Fault/Alarm
A357
Overload alarm at book 2 V phase IGBT.
(10)
High Load at IGBT V B2
F358
Overload fault at book 2 V phase IGBT.
(10)
Overload at IGBT V B2
A360
Overload alarm at book 2 W phase IGBT.
(10)
High Load at IGBT W B2
F361
Overload fault at book 2 W phase IGBT.
(10)
Overload at IGBT W B2
A363
Overload alarm at book 3 U phase IGBT.
(10)
High Load at IGBT U B3
F364
(10)
Overload fault at book 3 U phase IGBT.
Overload at IGBT U B3
A366
Overload alarm at book 3 V phase IGBT.
(10)
High Load at IGBT V B3
F367
Overload fault at book 3 V phase IGBT.
(10)
Overload at IGBT V B3
A369
Overload alarm at book 3 W phase IGBT.
(10)
High Load at IGBT W B3
F370
Overload fault at book 3 W phase IGBT.
(10)
Overload at IGBT W B3
A372
Overload alarm at book 4 U phase IGBT.
(10)
High Load at IGBT U B4
F373
Overload fault at book 4 U phase IGBT.
(10)
Overload at IGBT U B4
A375
Overload alarm at book 4 V phase IGBT.
(10)
High Load at IGBT V B4
F376
Overload fault at book 4 V phase IGBT.
(10)
Overload at IGBT V B4
A378
Overload alarm at book 4 W phase IGBT.
(10)
High Load at IGBT W B4
F379
Overload fault at book 4 W phase IGBT.
(10)
Overload at IGBT W B4
A381
Overload alarm at book 5 U phase IGBT.
(10)
High Load at IGBT U B5
F382
Overload fault at book 5 U phase IGBT.
(10)
Overload at IGBT U B5
A384
Overload alarm at book 5 V phase IGBT.
(10)
High Load at IGBT V B5
F385
Overload fault at book 5 V phase IGBT.
(10)
Overload at IGBT V B5
Temperature > 40 ºC or 45 ºC depending on the
model; refer to section 3.1 - Installation Environment,
of the user´s manual of the CFW-11M.
A387
Overload alarm at book 5 W phase IGBT.
(10)
High Load at IGBT W B5
F388
Overload fault at book 5 W phase IGBT.
(10)
Overload at IGBT W B5
A390
Phase U book 1current unbalance alarm.
(10)
Current Unbalance at
It indicates a 20 % unbalance in the current
Phase U B1
distribution between this phase and the smallest
current of the same phase in other book, only when
the current in this phase is higher than 75 % of its
nominal value.
Quick Parameter Reference, Faults and Alarms
Description
Possible Causes
High current at the inverter output (see figure 8.1 of the
CFW-11M user's manual).
Bad electric connection between the DC bus and the
power unit.
Bad electric connection between the power unit output
and the motor.
Note: In case of fast acceleration or braking, one of these
alarms may be indicated momentarily, disappearing after
3 seconds. This is not an indication of any anomaly in the
inverter.
If the alarm persists when the motor is operating at a constant
speed, it is an indication of an anomaly in the current
distribution among the power units.