P0696 - Value 1 For Analog Outputs; P0697 - Value 2 For Analog Outputs; P0698 - Value 3 For Analog Outputs; P0699 - Value 4 For Analog Outputs - WEG CFW-11 User Manual

Anybus-cc
Hide thumbs Also See for CFW-11:
Table of Contents

Advertisement

Bits
Function
P0696 – VALUE 1 FOR ANALOG OUTPUTS
P0697 – VALUE 2 FOR ANALOG OUTPUTS
P0698 – VALUE 3 FOR ANALOG OUTPUTS
P0699 – VALUE 4 FOR ANALOG OUTPUTS
Range:
-32768 to 32767
Properties:
-
Access groups
via HMI:
Description:
They allow the control of the analog outputs by means of network interfaces (Serial, CAN, etc.). These
parameters cannot be changed via HMI.
The value written in these parameters is used as the analog output value, providing that the function for the
desired analog output be programmed for "P0696 / P0697 / P0698 / P0699 value", at the parameters P0251,
P0254, P0257 or P0260.
The value must be written in a 15-bit scale (7FFFh = 32767)
value, i.e.:
P0696 = 0000h (0 decimal)
P0696 = 7FFFh (32767 decimal)
The showed example was for P0696, but the same scale is also used for the parameters P0697 / P0698 /
P0699. For instance, to control the analog output 1 via serial, the following programming must be done:
Choose a parameter from P0696, P0697, P0698 or P0699 to be the value used by the analog output 1. For
this example, we are going to select P0696.
Program the option "P0696 value" as the function for the analog output 1 in P0254.
Using the network interface, write in P0696 the desired value for the analog output 1, between 0 and 100
%, according to the parameter scale.
1
For the actual output resolution, refer to the product manual.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
15 to 5
Table 3.4: P0695 parameter bit functions
Bits
Bit 0
0: DO1 output open.
DO1 setting
1: DO1 output closed.
Bit 1
0: DO2 output open.
DO2 setting
1: DO2 output closed.
Bit 2
0: DO3 output open.
DO3 setting
1: DO3 output closed.
Bit 3
0: DO4 output open.
DO4 setting
1: DO4 output closed.
Bit 4
0: DO5 output open.
DO5 setting
1: DO5 output closed.
Bits 5 to 15
Reserved
01 PARAMETER GROUPS
49 Communication
111 Status and commands
→ analog output value = 0 %
→ analog output value = 100 %
4
3
2
Values
to represent 100 % of the output desired
1
1
0
Default: 0