Vector Control
Description:
Set it according to the used motor nameplate data, taking into consideration the motor voltage.
In the Guided Start-up routine the value adjusted in P0401 automatically modifies the parameters related to the
motor overload protection, according to the
P0402 – Motor Rated Speed
Adjustable
Range:
Properties:
Access groups
via HMI:
Description:
Set it according to the used motor nameplate data.
For V/f and VVW controls the setting is from 0 to 18000 rpm.
For vector control the setting is from 0 to 7200 rpm.
P0403 – Motor Rated Frequency
Adjustable
Range:
Properties:
Access groups
via HMI:
Description:
Set it according to the used motor nameplate data.
For V/f and VVW controls the setting range goes up to 300 Hz.
For vector control the setting range is from 30 Hz to 120 Hz.
P0404 – Motor Rated Power
Adjustable
Range:
Properties:
Access groups
via HMI:
11
Description:
Set it according to the used motor nameplate data.
11-12
Table 11.2 on page
0 to 18000 rpm
CFG
01 PARAMETER GROUPS
43 Motor Data
0 to 300 Hz
CFG
01 PARAMETER GROUPS
43 Motor Data
0 to 60 (refer to the
Table 11.1 on page
CFG
01 PARAMETER GROUPS
43 Motor Data
11-14.
Factory
Setting:
Factory
Setting:
11-13)
Factory
Setting:
1750 rpm
(1458 rpm)
60 Hz
(50 Hz)
Motor
max-ND