P0181 – Magnetization Mode
Adjustable
0 = General Enable
Range:
1 = Run/Stop
Properties:
CFG and Encoder
Access groups
01 PARAMETER GROUPS
via HMI:
Description:
P0181
0 = General Enable
1 = Run/Stop
In the sensorless vector control mode, the magnetizing current is permanently active. In order to disable it when the
motor is stopped, a digital input programmed for General Enabling can be used. There is also the possibility of
programming P0217 in 1 (active). Refer to the
a delay for disabling the magnetizing current can be set by programming P0219 bigger than zero.
P0188 – Proportional Gain of the Maximum Output Voltage Regulator
P0189 – Integral Gain of the Maximum Output Voltage Regulator
Adjustable
0.000 to 7.999
Range:
Properties:
Vector
Access groups
01 PARAMETER GROUPS
via HMI:
Description:
These parameters adjust the maximum output voltage regulator gains. In general the factory setting is adequate for
the majority of the applications. Refer to the
P0190 – Maximum Output Voltage
Adjustable
0 to 690 V
Range:
Properties:
PM and Vector
Access groups
01 PARAMETER GROUPS
via HMI:
29 Vector Control
92 Flux Regulator
Table 11.4 - Magnetization Mode
Applies magnetizing current after General Enabling = ON
Applies magnetizing current after Run/Stop = Run
Section 12.6 ZERO SPEED LOGIC [35] on page
29 Vector Control
92 Flux Regulator
Figure 11.1 on page 11-2
29 Vector Control
92 Flux Regulator
Factory
Setting:
Action
12-10. Besides this,
Factory
Setting:
or
Figure 11.2 on page
11-4.
Factory
P0296.
Setting:
Automatic setting
during the Oriented
Start-up Routine:
P0400.
Vector Control
0
P0188 = 0.200
P0189 = 0.001
11
11-21