Description:
This parameter presents the inverter rated current for the normal overload regimen (ND) and for the heavy overload
regimen (HD). The inverter operation mode, if it is ND or HD, is defined by the content of P0298.
P0296 – Line Rated Voltage
Adjustable
0 = 200... 240 V
Range:
1 = 380 V
2 = 400 / 415 V
3 = 440 / 460 V
4 = 480 V
5 = 500 / 525 V
6 = 550 / 575 V
7 = 600 V
8 = 660 / 690 V
Properties:
CFG
Access groups
01 PARAMETER GROUPS
via HMI:
Description:
Setting according to the inverter power supply voltage.
The adjustable range depends on the inverter model, according to the
presents the factory default value.
NOTE!
When adjusted via the keypad (HMI), this parameter may change automatically the following
parameters: P0151, P0153, P0185, P0190, P0321, P0322, P0323 and P0400.
NOTE!
When changed from P0296 = 5, 6 or 7 to P0296 = 8 or vice-versa, the following parameters
could be changed automatically: P0029, P0135, P0156, P0157, P0158, P0290, P0295, P0297,
P0401 and P0410.
Table 6.8 - P0296 setting according to the CFW-11 inverter model
Inverter Model
200-240 V
380-480 V
500-600 V
660-690 V
42 Inverter Data
Adjustable Range
0 = 200...240 V
1 = 380 V
2 = 400 / 415 V
3 = 440 / 460 V
4 = 480 V
5 = 500 / 525 V
6 = 550 / 575 V
7 = 600 V
8 = 660 / 690 V
Inverter Model and Accessories Identification
Table 6.8 on page
Factory Setting
Factory
According to
Setting:
the inverter
model
6-9, which also
0
3
6
8
6-9
6