WEG CFW-11 Programming Manual page 219

V5.8x
Hide thumbs Also See for CFW-11:
Table of Contents

Advertisement

P0155 – Dynamic Braking Resistor Power
Adjustable
0.02 to 650.00 kW
Range:
Properties:
Access groups
01 PARAMETER GROUPS
via HMI:
Description:
This parameter adjusts the trip level of the braking resistor overload protection.
It must be set according to the used braking resistor rated power (in kW).
Operation: if the average power dissipated on the braking resistor exceeds the value adjusted in P0155 for 2
minutes, the inverter will be disabled with F077 – DB Resistor Overload.
In order to get more details on the selection of the braking resistor, refer to the item 3.2.3.2 - Dynamic Braking, of
the user's manual.
28 Dynamic Braking
Dynamic Braking
Factory
2.60 kW
Setting:
14-3
14

Hide quick links: