2.0

Overview

2.1

System Overview

Radionics' D8024 Analog Fire Alarm Control Panel (FACP) is an expandable control panel that provides point identification
through addressable analog devices. The D8024 has two expansion slots to accommodate plug-in polling circuit modules.
Each of these polling circuit modules can support up to 126 analog addresses, giving the panel a potential of 252
addressable points. Flexibility in system design allows the option of grouping device points together and identifying
them as one location, or zone, in order to simplify system operation.
The D8024 includes the following features:
• Analog design using advanced communications protocol
• 80 character display
• Custom text annunciation
• Up to 252 addresses supported in a stand-alone system
• Can be networked with Radionics' D9024 and D10024 Analog FACPs as well as other D8024 FACPs
• 24 VDC, 2.5 A power supply and battery charger
• Programmable sensitivity levels by device
• Programmable "day/night" sensitivity levels
• PC programmable
• Service mode polling
• Fire test mode
• Event activity logger (up to 500 events)
• Suitable for ADA applications
• Meets NFPA National Fire Code standards
LED Display
Zone/Area Display
Copyright © 2001 Radionics

Figure 1: D8024 Fire Alarm Control Panel