Functions Common to All the Control Modes
P0321 – DC Link Power Loss
Adjustable
Range:
P0322 – DC Link Ride-Through
Adjustable
Range:
P0323 – DC Link Power Back
Adjustable
Range:
Properties:
Access groups
via HMI:
Description:
- P0321 – defines the U
- P0322 – defines the U
- P0323 – defines the U
motor must be reaccelerated.
NOTE!
These parameters work together with the parameters P0325 and P0326 for the Ride-Through in
vector control.
12
P0325 – Ride-Through Proportional Gain
Adjustable
Range:
12-18
178 to 282 V
308 to 616 V
308 to 616 V
308 to 616 V
308 to 616 V
425 to 737 V
425 to 737 V
486 to 885 V
486 to 885 V
178 to 282 V
308 to 616 V
308 to 616 V
308 to 616 V
308 to 616 V
425 to 737 V
425 to 737 V
486 to 885 V
486 to 885 V
178 to 282 V
308 to 616 V
308 to 616 V
308 to 616 V
308 to 616 V
425 to 737 V
425 to 737 V
486 to 885 V
486 to 885 V
Vector
01 PARAMETER GROUPS
44 FlyStart/RideThru
voltage level under which the line loss will be detected.
d
voltage level that the inverter will try to keep regulated, so that the motor keeps operating.
d
voltage level at which the inverter will identify the return of the line, and from where the
d
0.0 to 63.9
Factory
252 V (P0296 = 0)
436 V (P0296 = 1)
Setting:
459 V (P0296 = 2)
505 V (P0296 = 3)
551 V (P0296 = 4)
602 V (P0296 = 5)
660 V (P0296 = 6)
689 V (P0296 = 7)
792 V (P0296 = 8)
Factory
245 V (P0296 = 0)
423 V (P0296 = 1)
Setting:
446 V (P0296 = 2)
490 V (P0296 = 3)
535 V (P0296 = 4)
585 V (P0296 = 5)
640 V (P0296 = 6)
668 V (P0296 = 7)
768 V (P0296 = 8)
Factory
267 V (P0296 = 0)
462 V (P0296 = 1)
Setting:
486 V (P0296 = 2)
535 V (P0296 = 3)
583 V (P0296 = 4)
638 V (P0296 = 5)
699 V (P0296 = 6)
729 V (P0296 = 7)
838 V (P0296 = 8)
Factory
22.8
Setting: