WEG CFW-11 Programming Manual page 197

V5.8x
Hide thumbs Also See for CFW-11:
Table of Contents

Advertisement

When Torque is selected, the speed regulator parameters P0161 and P0162 become inactive (*). Thus, the Total Reference
becomes the input of the Torque Current Regulator. Refer to the
(*) The PID-type speed regulator is converted into a P-type regulator with proportional gain 1.00 and null integral gain.
When Speed is selected, the gains of the speed regulator become again defined by P0161 and P0162. In the
applications with torque control it is recommended to follow the method described at the parameter P0160.
-
DC Link Regulation: it must be used when P0184 = 2. For more details, refer to this parameter description
in the
Item 11.8.7 DC Link Regulator [96] on page
-
JOG+ and JOG-: those are functions valid only for P0202 = 3, 4, 6 or 7.
-
Disables Flying-Start: it is valid for P0202≠4. By applying +24 V to the digital input programmed for this
purpose, the Flying-Start function is disabled. By applying 0 V, the Flying-Start function is enabled again, provided
that P0320 be equal to 1 or 2. Refer to the
-
Load User 1/2: this function allows the selection of the user memory 1 or 2, in a similar process than P0204 = 7
or 8, with the difference that the user memory is loaded from a transition of the DIx programmed for this function.
When the state of the DIx changes from low level to high level (transition from 0 V to 24 V), the user memory
1 is loaded, provided that the contents of the inverter actual parameters had been previously transferred to the
parameter memory 1 (P0204 = 10).
When the sate of the DIx changes from high level to low level (transition from 24 V to 0 V), the user memory 2
is loaded, provided that the contents of the inverter actual parameters had been previously transferred to the
parameter memory 2 (P0204 = 11).
P0204=10
P0204=11
-
Load User 3: this function allows the selection of the user memory 3, in a similar process than P0204 = 9,
with the difference that the user memory is loaded from a transition of the DIx programmed for this function.
When the DIx state changes from low level to high level (transition from 0 V to 24 V), the user memory 3 is loaded,
provided that the contents of the inverter actual parameters had been previously transferred to the parameter
memory 3 (P0204 = 12).
NOTE!
Make sure that when using those functions the parameter sets (user memory 1, 2 or 3) be totally
compatible with the application (motors, Run/Stop commands, etc.).
It will not be possible to load the user memory with the inverter enabled.
If two or three parameter sets from different motors were saved in the user memories 1, 2 and/or 3,
the correct current values must be adjusted at the parameters P0156, P0157 and P0158 for
each user memory.
Section 12.7 FLYING START/RIDE-THROUGH [44] on page
Inverter
Parameters
P0263 to P0270
(DIx)=27
User 1
DIx=0 V
User 2
P0263 to P0270 (DIx)=27
Figure 13.4 - Details on the working of the Load User 1/2 function
Digital and Analog Inputs and Outputs
Figure 11.1 on page 11-2
11-30, of this manual.
DIx=24 V
DIx=0 V
DIx=24 V
and
Figure 11.2 on page
11-4.
12-11.
13-15
13

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents