c) Adjust the password P0000 = 5: according to the
5-3, of this manual.
d) Adjust the inverter to operate with the application line and motor: by means of the "Oriented Start-up"
Menu access P0317 and change its content to 1, which makes the inverter initiate the "Oriented Start-up" routine.
The "Oriented Start-up" routine presents on the keypad (HMI) the main parameters in a logical sequence. The setting
of these parameters prepares the inverter for operation with the application line and motor. Verify the step by step
sequence in the
Figure 11.6 on page
The setting of the parameters presented in this operation mode results in the automatic modification of the content
of other inverter parameters and/or internal variables, as indicated in the
gets a stable operation of the control circuit with adequate values to obtain the best motor performance.
During the "Oriented Start-up" routine the "Config" (Configuration) status will be indicated on the top left part of the
keypad (HMI).
Parameters related to the motor:
 Program the contents of parameters from P0398, P0400 to P0406 directly with the motor nameplate data.
 Options for the setting of parameters P0409 to P0412:
- Automatic, with the inverter executing the self-tuning routine as selected in one of the P0408 options.
- From the motor data sheet supplied by its manufacturer. Refer to the procedure in the
of the Parameters P0409 to P0412 Based on the Motor Data Sheet on page
- Manually, copying the contents of the parameters from another CFW-11 inverter, which uses and
identical motor.
e) Setting of specific parameters and functions for the application: set the digital and analog inputs and
outputs, HMI keys, etc., according to the application needs.
For applications:
 That are simple, which can use the factory settings programming for the digital and analog inputs
and outputs, use the Menu [04] "Basic Application". Refer to the item 5.2.3 - Setting Basic Application
Parameters, of the CFW-11 user's manual.
 That require only the digital and analog inputs and outputs with programming different from the factory
settings, use the Menu [07] "I/O Configuration".
 That need functions as Flying Start, Ride-Through, DC Braking, Dynamic Braking, etc., access and
modify those function parameters by means of the Menu [01] "Parameter Groups".
Section 5.3 PASSWORD SETTING IN P0000 on page
11-33.
Vector Control
Figure 11.6 on page
11-33. In this way one
Item 11.7.1 Adjustment
11-15, of this manual.