Vector Control
Description:
It is the motor magnetizing current value, which is automatically adjusted by the self-tuning
TUNING on page
Parameters P0409 to P0412 Based on the Motor Data Sheet on page
It can be estimated by the self-tuning routine when P0408 = 2 (Run for I
in standard WEG motors, when P0408 = 1 (No rotation).
When a standard WEG motor is not used and it is not possible to run the self-tuning with P0408 = 2 (Run for I
then adjust P0410 with a value equal to the motor no load current, before initiating the self-tuning.
For P0202 = 4 (vector mode with encoder), the value P0410 determines the motor flux, therefore it must be
properly adjusted. If it is low, the motor will operate with a reduced flux compared to the rated condition, having,
consequently, its torque capability reduced.
P0411 – Motor Flux Leakage Inductance (σls)
Adjustable
Range:
Properties:
Access groups
via HMI:
Description:
The value is automatically adjusted by the self-tuning
can also be calculated from the motor data sheet
Based on the Motor Data Sheet on page
NOTE!
When adjusted via the keypad (HMI), this parameter will change the parameter P0167 automatically.
P0412 – Lr/Rr Constant (Rotor Time Constant – T
Adjustable
Range:
Properties:
Access groups
via HMI:
11
11-26
11-5). Its value can also be obtained on the motor data sheet
0.00 to 99.99 mH
CFG and Vector
01 PARAMETER GROUPS
29 Vector Control
94 Self-tuning
11-15).
0.000 to 9.999 s
Vector
01 PARAMETER GROUPS
29 Vector Control
94 Self-tuning
11-15).
) or obtained from an internal table based
m
05 SELF-TUNING
or
(Section 11.3 SELF-TUNING on page
(Item 11.7.1 Adjustment of the Parameters P0409 to P0412
)
r
05 SELF-TUNING
or
(Section 11.3 SELF-
(Item 11.7.1 Adjustment of the
Factory
0.00 mH
Setting:
11-5). This parameter
Factory
0.000 s
Setting:
),
m