P0184 – DC Link Regulation Mode
Adjustable
0 = With losses
Range:
1 = Without losses
2 = Enable/Disable DIx
Properties:
CFG, PM and Vector
Access groups
01 PARAMETER GROUPS
via HMI:
Description:
It enables or disables the Optimal Braking function
voltage regulation, according to the next table.
P0184
0 = With losses
(Optimal Braking)
1 = Without losses
2 = Enable/Disable via DIx
P0185 – DC Link Voltage Regulation Level
Adjustable
339 to 400 V
Range:
585 to 800 V
585 to 800 V
585 to 800 V
585 to 800 V
809 to 1000 V
809 to 1000 V
924 to 1200 V
924 to 1200 V
Properties:
Vector
Access groups
01 PARAMETER GROUPS
via HMI:
29 Vector Control
96 DC Link Regulator
(Section 11.6 OPTIMAL BRAKING on page
Table 11.8 - DC link regulation modes
The Optimal Braking is active as described at P0185. This assures the minimum possible decelera-
tion time without using dynamic or regenerative braking
Automatic control of the deceleration ramp. The Optimal Braking is inactive. The deceleration ramp
is automatically adjusted in order to keep the DC link below the level adjusted in P0185. This proce-
dure avoids the overvoltage fault at the DC link (F022). It can also be used with eccentric loads
DIx = 24 V: Braking actuates as described for P0184 = 1
DIx = 0 V: The Without Losses Braking stays inactive. The DC link voltage will be controlled by
the parameter P0153 (Dynamic Braking)
29 Vector Control
96 DC Link Regulator
Vector Control
Factory
Setting:
11-8) in the DC
Action
Factory
P0296=0: 400 V
Setting:
P0296=1: 800 V
P0296=2: 800 V
P0296=3: 800 V
P0296=4: 800 V
P0296=5: 1000 V
P0296=6: 1000 V
P0296=7: 1000 V
P0296=8: 1200 V
1