WEG CFW-11 Programming Manual page 213

V5.8x
Hide thumbs Also See for CFW-11:
Table of Contents

Advertisement

P0224 – Run/Stop Selection – LOCAL Situation
P0227 – Run/Stop Selection - REMOTE Situation
Adjustable
0 = Keys
Range:
1 = DIx
2 = Serial/USB
3 = Anybus-CC
4 = CANopen/DeviceNet/Profibus DP
5 = SoftPLC
6 = PLC11
Properties:
CFG
Access groups
01 PARAMETER GROUPS
via HMI:
Description:
They define the origin of the Run/Stop command in the LOCAL situation and in the REMOTE situation.
P0225 – JOG Selection – LOCAL Situation
P0228 – JOG Selection - REMOTE Situation
Adjustable
0 = Disabled
1 = JOG Key
Range:
2 = DIx
3 = Serial/USB
4 = Anybus-CC
5 = CANopen/DeviceNet/Profibus DP
6 = SoftPLC
7 = PLC11
Properties:
CFG
Access groups
01 PARAMETER GROUPS
via HMI:
Description:
They define the origin of the JOG command in the LOCAL situation and in the REMOTE situation.
P0229 – Stop Mode Selection
Adjustable
0 = Ramp to Stop
1 = Coast to Stop
Range:
2 = Fast Stop
3 = By Ramp with Iq*
4 = Fast Stop with Iq*
Properties:
CFG
Access groups
01 PARAMETER GROUPS
via HMI:
,
31 Local Command
31 Local Command
31 Local Command
Digital and Analog Inputs and Outputs
Factory
Setting:
or
01 PARAMETER GROUPS
32 Remote Command
Factory
Setting:
or
01 PARAMETER GROUPS
32 Remote Command
Factory
Setting:
or
01 PARAMETER GROUPS
32 Remote Command
P0224 = 0
P0227 = 1
P0225 = 1
P0228 = 2
0
13
13-31

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents