2 times siren/alarm period, the zone will be locked out.
And a fault report for this zone will be sent.