Derating Data; Technical Data - Siemens SINAMICS G150 Operating Manual

Converter cabinet units 75 kw to 800 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

11/03
12.2.1

Derating Data

Current Derating as a Function of the Site Altitude and Ambient Temperature
If the cabinet units are operated at a site altitude >2000 m above sea level, the
maximum permissible output current can be calculated using the following tables.
The site altitude and ambient temperature are compensated here. The degree of
protection selected for the cabinet units must also be taken into account.
Table 12-2
Current derating as a function of the ambient temperature and site altitude for cabinet units
with degree of protection IP20 / IP21 and IP23
Site altitude
above sea level in
m
0 to 2000
Up to 2500
Up to 3000
Up to 3500
Up to 4000
Table 12-3
Current derating as a function of the ambient temperature and site altitude for cabinet units
with degree of protection IP54
Site altitude
above sea level in
m
0 to 2000
Up to 2500
100%
Up to 3000
Up to 3500
96.0%
Up to 4000
92.0%
SINAMICS G150
Operating Manual
Ambient temperature in °C
20
25
30
100%
96.7%
97.8%
92.7%
Ambient temperature in °C
20
25
30
98.0%
99.0%
94.0%
95.0%
90.0%
91.0%
87.0%
87.0%
83.0%
35
40
95.0%
96.3%
91.4%
96.2%
92.5%
87.9%
92.3%
88.8%
84.3%
88.4%
85.0%
80.8%
35
40
93.0%
90.0%
85.0%
90.0%
86.0%
82.0%
86.0%
83.0%
79.0%
83.0%
80.0%
75.0%
79.0%
76.0%
72.0%

Technical Data

45
50
90.0%
86.6%
83.3%
79.9%
76.5%
45
50
81.0%
77.0%
74.0%
71.0%
68.0%
12-3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents