9.3

SIA CP-01 False Alarm Prevention Options

Notice!
Some programming parameters are preset for compliance with SIA standard CP-01 (false
alarm prevention). These settings are in AREA WIDE PARAMETERS→Area Parameters. They
affect control panel operation as described below.
Bosch Security Systems, Inc.
Turning the System ON or OFF and Keypad Commands for B920/B930 | en
All On-No Exit=YES: This setting provides for a Perimeter Delay point to be faulted when
master arming each area, or the arming state defaults to Perimeter Delayed.
Exit Delay Warning=YES: When this parameter is set to YES, the alarm bell pulses on and
off every two seconds for the remaining 10 sec of Exit Delay.
Entry Delay Warning=YES: When this parameter is set to YES, the alarm bell pulses on
and off every two seconds for the remaining 10 sec of Entry Delay.