Pm Vector Control [29]; Speed Regulator [90]; Current Regulator [91] - WEG CFW-11 Programming Manual

V5.8x
Hide thumbs Also See for CFW-11:
Table of Contents

Advertisement

Description:
Values obtained from the motor nameplate data. The view of parameters P0435 and P0444 will depend on the
value set in P0430.
NOTE!
If this information is not available, it can be obtained using the following procedure:
1. Drive the motor with no load, setting P0121 = 1000 rpm.
2. After reaching the speed set, read the value of P0007.
3. Disable the inverter and set P0435 or P0444 (depending on the value set in P0430) with the
value read in P0007.

21.7 PM VECTOR CONTROL [29]

21.7.1 Speed Regulator [90]

The parameters related to the CFW-11 speed regulator are presented in this group.
P0160 – Speed Regulator Configuration
P0161 – Speed Regulator Proportional Gain
P0162 – Speed Regulator Integral Gain
P0163 – Local Reference Offset
P0164 – Remote Reference Offset
P0165 – Speed Filter
P0166 – Speed Regulator Differential Gain

21.7.2 Current Regulator [91]

The parameters related to the CFW-11 current regulator are presented in this group.
P0438 – Iq Current Regulator Proportional Gain
P0440 – Id Current Regulator Proportional Gain
Adjustable
0.00 to 1.99
Range:
PM Vector Control
Factory
P0438 = 0.80
Setting:
P0440 = 0.50
21-9
21