Functions Common to All the Control Modes
P0133 – Minimum Speed Reference Limit
Adjustable
Range:
P0134 – Maximum Speed Reference Limit
Adjustable
Range:
Properties:
Access groups
via HMI:
Description:
They define the maximum/minimum values for the motor speed reference when the inverter is enabled. They
are valid for any type of reference signal. For details on the actuation of P0133, refer to the parameter P0230
(Dead Zone of the Analog Inputs).
NOTE!
The maximum allowed speed is limited at the value defined by 3.4 x P0402. P0134 is always the
reference limit of the maximum speed, even if the value configured in P0133 is greater than the
value of P0134.
-10 V
-10 V
12
12-6
0 to 18000 rpm
0 to 18000 rpm
01 PARAMETER GROUPS
22 Speed Limits
Output speed
P0134
P0133
Speed Reference
+10 V
-P0133
-P0134
Figura 12.3 - (a) - Speed limits considering the "Dead Zone" inactive (P0230 = 0)
Output speed
P0134
P0133
Speed Reference
+10 V
-P0133
-P0134
Figure 12.3 - (b) - Speed limits considering the "Dead Zone" active (P0230 = 1)
Factory
Setting:
Factory
Setting:
Output speed
P0134
P0133
Speed Reference
0
Output speed
P0134
P0133
Speed Reference
0
0 ........................ 100 %
0 ...........................10 V
0 ........................20 mA
4 mA ....................20 mA
10 V .............................0
20 mA ..........................0
20 mA ....................4 mA
90 rpm
(75 rpm)
1800 rpm
(1500 rpm)