WEG CFW-11 Programming Manual page 89

V5.8x
Hide thumbs Also See for CFW-11:
Table of Contents

Advertisement

P0317 - Oriented Start-up
Adjustable
0 = No
Range:
1 = Yes
Properties:
CFG
Access groups
02 ORIENTED START-UP
via HMI:
Description:
When this parameter is changed to "1", the Oriented Start-up routine starts. The CFW11 goes into the "CONF"
state, which is indicated on the HMI. Within the Oriented Start-up, the user has access to important configuration
parameters of the CFW11 and of the motor for the control type to be used in the application. For further information
on the use of this parameter, refer to the following sections:
Section 10.3 VVW CONTROL MODE START-UP on page
Section 11.9 START-UP IN THE VECTOR MODES SENSORLESS AND WITH ENCODER on page
P0318 – Copy Function MemCard
Adjustable
0 = Off
1 = VFD → MemCard
Range:
2 = MemCard → VFD
Properties:
CFG
Access groups
06 BACKUP PARAMETERS
via HMI:
Description:
This function allows saving the contents of the inverter writing parameters in the FLASH Memory Module (MMF), or
vice-versa, and can be used to transfer the contents of the parameters from one inverter to another.
P0318
0
Inactive: no action
1
Inverter → MemCard: transfers the inverter current parameters contents to the MMF
MemCard → Inverter: transfers the contents of the parameters stored in the MMF to the inverter control board
2
After the transfer has been finished, an inverter reset occurs. The content of P0318 returns to 0
After storing the parameters of one inverter in a FLASH memory module, it is possible to pass them to another
inverter with this function. However, if the inverters are form different models or with incompatible software versions,
the keypad (HMI) will exhibit the message "Flash Mem. Module with invalid parameters" and will not allow the copy.
NOTE!
Valid for P0318 = 1.
During the inverter operation the modified parameters are saved in the FLASH memory module,
regardless of a user command. This assures that the MMF will always have an updated copy of
the inverter parameters.
10-4.
Table 7.2 - Parameter P0318 options
Action
Starting-up and Settings
Factory
0
Setting:
11-34.
Factory
0
Setting:
7
7-3