Trace Function [52]; Trace Function - WEG CFW-11 Programming Manual

V5.8x
Hide thumbs Also See for CFW-11:
Table of Contents

Advertisement

19 TRACE FUNCTION [52]

19.1 TRACE FUNCTION

The trace function is used to record variables of interest from the CFW-11 (as current, voltage, speed) when a
particular event occurs in the system (e.g.: alarm/fault, high current, etc.). This system event, for starting the data
recording process, is called "trigger". The stored variables can be visualized as graphs through the SuperDrive
G2 executed by a PC connected via USB or Serial to the CFW-11.
The parameters related to this function are presented next.
P0550 – Trigger Signal Source
Adjustable
0 = Not selected
Range:
1 = Speed Reference
2 = Motor Speed
3 = Motor Current
4 = DC Link Voltage
5 = Motor Frequency
6 = Motor Voltage
7 = Motor Torque
8 = Process Variable
9 = PID Setpoint
10 = AI1
11 = AI2
12 = AI3
13 = AI4
Properties:
Access groups
01 PARAMETER GROUPS
via HMI:
Description:
It selects the variable that will be used as the trigger source for the Trace Function.
This parameter has no effect when P0552 = "Alarm", "Fault" or "DIx".
Those same variables can also be used as signals to be acquired, through the parameters from P0561 up to
P0564.
P0551 – Trigger Level for Trace
Adjustable
-100.0 to 340.0 %
Range:
Properties:
Access groups
01 PARAMETER GROUPS
via HMI:
52 Trace Function
52 Trace Function
Trace Function [52]
Factory
0
Setting:
Factory
0.0 %
Setting:
19-1