WEG CFW-11 Programming Manual page 304

V5.8x
Hide thumbs Also See for CFW-11:
Table of Contents

Advertisement

PM Vector Control
Seq.
Action/Result
- Monitoring Mode.
1
- Press "Menu"
(right "soft key").
- The group "00 ALL
PARAMETERS" is already
2
selected.
- The group "01
PARAMETER GROUPS" is
3
selected.
- The group "02 ORIENTED
START-UP" is then
4
selected.
- Press "Selec.".
- The parameter "Oriented
Start-up P0317: No" is
5
already selected.
- Press "Selec.".
- The content of
"P0317 = [000] No" is
6
showed.
- The content of the
parameter is changed to
7
"P0317 = [001] Yes".
- Press "Save".
- At this moment, the
Oriented Start-up routine is
initiated and the "Config"
status is indicated at the
top left part of the keypad
(HMI).
- The parameter "Language
8
P0201: English" is
already selected.
- If necessary, change the
language by pressing
"Selec.", next
and
language and then press
"Save".
21
21-16
Display Indication
Ready
LOC
0
rpm
0.0
A
0.0
Hz
13:48
Ready
LOC
00 ALL PARAMETERS
01 PARAMETER GROUPS
02 ORIENTED START-UP
03 CHANGED PARAMETERS
Return
13:48
Ready
LOC
00 ALL PARAMETERS
01 PARAMETER GROUPS
02 ORIENTED START-UP
03 CHANGED PARAMETERS
Return
13:48
Ready
LOC
00 ALL PARAMETERS
01 PARAMETER GROUPS
02 ORIENTED START-UP
03 CHANGED PARAMETERS
Return
13:48
Ready
LOC
Oriented Start-up
P0317: No
Return
13:48
Ready
LOC
P0317
Oriented Start-up
[000] No
Return
13:48
Ready
LOC
P0317
Oriented Start-up
[001] Yes
Return
13:48
Config
LOC
Language
P0201: English
Type of Control
P0202: V/f 60Hz
Reset
13:48
to select the
Seq.
Action/Result
- Set the content of P0202
0rpm
pressing "Selec.".
- Next press
selecting the option: "[007]
Menu
9
Sensorless PM" or "[006]
PM with Encoder ".
0rpm
- Then press "Save".
Select
- If necessary, change
the content of P0296
0rpm
according to the used line
voltage. Therefore press
"Selec.". This change will
10
Select
affect P0151, P0153,
P0185, P0321, P0322,
0rpm
P0323 and P0400.
Select
- If necessary, change
the content of P0298
0rpm
according to the inverter
application. Therefore
press "Selec.". This change
Select
will affect P0156, P0157,
0rpm
P0158, P0169, P0170,
11
P0401 and P0404. The
actuation time and level
of the IGBTs overload
Save
protection will also be
0rpm
affected.
- If necessary, adjust
Save
the content of P0398
according to the motor
service factor. Therefore
press "Selec.". This change
12
will affect the current
value and the time for the
actuation of the motor
0rpm
overload function.
If necessary, change the
Select
content of P0400 according
to the rated motor voltage.
Therefore press "Selec.".
13
This change will affect
P0190.
Display Indication
until
Config
0rpm
LOC
Language
P0201: English
Type of Control
P0202: V/f 60Hz
Reset
13:48
Select
Config
LOC
0rpm
Type of Control
P0202: VVW
Line Rated Voltage
P0296: 440 - 460 V
Reset
13:48
Select
Config
0rpm
LOC
Line Rated Voltage
P0296: 440 - 460 V
Application
P0298: Heavy Duty
Reset
13:48
Select
Config
LOC
0rpm
Application
P0298: Heavy Duty
Motor Service Factor
P0398:
1.15
Reset
13:48
Select
Config
0rpm
LOC
Motor Service Factor
P0398:
1:15
Motor Rated Voltage
P0400:
440 V
Reset
13:48
Select

Hide quick links:

Advertisement

Table of Contents
loading