Example: For a motor with the following characteristics,
I
= 10.8 A
n
T
= 4 s (hot motor blocked rotor time)
BR
= 7.8 ⇒ I
I
/ I
= 7.8 x 10.8 A= 84.2 A
p
n
p
SF = 1.15
one gets,
Overload Current =
I
x SF
n
Overload Time = T
= 4 s
BR
After this, it is only necessary to plot the calculated values on the motor overload graph (
the thermal class curve immediately below the calculated point.
Overload Time
100000
10000
1000
100
10
1
0
I
84.2
p
=
x 100 = 678 %
10.8 x 1.15
1
2
3
4
5
1x
2x
3x
4x
5x
6x
(a) - Cold motor overload curves for loads of the HD and ND types
Class 45
Class 40
Class 35
Class 30
Class 25
Class 20
Class 15
Class 10
Class 5
Current x In for F.S. = 1.00
6
7
8
9
10
Current x In for F.S. = 1.15
7x
8x
9x
10x
Faults and Alarms
on page
15-7, and to select
15-7
15