The overtemperature protection is carried out by means of the measurement of the temperature with the IGBTs and
power board internal air NTCs, being able to generate alarms and faults.
In order to configure the desired protection, set P0353 according to the table below.
P0353
0 = HS-F/A, Air-F/A
1 = HS-F/A, Air-F
2 = HS-F, Air-F/A
3 = HS-F, Air-F
4 = HS-F/A, Air-F/A *
5 = HS-F/A, Air-F *
6 = HS-F, Air-F/A *
7 = HS-F, Air-F *
(*) Disable alarm (A155) and fault (F156).
P0354 – Fan Speed Fault Configuration
Adjustable
Range:
Properties:
Access groups
via HMI:
Description:
This parameter allows setting whether a fault or an alarm should take place when the heatsink fan reaches ¼ of the
rated speed. If set to 1, the fault F179 will occur and the inverter will be disabled. If set to 0, the alarm A178 will
occur and the inverter won't be disabled.
P0354
0 = Off
1 = Fault
P0355 – Configuration of Fault F185
15
Adjustable
Range:
Properties:
Access groups
via HMI:
15-14
Table 15.6 - Options of the parameter P0353
Enables fault (F051) – IGBT Overtemperature and alarm (A050) – IGBT High Temperature
Enables fault (F153) – Internal Air Overtemperature and alarm (A152) – Internal Air High
Temperature
Enable Alarm of Overtemperature on the Rectifier (A010)
Enables fault (F051) and alarm (A050) for IGBTs overtemperature
Enables only fault (F153) for internal air overtemperature
Enable Alarm of Overtemperature on the Rectifier (A010)
Enables only fault (F051)for IGBT overtemperature
Enables fault (F153) and alarm (A152) for internal air overtemperature
Enables only fault (F051)for IGBT overtemperature
Enables only fault (F153) for internal air overtemperature
Enables fault (F051) – IGBT Overtemperature and alarm (A050) – IGBT High Temperature
Enables fault (F153) – Internal Air Overtemperature and alarm (A152) – Internal Air High
Temperature
Enable Alarm of Overtemperature on the Rectifier (A010) (*)
Enables fault (F051) and alarm (A050) for IGBTs overtemperature
Enables only fault (F153) for internal air overtemperature
Enable Alarm of Overtemperature on the Rectifier (A010) (*)
Enables only fault (F051)for IGBT overtemperature
Enables fault (F153) and alarm (A152) for internal air overtemperature (*)
Enables only fault (F051)for IGBT overtemperature
Enables only fault (F153) for internal air overtemperature (*)
0 = Alarm
1 = Fault
CFG
01 PARAMETER GROUPS
45 Protections
Table 15.7 - Actions for the parameter P0354 options
The heatsink fan speed fault protection is disabled
It enables the fault (F179). The inverter will be disabled if the fault occurs
0 = Off
1 = On