7 STARTING-UP AND SETTINGS

In order to start-up in the several types of controls, beginning from the factory settings, consult the following
sections:
-
Section 9.5 ENERGY SAVING FUNCTION on page
-
Section 10.3 VVW CONTROL MODE START-UP on page
-
Section 11.9 START-UP IN THE VECTOR MODES SENSORLESS AND WITH ENCODER on page
In order to use previously loaded parameters, refer to the
7-1, described next.

7.1 BACKUP PARAMETERS [06]

The CFW-11 BACKUP functions allow saving the content of the current inverter parameters in a specific memory,
or vice-versa (overwrite the contents of the current parameters with the memory contents). Besides, there is a
function exclusive for software update, by means of the FLASH Memory Module.
P0204 – Load/Save Parameters
Adjustable
0 = Not Used
Range:
1 = Not Used
2 = Reset P0045
3 = Reset P0043
4 = Reset P0044
5 = Load 60 Hz
6 = Load 50 Hz
7 = Load User 1
8 = Load User 2
9 = Load User 3
10 = Save User 1
11 = Save User 2
12 = Save User 3
Properties:
CFG
Access groups
06 BACKUP PARAMETERS
via HMI:
Description:
It makes it possible to save the actual inverter parameters in an area of the control module EEPROM memory or the other way
around, to load the contents of that area into the parameters. It also allows resetting the Time Enabled (P0043), kWh (P0044)
and Fan Enabled Time (P0045) counters. The
9-13.
10-4.
Section 7.1 BACKUP PARAMETERS [06] on page
Table 7.1 on page 7-2
describes the actions performed by each option.
Starting-up and Settings
11-34.
Factory
0
Setting:
7
7-1