Digital Outputs / Relays [41] - WEG CFW-11 Programming Manual

V5.8x
Hide thumbs Also See for CFW-11:
Table of Contents

Advertisement

Digital and Analog Inputs and Outputs

13.1.4 Digital Outputs / Relays [41]

The CFW-11 has 3 relay digital outputs as standard on its control board, and 2 more digital outputs of the
open collector type that can be added with the accessories IOA-01 or IOB-01. The next parameters configure
the functions related to those outputs.
P0013 – DO5 to DO1 Status
Adjustable
Range:
Properties:
Access groups
via HMI:
Description:
By means of this parameter it is possible to visualize the status of the control board 3 digital outputs (DO1 to DO3)
and the 2 digital outputs of the optional board (DO4 and DO5).
The indication is done by means of the numbers "1" and "0", representing respectively the "Active" and "Inactive"
states of the outputs. The state of each output is considered as one digit in the sequence where DO1 represents the
least significant digit.
Example: In case the sequence 00010010 is presented on the keypad (HMI), it will correspond to the following
status of the DOs:
P0275 – DO1 Function (RL1)
P0276 – DO2 Function (RL2)
P0277 – DO3 Function (RL3)
P0278 – DO4 Function
P0279 – DO5 Function
Adjustable
Range:
13
Properties:
Access groups
via HMI:
13-20
Bit 0 = DO1
Bit 1 = DO2
Bit 2 = DO3
Bit 3 = DO4
Bit 4 = DO5
RO
07 I/O CONFIGURATION
41 Digital Outputs
Table 13.10 - Digital outputs status
DO5
DO4
Active
Inactive
(+24 V)
(0 V)
0 to 42
07 I/O CONFIGURATION
41 Digital Outputs
or
01 PARAMETER GROUPS
41 Digital Outputs
DO3
DO2
DO1
Inactive
Active
Inactive
(0 V)
(+24 V)
(0 V)
or
01 PARAMETER GROUPS
41 Digital Outputs
Factory
Setting:
Factory
P0275=13
Setting:
P0276=2
P0277=1
P0278=0
P0279=0