Derating Diagram; List Of The Miniature Circuit Breakers And Circuit Breakers; Marine Version - Siemens SINAMICS G150 Reference Manual

Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Result
The test is passed if the dimensions match with what is specified in the dimension drawing.
3.1.8

Derating diagram

Fundamentals
The power must be derated for operation under higher ambient temperatures. The derating
diagram required is attached to one of the drive doors.
Test procedure
1. The existence of the diagram is checked.
Result
The check is passed if the diagram is available
3.1.9

List of the miniature circuit breakers and circuit breakers

Fundamentals
The existence of the list with miniature circuit breakers and circuit breakers is checked.
Test procedure
1. Random samples of the values in the list are compared with the circuit diagram.
Result
The test is passed if the checked values match what is specified in the circuit diagram.
3.1.10

Marine version

Fundamentals
A check is made as to whether the mechanical housing design of the ordered marine version
complies with what is described in the catalog.
SINAMICS G150 6SL37102G E11 F72 F76 F79 L45 L50 L57 L68 M54 U11
Reference Manual Rev.201902141443 LV Umrichter
Tests
3.1 Visual inspection
19

Advertisement

Table of Contents
loading

Table of Contents