P0695 - Digital Outputs Setting - WEG CFW11 User Manual

Operation of the cfw11 frequency inverter using the ethercat protocol
Hide thumbs Also See for CFW11:
Table of Contents

Advertisement

P0685 = 0000h (0 decimal)
P0685 = 2000h (8192 decimal)
Intermediate or higher reference values can be programmed by using this scale. E.g. for a 4 pole motor and 1800
rpm of synchronous speed, to obtain a reference of 900 rpm, one must calculate:
1800 rpm ⇒ 8192
900 rpm ⇒ Reference in 13 bits
Reference in 13 bits =
Reference in 13 bits = 4096
This parameter also accepts negative values to revert the motor speed direction. The speed reference direction,
however, depends also on the bit 2 of control word:
Bit 2 = 1 and P0685 > 0: forward direction of rotation
Bit 2 = 1 and P0685 < 0: reverse direction of rotation
Bit 2 = 0 and P0685 > 0: reverse direction of rotation
Bit 2 = 0 and P0685 < 0: forward direction of rotation
P0695 – DIGITAL OUTPUTS SETTING
Range:
Properties:
Description:
It allows the control of the digital outputs by means of the network interfaces (EtherCAT, etc.). It is not possible to
change this parameter via HMI.
Each bit of this parameter corresponds to the desired value for one digital output. In order to control the correspondent
digital output according to this content, it is necessary that its function be programmed for "P0695 Content" at
parameters to program digital outputs function.
Bit
15
14
Function
Bit
Bit 0
Value for DO1
Bit 1
Value for DO2
Bit 2
Value for DO3
Bit 3
Value for DO4
Bit 4
Value for DO5
Bit 5...15
speed reference = 0
speed reference = synchronous speed
900 × 8192
1800
⇒ Value corresponding to 900 rpm in a 13 bit scale
00000b... 11111b
RW
13
12
11
10
Table 5.4: Bit function for parameter P0695
0: Open DO1.
1: Close DO1.
0: Open DO2.
1: Close DO2.
0: Open DO3 .
1: Close DO3.
0: Open DO4.
1: Close DO4.
0: Open DO5.
1: Close DO5.
Reserved.
9
8
7
6
Valor/Descrição
Parameterization
Default: 00000b
5
4
3
2
CFW11 | 16
1
0