WEG CFW-11 Programming Manual

WEG CFW-11 Programming Manual

V5.8x
Hide thumbs Also See for CFW-11:
Table of Contents

Advertisement

Motors | Automation | Energy | Transmission & Distribution | Coatings
Frequency Inverter
CFW-11 V5.8X
Programming Manual

Advertisement

Table of Contents
loading

Summary of Contents for WEG CFW-11

  • Page 1 Motors | Automation | Energy | Transmission & Distribution | Coatings Frequency Inverter CFW-11 V5.8X Programming Manual...
  • Page 3 Programming Manual Series: CFW-11 Language: English Document Number: 10004274148 / 00 Software Version: 5.8X Publication Date: 05/2016...
  • Page 4 Summary of Reviews The table below describes all revisions made to this manual. Version Review Description V5.8X First edition.
  • Page 5: Table Of Contents

    2.2.2 Numerical Representation ..............2-3 2.2.3 Symbols for the Parameter Properties Description ......2-3 3 ABOUT THE CFW-11............... 3-1 3.1 ABOUT THE CFW-11 ................... 3-1 4 KEYPAD (HMI) ................. 4-1 4.1 KEYPAD (HMI) ..................... 4-1 5 PROGRAMMING BASIC INSTRUCTIONS ......... 5-1 5.1 PARAMETER STRUCTURE ................
  • Page 6 Summary 10 VVW CONTROL ................. 10-1 10.1 VVW CONTROL [25] ................10-3 10.2 MOTOR DATA [43] .................. 10-3 10.3 VVW CONTROL MODE START-UP ............10-4 11 VECTOR CONTROL ..............11-1 11.1 SENSORLESS CONTROL AND WITH ENCODER ........11-1 11.2 I/F MODE (SENSORLESS)................. 11-5 11.3 SELF-TUNING ..................
  • Page 7 Summary 13 DIGITAL AND ANALOG INPUTS AND OUTPUTS ......13-1 13.1 I/O CONFIGURATION [07] ..............13-1 13.1.1 Analog Inputs [38] ................. 13-1 13.1.2 Analog Outputs [39] ............... 13-7 13.1.3 Digital Inputs [40] ................ 13-12 13.1.4 Digital Outputs / Relays [41] ............13-20 13.2 LOCAL AND REMOTE COMMAND ............
  • Page 8 Summary 20 PID REGULATOR [46] ..............20-1 20.1 DESCRIPTION AND DEFINITIONS ............20-1 20.2 COMMISSIONING ................... 20-3 20.3 SLEEP MODE ................... 20-8 20.4 MONITORING MODE SCREENS .............. 20-8 20.5 CONNECTION OF A 2-WIRE TRANSDUCER ..........20-9 20.6 PARAMETERS ................... 20-9 20.7 ACADEMIC PID ..................
  • Page 9: Quick Parameter Reference, Faults And Alarms

    Quick Parameter Reference, Faults and Alarms QUICK PARAMETER REFERENCE, FAULTS AND ALARMS User Parameter Function Adjustable Range Factory Setting Properties Groups Pag. Setting P0000 Access to Parameters 0 to 9999 P0001 Speed Reference 0 to 18000 rpm 16-1 P0002 Motor Speed 0 to 18000 rpm 16-1 P0003...
  • Page 10: Quick Parameter Reference, Faults And Alarms

    Quick Parameter Reference, Faults and Alarms User Parameter Function Adjustable Range Factory Setting Properties Groups Pag. Setting P0030 IGBTs Temperature U -20.0 to 150.0 °C 09, 45 16-6 P0031 IGBTs Temperature V -20.0 to 150.0 °C 09, 45 16-6 P0032 IGBTs Temperature W -20.0 to 150.0 °C 09, 45...
  • Page 11 Quick Parameter Reference, Faults and Alarms User Parameter Function Adjustable Range Factory Setting Properties Groups Pag. Setting P0092 Speed At Last Fault 0 to 18000 rpm 16-14 P0093 Reference Last Fault 0 to 18000 rpm 16-14 P0094 Frequency Last Fault 0.0 to 1020.0 Hz 16-14 P0095...
  • Page 12 Quick Parameter Reference, Faults and Alarms User Parameter Function Adjustable Range Factory Setting Properties Groups Pag. Setting P0151 DC Regul. Level V/f 339 to 400 V 400 V (P0296=0) V/f and VVW 9-12 585 to 800 V 800 V (P0296=1) 585 to 800 V 800 V (P0296=2) 585 to 800 V...
  • Page 13 Quick Parameter Reference, Faults and Alarms User Parameter Function Adjustable Range Factory Setting Properties Groups Pag. Setting P0185 DC Link Regul. Level 339 to 400 V 400 V (P0296=0) Vector 11-31 585 to 800 V 800 V (P0296=1) 585 to 800 V 800 V (P0296=2) 585 to 800 V 800 V (P0296=3)
  • Page 14 Quick Parameter Reference, Faults and Alarms User Parameter Function Adjustable Range Factory Setting Properties Groups Pag. Setting P0205 Read Parameter Sel. 1 0 = Not selected 1 = Speed Refer. # 2 = Motor Speed # 3 = MotorCurrent # 4 = DC Link Volt # 5 = Motor Freq.
  • Page 15 Quick Parameter Reference, Faults and Alarms User Parameter Function Adjustable Range Factory Setting Properties Groups Pag. Setting P0220 LOC/REM Selection Src 0 = Always LOC 31, 32, 33, 13-29 1 = Always REM 2 = LR Key LOC 3 = LR Key REM 4 = DIx 5 = Serial/USB LOC 6 = Serial/USB REM...
  • Page 16 Quick Parameter Reference, Faults and Alarms User Parameter Function Adjustable Range Factory Setting Properties Groups Pag. Setting P0229 Stop Mode Selection 0 = Ramp to Stop 31, 32, 33, 13-31 1 = Coast to Stop 2 = Fast Stop 3 = By Ramp with Iq* 4 = Fast Stop with Iq* P0230 Dead Zone (AIs)
  • Page 17 Quick Parameter Reference, Faults and Alarms User Parameter Function Adjustable Range Factory Setting Properties Groups Pag. Setting P0251 AO1 Function 0 = Speed Ref. 13-8 1 = Total Ref. 2 = Real Speed 3 = Torque Cur.Ref 4 = Torque Current 5 = Output Current 6 = Process Var.
  • Page 18 Quick Parameter Reference, Faults and Alarms User Parameter Function Adjustable Range Factory Setting Properties Groups Pag. Setting P0257 AO3 Function 0 = Speed Ref. 13-8 1 = Total Ref. 2 = Real Speed 3 = Torque Cur.Ref 4 = Torque Current 5 = Output Current 6 = Process Var.
  • Page 19 Quick Parameter Reference, Faults and Alarms User Parameter Function Adjustable Range Factory Setting Properties Groups Pag. Setting P0259 AO3 Signal Type 0 = 0 to 20 mA 13-11 1 = 4 to 20 mA 2 = 20 to 0 mA 3 = 20 to 4 mA 4 = 0 to 10 V 5 = 10 to 0 V...
  • Page 20 Quick Parameter Reference, Faults and Alarms User Parameter Function Adjustable Range Factory Setting Properties Groups Pag. Setting P0266 DI4 Function 0 = Not Used 20, 31, 32, 13-13 1 = Run/Stop 33, 34, 36, 2 = General Enable 37, 40, 44, 3 = Fast Stop 45, 46 4 = FWD Run...
  • Page 21 Quick Parameter Reference, Faults and Alarms User Parameter Function Adjustable Range Factory Setting Properties Groups Pag. Setting P0275 DO1 Function (RL1) 0 = Not Used 13-20 1 = N* > Nx 2 = N > Nx 3 = N < Ny 4 = N = N* 5 = Zero Speed 6 = Is >...
  • Page 22 Quick Parameter Reference, Faults and Alarms User Parameter Function Adjustable Range Factory Setting Properties Groups Pag. Setting P0276 DO2 Function (RL2) 0 = Not Used 13-20 1 = N* > Nx 2 = N > Nx 3 = N < Ny 4 = N = N* 5 = Zero Speed 6 = Is >...
  • Page 23 Quick Parameter Reference, Faults and Alarms User Parameter Function Adjustable Range Factory Setting Properties Groups Pag. Setting P0278 DO4 Function 0 = Not Used 13-20 1 = N* > Nx 2 = N > Nx 3 = N < Ny 4 = N = N* 5 = Zero Speed 6 = Is >...
  • Page 24 Quick Parameter Reference, Faults and Alarms User Parameter Function Adjustable Range Factory Setting Properties Groups Pag. Setting P0295 ND/HD VFD Rated Curr. 0 = 3.6 A / 3.6 A 09, 42 1 = 5 A / 5 A 2 = 6 A / 5 A 3 = 7 A / 5.5 A 4 = 7 A / 7 A 5 = 10 A / 8 A...
  • Page 25 Quick Parameter Reference, Faults and Alarms User Parameter Function Adjustable Range Factory Setting Properties Groups Pag. Setting 61 = 8.5 A / 7 A 62 = 10 A / 9 A 63 = 11 A / 9 A 64 = 12 A / 10 A 65 = 15 A / 13 A 66 = 17 A / 17 A 67 = 20 A / 17 A...
  • Page 26 Quick Parameter Reference, Faults and Alarms User Parameter Function Adjustable Range Factory Setting Properties Groups Pag. Setting P0301 DC-Braking Speed 0 to 450 rpm 30 rpm V/f, VVW 12-22 and Sless P0302 DC-Braking Voltage 0.0 to 10.0 % 2.0 % V/f and VVW 12-22 P0303...
  • Page 27 Quick Parameter Reference, Faults and Alarms User Parameter Function Adjustable Range Factory Setting Properties Groups Pag. Setting P0323 DC Link Power Back 178 to 282 V 267 V (P0296=0) Vector 12-18 308 to 616 V 462 V (P0296=1) 308 to 616 V 486 V (P0296=2) 308 to 616 V 535 V (P0296=3)
  • Page 28 Quick Parameter Reference, Faults and Alarms User Parameter Function Adjustable Range Factory Setting Properties Groups Pag. Setting P0357 Line Phase Loss Time 0 to 60 s 15-15 P0358 Encoder Fault Config. 0 = Off CFG and 15-16 1 = F067 ON Encoder 2 = F065, F066 ON 3 = All ON...
  • Page 29 Quick Parameter Reference, Faults and Alarms User Parameter Function Adjustable Range Factory Setting Properties Groups Pag. Setting P0403 Motor Rated Frequency 0 to 300 Hz 60 (50) Hz 05, 43, 94 10-4 P0404 Motor Rated Power 0 = 0.33hp 0.25kW Motor 05, 43, 94 10-4...
  • Page 30 Quick Parameter Reference, Faults and Alarms User Parameter Function Adjustable Range Factory Setting Properties Groups Pag. Setting 0 = No P0408 Run Self-Tuning CFG, VVW 05, 43, 94 11-14 1 = No Rotation and Vector 2 = Run for I 3 = Run for T 4 = Estimate T 0.000 to 9.999 ohm...
  • Page 31 Quick Parameter Reference, Faults and Alarms User Parameter Function Adjustable Range Factory Setting Properties Groups Pag. Setting P0552 Trigger Condition 0 = P0550* = P0551 19-2 1 = P0550* <>P0551 2 = P0550* > P0551 3 = P0550* < P0551 4 = Alarm 5 = Fault 6 = DIx...
  • Page 32 Quick Parameter Reference, Faults and Alarms User Parameter Function Adjustable Range Factory Setting Properties Groups Pag. Setting P0682 Serial/USB Control Bit 0 = Ramp Enable 09, 111 17-1 Bit 1 = General Enable Bit 2 = Run Forward Bit 3 = JOG Enable Bit 4 = Remote Bit 5 = 2nd Ramp Bit 6 = Reserved...
  • Page 33 Quick Parameter Reference, Faults and Alarms User Parameter Function Adjustable Range Factory Setting Properties Groups Pag. Setting P0720 DNet Master Status 0 = Run 09, 112 17-2 1 = Idle P0721 CANopen Comm. Status 0 = Disabled 09, 112 17-2 1 = Reserved 2 = Comm.
  • Page 34 Quick Parameter Reference, Faults and Alarms User Parameter Function Adjustable Range Factory Setting Properties Groups Pag. Setting P0734 Anybus Write Word #3 0 to 1499 17-3 P0735 Anybus Write Word #4 0 to 1499 17-3 P0736 Anybus Write Word #5 0 to 1499 17-3 P0737...
  • Page 35 Quick Parameter Reference, Faults and Alarms User Parameter Function Adjustable Range Factory Setting Properties Groups Pag. Setting P0813 Temper. V-B5/IGBT V5 -20.0 to 150.0 °C CFW-11M 09, 45 15-18 and RO P0814 Temper. W-B5/IGBT W5 -20.0 to 150.0 °C CFW-11M 09, 45 15-18 and RO...
  • Page 36 Quick Parameter Reference, Faults and Alarms User Parameter Function Adjustable Range Factory Setting Properties Groups Pag. Setting P0947 Fault Number 0 to 65535 09, 115 17-4 P0963 Profibus Baud Rate 0 = 9.6 kbit/s 09, 115 17-4 1 = 19.2 kbit/s 2 = 93.75 kbit/s 3 = 187.5 kbit/s 4 = 500 kbit/s...
  • Page 37 Quick Parameter Reference, Faults and Alarms User Parameter Function Adjustable Range Factory Setting Properties Groups Pag. Setting P1028 SoftPLC Parameter 19 -32768 to 32767 18-1 P1029 SoftPLC Parameter 20 -32768 to 32767 18-1 P1030 SoftPLC Parameter 21 -32768 to 32767 18-1 P1031 SoftPLC Parameter 22...
  • Page 38 Quick Parameter Reference, Faults and Alarms Fault/Alarm Description Possible Causes F006 Mains voltage imbalance too high or phase missing Phase missing at the inverter's input power supply. Imbalance or in the input power supply. Input voltage imbalance >5 %. Input Phase Loss Note: For the Frame Size E: - If the motor is unloaded or operating with reduced...
  • Page 39 Quick Parameter Reference, Faults and Alarms Fault/Alarm Description Possible Causes A050 A high temperature alarm was detected by the NTC Surrounding air temperature is too high (>50 °C (122 °F)) IGBT High Temperature U temperature sensors located on the IGBTs. and output current is too high.
  • Page 40 Alarm that indicates an access error to the Defective, unrecognized, or improperly installed Anybus-CC Anybus Access Error Anybus-CC communication module. module. Conflict with a WEG option board. A133 Alarm indicating that the power supply was not Broken or loose cable. CAN Not Powered connected to the CAN controller.
  • Page 41 Quick Parameter Reference, Faults and Alarms Fault/Alarm Description Possible Causes A138 It indicates that the inverter received a command Verify the network master status, making sure it is in Profibus DP Interface in from the Profibus DP network master to enter the execution mode (Run).
  • Page 42 Quick Parameter Reference, Faults and Alarms Fault/Alarm Description Possible Causes F183 Overtemperature related to the IGBTs overload Surrounding air temperature too high. IGBT Overload + protection. Operation with frequencies < 10 Hz under overload. Temperature F185 It indicates fault at the pre-charge Contactor. Pre-charge contactor defect.
  • Page 43 Quick Parameter Reference, Faults and Alarms Fault/Alarm Description Possible Causes F238 Refer to the Profibus DP communication manual. Profibus DP Interface in Clear Mode F239 Offline Profibus DP Interface F240 Profibus DP Module Access Error A300 High temperature alarm measured with the High ambient temperature and high output current.
  • Page 44 Quick Parameter Reference, Faults and Alarms Fault/Alarm Description Possible Causes F322 Overtemperature fault measured with the temperature High ambient temperature and high output current. (10) Overtemperature at IGBT sensor (NTC) of the book 3 V phase IGBT. Blocked or defective fan. V B3 Fins of the book heatsink too dirty, impairing the air flow.
  • Page 45 Quick Parameter Reference, Faults and Alarms Fault/Alarm Description Possible Causes A357 Overload alarm at book 2 V phase IGBT. High current at the inverter output (see figure 8.1 of the (10) High Load at IGBT V B2 CFW-11M user's manual). F358 Overload fault at book 2 V phase IGBT.
  • Page 46 Quick Parameter Reference, Faults and Alarms Fault/Alarm Description Possible Causes A391 Phase V book 1current unbalance alarm. Bad electric connection between the DC bus and the (10) Current Unbalance at It indicates a 20 % unbalance in the current power unit. Phase V B1 distribution between this phase and the smallest Bad electric connection between the power unit output...
  • Page 47 Quick Parameter Reference, Faults and Alarms Fault/Alarm Description Possible Causes A402 Phase U book 5 current unbalance alarm. Bad electric connection between the DC bus and the (10) Current Unbalance at It indicates a 20 % unbalance in the current power unit.
  • Page 48 Quick Parameter Reference, Faults and Alarms Models where they can occur: (1) All the models from frame size A to G. (2) CFW110086T2, CFW110105T2, CFW110045T4, CFW110058T4, CFW110070T4 and CFW110088T4. (3) All the models of frame sizes D and E. (4) All the models of frame sizes A, B and C. (5) With a Profibus DB module connected into the slot 3 (XC43).
  • Page 49: Safety Instructions

    Safety Instructions 1 SAFETY INSTRUCTIONS This Manual contains the information necessary for the correct use of the CFW-11 Frequency Inverter. It has been developed to be used by qualified personnel with suitable training or technical qualification for operating this type of equipment.
  • Page 50: Preliminary Recommendations

    NOTE! For the purposes of this manual, qualified personnel are those trained to be able to: 1. Install, ground, energize and operate the CFW-11 according to this manual and the effective legal safety procedures. 2. Use protection equipment according to the established standards.
  • Page 51: General Information

    This manual presents the necessary information for the configuration of all of the functions and parameters of the CFW-11 Frequency Inverter. This manual must be used together with the CFW-11 user's manual. The text intents to supply additional information to facilitate the use and programming of the CFW-11 in specific applications.
  • Page 52 General Information NTC: It’s a resistor whose resistance value in ohms decreases proportionally to the temperature increase; it is used as a temperature sensor in power modules. Keypad (HMI): Human-Machine Interface; It is the device that allows the control of the motor, the visualization and the modification of the inverter parameters.
  • Page 53: Numerical Representation

    General Information kHz: kilohertz = 1000 Hz. mA: milliamp = 0.001 Amp. min: minute. ms: millisecond = 0.001 second. Nm: newton meter; torque measurement unit. rms: "Root Mean Square"; effective value. rpm: revolutions per minute: speed measurement unit. s: second. V: volt.
  • Page 54 General Information...
  • Page 55: About The Cfw-11

    3 ABOUT THE CFW-11 3.1 ABOUT THE CFW-11 The CFW-11 is a high performance Frequency Inverter that makes it possible the control of speed and torque of three-phase AC induction motors. The principal characteristic of this product is the "Vectrue" technology, which presents the following advantages: Scalar Control (V/f), VVW or vector control programmable in the same product.
  • Page 56 (Slot 3 – green) Board with Analog Inputs 32-bit (AI1 and AI2) "RISC" CPU COMM 2 (Anybus) (Slot 4) FLASH Analog Outputs Memory (AO1 and AO2) Module Digital Outputs (Slot 5) DO1(RL1) to DO3 (RL3) ƒ=Human-Machine Interface Figure 3.1 - CFW-11 block diagram...
  • Page 57 E – COMM 2 module (Anybus) F – Accessory board module G – FLASH memory module H – Front cover I – Keypad (HMI) Figure 3.2 - CFW-11 main components USB connector USB LED Off: without USB connection On/blinking: USB communication active...
  • Page 58 About the CFW-11...
  • Page 59: Keypad (Hmi)

    Keypad (HMI) 4 KEYPAD (HMI) 4.1 KEYPAD (HMI) Through the keypad (HMI) it is possible to command the inverter, visualize and adjust all the parameters. It presents a navigation manner similar to the one used in cell phones, with options to access the parameters sequentially or by means of groups (menu).
  • Page 60 Keypad (HMI) Cover Cover for battery access Remove the cover Press the cover and rotate it counterclockwise Remove the battery with the help HMI without the battery Install the new battery positioning it of a screwdriver positioned in first at the left side the right side Press the battery for its insertion Put the cover back and rotate it clockwise...
  • Page 61: Programming Basic Instructions

    The reset to the factory default may change the content of the parameters related to the frequency (50 Hz/60 Hz). In the detailed description, some parameters present values in parentheses, which must be adjusted in the inverter for using the 50 Hz frequency. Table 5.1 - CFW-11 parameter groups structure Level 0 Level 1...
  • Page 62: Groups Accessed In The Option Menu In The Monitoring Mode

    Only parameters whose contents are different from the factory settings Parameters for simple applications: ramps, minimum and maximum speed, maximum current and BASIC APPLICATION torque boost. Presented in details in the CFW-11 user's manual at section 5.2.3 - Setting Basic Application Parameters SELF-TUNING...
  • Page 63: Password Setting In P0000

    Programming Basic Instructions 5.3 PASSWORD SETTING IN P0000 P0000 – Access to Parameters Adjustable 0 to 9999 Factory Range: Setting: Properties: Access groups 00 ALL PARAMETERS via HMI: In order to be able to change the content of the parameters, it is necessary to set correctly the password in P0000, as indicated below.
  • Page 64: Hmi [30]

    Programming Basic Instructions 5.4 HMI [30] In the group "30 HMI" are the parameters related to the presentation of information on the keypad (HMI) display. See next the detailed description of the possible settings for those parameters. P0193 – Day of the Week Adjustable 0 = Sunday Factory...
  • Page 65 Description: Those parameters set the date and time of the CFW-11 real time clock. It is important to configure them with the correct date and time so that the fault and alarm record occurs with actual date and time information.
  • Page 66 Programming Basic Instructions P0205 – Reading Parameter Selection 1 P0206 – Reading Parameter Selection 2 P0207 – Reading Parameter Selection 3 Adjustable 0 = Not selected Factory P0205 = 2 1 = Speed Reference # Range: Setting: P0206 = 3 2 = Motor Speed # P0207 = 5 3 = Motor Current #...
  • Page 67 Programming Basic Instructions P0208 – Reference Scale Factor Adjustable 1 to 18000 Factory 1800 Range: Setting: (1500) P0212 – Reference Decimal Point Adjustable 0 = wxyz Factory Range: 1 = wxy.z Setting: 2 = wx.yz 3 = w.xyz Properties: Access groups 01 PARAMETER GROUPS via HMI: 30 HMI...
  • Page 68 Programming Basic Instructions P0209 – Reference Engineering Unit 1 P0210 – Reference Engineering Unit 2 P0211 – Reference Engineering Unit 3 Adjustable 32 to 127 Factory P0209 = 114 (r) Range: Setting: P0210 = 112 (p) P0211 = 109 (m) Properties: Access groups 01 PARAMETER GROUPS...
  • Page 69: Date And Time Setting

    Programming Basic Instructions P0216 – HMI Display Contrast Adjustable 0 to 37 Factory Range: Setting: Properties: Access groups 01 PARAMETER GROUPS via HMI: 30 HMI Description: It allows setting the keypad (HMI) display contrast level. Higher values configure a higher contrast level. 5.5 DATE AND TIME SETTING Seq.
  • Page 70: Display Indications In The Monitoring Mode Settings

    Programming Basic Instructions 5.6 DISPLAY INDICATIONS IN THE MONITORING MODE SETTINGS Every time the inverter is powered the display goes to the Monitoring Mode. In order to make it easier the reading of the motor main parameters, the keypad (HMI) display can be configured to show them in 3 different modes. Content of the 3 parameters in numerical form: Selection of the parameters via P0205, P0206 and P0207.
  • Page 71 Programming Basic Instructions Seq. Action/Result Display Indication Seq. Action/Result Display Indication - Monitoring Mode. Ready 0rpm - Press until Ready 0rpm - Press "Menu" P0205 selecting the option (right "soft key"). "[11] Speed Refer. –". Read Parameter Sel. 1 [011] Speed Refer. - - Press "Save".
  • Page 72: Incompatibility Between Parameters

    Programming Basic Instructions 5.7 INCOMPATIBILITY BETWEEN PARAMETERS If any of the combinations listed below occur, the CFW-11 goes to the "Config" state. Two or more DIx (P0263...P0270) programmed for (4 = FWD Run). Two or more DIx (P0263...P0270) programmed for (5 = REV Run).
  • Page 73 Inverter Model and Accessories Identification 25) [P0221 or P0222 programmed for (7 = E.P .)] AND [without DIx (P0263...P0270) programmed for (11 = Increase E.P .) OR without DIx (P0263...P0270) programmed for (12 = Decrease E.P .)]. 26) [P0221 and P0222 not programmed for (7 = E.P .)] AND [with DIx (P0263...P0270) programmed for (11 = Increase E.P .) OR with DIx (P0263...P0270) programmed for (12 = Decrease E.P .)].
  • Page 74 Inverter Model and Accessories Identification 5-14...
  • Page 75: Inverter Model And Accessories Identification

    Once the inverter model identification code is verified, one must interpret it in order to understand its meaning. Refer to the table present in the section 2.4 - Identification Labels for the CFW-11, of the CFW-11 user's manual and in the section 2.6 - How to Specify the CFW-11M Model (Smart Code), of the CFW-11M user's manual.
  • Page 76: Inverter Data [42]

    For the accessories installed in the slots 1 and 2 the identification code is informed at the parameter P0027. In case of modules connected in the slots 3, 4 or 5, the code will be shown through the parameter P0028. Table 6.1 on page 6-3 shows the codes shown in those parameters, regarding the main CFW-11 accessories.
  • Page 77 Inverter Model and Accessories Identification Table 6.1 - CFW-11 accessory identification codes Identification Code Name Description Slot P0027 P0028 Module with 2 14-bit analog inputs, 2 digital inputs, 2 14-bit analog IOA-01 FD-- ---- outputs in voltage or current, 2 open collector digital outputs...
  • Page 78 Inverter Model and Accessories Identification Table 6.4 - Example of the two first characters of the code showed in P0028 for PROFIBUS DP-05 and FLASH memory module P0029 – Power Hardware Configuration Adjustable Bit 0 to 5 = Rated Current Factory Range: Bit 6 and 7 = Rated Voltage...
  • Page 79 Inverter Model and Accessories Identification Table 6.6 - Current codification for the parameter P0029 Bits Bits Frame Size Voltage Current 2 A* 6 A* 7 A* 10 A 10 A 13 A 16 A 24 A 200... 240 V 28 A 33.5 A 45 A 54 A...
  • Page 80 * Models with single-phase/three-phase power supply. Example: For a 10 V, 380...480 V CFW-11, with RFI suppressor filter, without safety relay and without external 24 V supply, the hexadecimal code presented in the keypad (HMI) for the parameter P0029 is C544 (refer to the Table 6.7...
  • Page 81 Inverter Model and Accessories Identification P0295 – ND/HD VFD Rated Current Adjustable 0 = 3.6 A / 3.6 A Factory Range: 1 = 5 A / 5 A Setting: 2 = 6 A / 5 A 3 = 7 A / 5.5 A 4 = 7 A / 7 A 5 = 10 A / 8 A 6 = 10 A / 10 A...
  • Page 82 Inverter Model and Accessories Identification 63 = 11 A / 9 A 64 = 12 A / 10 A 65 = 15 A / 13 A 66 = 17 A / 17 A 67 = 20 A / 17 A 68 = 22 A / 19 A 69 = 24 A / 21 A 70 = 27 A / 22 A...
  • Page 83 When changed from P0296 = 5, 6 or 7 to P0296 = 8 or vice-versa, the following parameters could be changed automatically: P0029, P0135, P0156, P0157, P0158, P0290, P0295, P0297, P0401 and P0410. Table 6.8 - P0296 setting according to the CFW-11 inverter model Inverter Model Adjustable Range...
  • Page 84 Refer to the allowed current for switching frequencies different from the default, in the tables available in chapter 8 - Technical Specifications, of the CFW-11 user's manual. The inverter switching frequency can be adjusted according to the needs of the application.
  • Page 85 The I and I are presented in P0295. Refer to the CFW-11 user's manual chapter 8 - Technical Specifications, nom-ND nom-HD for more details regarding these operation regimens.
  • Page 86 Inverter Model and Accessories Identification 6-12...
  • Page 87: Starting-Up And Settings

    7-1, described next. 7.1 BACKUP PARAMETERS [06] The CFW-11 BACKUP functions allow saving the content of the current inverter parameters in a specific memory, or vice-versa (overwrite the contents of the current parameters with the memory contents). Besides, there is a function exclusive for software update, by means of the FLASH Memory Module.
  • Page 88 Memory 3 Figure 7.1 - Parameter transfer In order to load parameters from User 1, User 2 and/or User 3 to the CFW-11 operation area (P0204 = 7, 8 or 9), it is necessary that these areas had been saved previously.
  • Page 89 Starting-up and Settings P0317 - Oriented Start-up Adjustable 0 = No Factory Range: 1 = Yes Setting: Properties: Access groups 02 ORIENTED START-UP via HMI: Description: When this parameter is changed to “1”, the Oriented Start-up routine starts. The CFW11 goes into the “CONF” state, which is indicated on the HMI.
  • Page 90 Starting-up and Settings NOTE! Valid for P0318 = 1. When the inverter is powered and the memory module is present, the current parameter contents are compared with the contents of the parameters saved in the MMF and, in case they are different, the keypad (HMI) will exhibit the message "Flash Mem.Module with different parameters", after 3 seconds the message is replaced by the parameter P0318 menu.
  • Page 91 Starting-up and Settings Example: Version V1.60 → (x = 1, y = 6 and z = 0) previously stored in the keypad (HMI)  Inverter version: V1.75 → (x’ = 1, y’ = 7 and z’ = 5) P0319 = 2 → F082 [(y = 6) → (y’ = 7)]  Inverter version: V1.62 →...
  • Page 92 Starting-up and Settings 8. In order to copy the contents of the Inverter A parameters to other inverters, repeat the same procedures 5 to 7 described previously. INVERTER INVERTER Parameters Parameters INV → HMI HMI → INV EEPROM EEPROM Figure 7.2 - Parameter copy from "Inverter A" to the "Inverter B" NOTE! As long as the keypad (HMI) is performing the reading or the writing procedure, it will not be possible to operate it.
  • Page 93: Available Control Types

    (programmable); it allows multimotor operation.  VVW: Voltage Vector WEG; it allows a static speed control more accurate than the V/f mode; it adjusts itself automatically to the line variations, and also to the load variations, however it does not present fast dynamic response.
  • Page 94 Available Control Types...
  • Page 95: Scalar Control (V/F)

    Scalar Control (V/f) 9 SCALAR CONTROL (V/F) It consists of a simple control based on a curve that links output voltage and frequency. The inverter operates as a voltage source, generating frequency and voltage values according to that curve. It is possible to adjust this curve to standard 50 Hz or 60 Hz motors or to special ones through the adjustable V/f curve.
  • Page 96: V/F Control [23]

    Scalar Control (V/f) 9.1 V/F CONTROL [23] P0136 – Manual Torque Boost Adjustable 0 to 9 Factory According Range: Setting: to inverter model Properties: Access groups 01 PARAMETER GROUPS via HMI: 23 V/f Control Description: It acts at low speeds, increasing the inverter output voltage in order to compensate the voltage drop across the motor stator resistance, with the purpose of keeping the torque constant.
  • Page 97 Scalar Control (V/f) P0007 P0136 Voltage Applied to Speed Reference I x R the Motor P0137 Active Output Automatic Current I x R P0139 Figure 9.3 - Torque Boost block diagram Output Voltage Nominal 1/2 Nominal Compensation Zone Speed nom/2 Figure 9.4 - Effect of P0137 on the V/f curve (P0202 = 0…2) P0138 –...
  • Page 98 Scalar Control (V/f) Total Reference (Refer to Figure 9.1 on page 9-1) Speed ∆ F Output Slip Compensation Active Current P0139 P0138 Figure 9.5 - Slip compensation block diagram Output Voltage ∆V (function of the motor load) ∆F Speed Figure 9.6 - V/f curve with slip compensation For the adjustment of the parameter P0138 to compensate the motor slip: 1) Run the motor with no load at approximately half the working speed.
  • Page 99 (P0320 = 1 or 2). P0202 – Type of Control Adjustable 0=V/f 60 Hz Factory Range: 1=V/f 50 Hz Setting: 2=V/f Adjustable 3=Sensorless 4=Encoder 5=VVW (Voltage Vector WEG) 6=Encoder PM 7=Sensorless PM Properties: Access groups 01 PARAMETER GROUPS via HMI: 23 V/f Control...
  • Page 100: Adjustable V/F Curve [24]

    Scalar Control (V/f) Description: In order to get an overview of the control types, as well as orientation to choose the most suitable type for the application, refer to the Chapter 8 AVAILABLE CONTROL TYPES on page 8-1. For the V/f mode, select P0202 = 0, 1 or 2: Parameter P0202 setting for the V/f mode:  P0202 = 0 for motors with rated frequency = 60 Hz.
  • Page 101: V/F Current Limitation [26]

    Scalar Control (V/f) The factory setting of P0144 (8.0 %) is adequate for standard motors with rated frequency of 60 Hz. When using a motor with rated frequency (adjusted in P0403) different from 60 Hz, the default value for P0144 may become inadequate, being able to cause difficulties in the motor starting.
  • Page 102 Scalar Control (V/f) Description: It is the current limitation for the V/f control with actuation mode defined by P0344 (refer to the Table 9.1 on page 9-8) and the current limit defined by P0135. Table 9.1 - Current limitation configuration P0344 Function Description...
  • Page 103 Scalar Control (V/f) Motor current Motor current P0135 P0135 Time Time Speed Speed Deceleration via ramp Acceleration (P0101) via ramp (P0100) Time Time During acceleration During deceleration (a) "Ramp Hold" Motor current Time P0135 Time Speed Decelerates via ramp P0101 Time (b) "Ramp Deceleration"...
  • Page 104: V/F Dc Voltage Limitation [27]

    Scalar Control (V/f) 9.4 V/F DC VOLTAGE LIMITATION [27] There are two functions in the inverter for limiting the DC link voltage during the motor braking. They act limiting the braking torque and power, avoiding therefore the tripping of the inverter by overvoltage (F022). The overvoltage on the DC link is more common when a load with high inertia is driven or when a short deceleration time is programmed.
  • Page 105 Scalar Control (V/f) DC Link Voltage (P0004) F022 – Overvoltage DC Link Regulation P0151 Nominal U Time Output Speed Time Figure 9.11 - Example of the DC link voltage limitation working with the Ramp Hold function 2 - Ramp Acceleration: It is effective in any situation, regardless of the motor speed condition, accelerating, decelerating or at constant speed.
  • Page 106 Scalar Control (V/f) DC Link Voltage (P0004) F022-Overvoltage P0151 DC Link Regulation Nominal U Time Output Speed Time Figure 9.13 - Example of the DC link voltage limitation working with the Ramp Acceleration function P0150 – DC Regulator Type (V/f) Adjustable 0 = Ramp Hold Factory...
  • Page 107: Energy Saving Function

    Scalar Control (V/f) Description: It is the actuation level of the DC link voltage limitation function for the V/f mode. Setting of P0151 value: a) The P0151 factory setting leaves inactive the DC link voltage limitation function for the V/f mode. In order to activate it, one must reduce the value of P0151 as suggested in the Table 9.2 on page 9-13.
  • Page 108 Scalar Control (V/f) The energy saving function reduces the motor losses when it is running with loads significantly below the rated load. The efficiency is increased by reducing the motor flux, which is kept saturated for any load value. The function is active when the applied load is smaller than the value set in P0588, and the motor effective speed is higher than the value set in P0589.
  • Page 109: Start-Up In The V/F Control Mode

    Read the whole CFW-11 user's manual before installing, powering or operating the inverter. Sequence for installation, verification, powering and start-up: a) Install the inverter: according to the chapter 3 – Installation and Connection of the CFW-11 user's manual, wiring all the power and control connections.
  • Page 110 5-3, of this manual. d) Adjust the inverter to operate with the application line and motor: execute the Oriented Start-up routine according to the item 5.2.2 - Oriented Start-Up, of the CFW-11 user's manual. Refer to the Section 11.7 MOTOR DATA [43] on page 11-10, of this manual.
  • Page 111: Vvw Control

    VVW Control 10 VVW CONTROL The VVW (Voltage Vector WEG) control mode uses a control method with intermediate performance between V/f and Sensorless Vector. Refer to the Figure 10.1 on page 10-2 block diagram. The main advantage compared to the V/f control is the better speed regulation with higher torque capability at low speeds (frequencies below 5 Hz), allowing a sensible improvement of the inverter performance in permanent regimen.
  • Page 112 VVW Control Figure 10.1 - VVW control block diagram 10-2...
  • Page 113: Motor Data [43]

    VVW Control 10.1 VVW CONTROL [25] The parameter group [25] – VVW Control – contains only 5 parameters related to that function: P0139, P0140, P0141, P0202 and P0397. However, since the parameters P0139, P0140, P0141 and P0202 were already presented in the Section 9.1 V/F CONTROL [23] on page 9-2, only the parameter P0397 will be described next.
  • Page 114: Vvw Control Mode Start-Up

    The default value of this parameter is adjusted automatically when the parameter P0404 is changed. The suggested value is valid for three-phase, IV pole WEG motors. For other motor types the setting must be done manually. P0408– Run Self-Tuning P0409 –...
  • Page 115 VVW Control b) Prepare the inverter and apply power: according to the section 5.1 - Prepare for Start-Up, of the CFW-11 user's manual. c) Adjust the password P0000 = 5: according to the Section 5.3 PASSWORD SETTING IN P0000 on page 5-3, of this manual.
  • Page 116 VVW Control Seq. Action/Result Display Indication Seq. Action/Result Display Indication Ready 0rpm Config 0rpm - Monitoring Mode. Language - Press "Menu" P0201: English - Set the content of P0202 Type of Control (right "soft key"). pressing "Select". P0202: V/f 60Hz 13:48 Menu Reset...
  • Page 117 VVW Control Seq. Action/Result Display Indication Seq. Action/Result Display Indication - If necessary, change - If necessary, change the content of P0400 the content of P0406 Config 0rpm according to the motor according to the motor Config 0rpm Motor Rated Power rated voltage.
  • Page 118 VVW Control 10-8...
  • Page 119: Vector Control

    Another advantage of this control type is the greater robustness against sudden line voltage and load changes, avoiding unnecessary overcurrent trips. The necessary settings for the good operation of the sensorless vector control are done automatically. Therefore the used motor must be connected to the CFW-11 inverter. 11-1...
  • Page 120 Vector Control Figure 11.1 - Sensorless vector control block diagram 11-2...
  • Page 121 Vector Control The Vector Control with Encoder presents the same advantages of the sensorless control previously described, with the following additional benefits:  Torque and speed control down to 0 (zero) rpm.  Speed control accuracy of 0.01 % (if the 14-bit analog speed reference via optional board IOA-01 is used, or if digital references are used, for instance via keypad (HMI), Profibus DP , DeviceNet, etc.).
  • Page 122 Vector Control Figure 11.2 - Vector with encoder control block diagram 11-4...
  • Page 123: I/F Mode (Sensorless)

    In the option P0408 = 1 (No Rotation) the motor remains stopped throughout the self-tuning. The magnetizing current value (P0410) is obtained from a table, valid for WEG motors up to 12 poles. In the option P0408 = 2 (Run for I ) the value of P0410 is estimated with the motor rotating and the load decoupled from the motor shaft.
  • Page 124: Optimal Flux For Sensorless Vector Control

    Active function only on the Sensorless Vector mode (P0202 = 3), if P0406 = 2. The Optimal Flux function can be used for driving some types of WEG motors (*) making it possible the operation at low speed with rated torque without the need of forced ventilation on the motor. The frequency range for operation is 12:1, i.e., from 5 Hz to 60 Hz for 60 Hz rated frequency motors and from 4.2 Hz to 50 Hz for...
  • Page 125: Torque Control

    Vector Control NOTE! (*) WEG motors that can be used with the Optimal Flux function: Nema Premium Efficiency, Nema High Efficiency, IEC Premium Efficiency, IEC Top Premium Efficiency and "Alto Rendimento Plus". When this function is activating, the motor flux is controlled in a way to reduce their electric losses on slow speeds.
  • Page 126: Optimal Braking

    - In the vector with encoder control type set the speed regulator for the mode "saturated" (P0160 = 1), besides keeping the regulator in the saturated state. NOTE! The motor rated current must be equivalent to the CFW-11 rated current, in order that the torque control has the best possible accuracy. Settings for the torque control: Torque limitation: 1.
  • Page 127 Vector Control The Optimal Braking makes it possible braking the motor with a higher torque than the one obtained with traditional methods, as for instance, the braking by the injection of direct current (DC braking). In the DC braking case, only the losses in the motor rotor are used to dissipate the energy stored as the mechanic load inertia, rejecting the total friction losses.
  • Page 128: Motor Data [43]

    Vector Control 1 hp/0.75 kW, IV poles: η = 0.76 resulting in TB1 = 0.32. Examples: 20 hp/15.0 kW, IV poles: η = 0.86 resulting in TB1 = 0.16. Figure 11.3 - T x N curve for Optimal Braking with a typical 10 hp/7.5 kW motor, driven by an inverter with the torque adjusted at a value equal to the motor rated torque (a) Torque generated by the motor in normal operation, driven by the inverter in the "motor mode"...
  • Page 129 Vector Control P0398 – Motor Service Factor Adjustable 1.00 to 1.50 Factory 1.00 Range: Setting: Properties: Access groups 01 PARAMETER GROUPS via HMI: 43 Motor Data Description: It is the continuous overload capability, i.e., a reserve of power that gives the motor the capability to withstand working in adverse conditions.
  • Page 130 Vector Control Description: Set it according to the used motor nameplate data, taking into consideration the motor voltage. In the Guided Start-up routine the value adjusted in P0401 automatically modifies the parameters related to the motor overload protection, according to the Table 11.2 on page 11-14.
  • Page 131 Vector Control Table 11.1 - P0404 (Motor Rated Power) setting Motor Rated Motor Rated P0404 P0404 Power (hp) Power (hp) 0.33 300.0 0.50 350.0 0.75 380.0 400.0 430.0 440.0 450.0 475.0 500.0 540.0 600.0 620.0 10.0 670.0 12.5 700.0 15.0 760.0 20.0 800.0...
  • Page 132 Vector Control P0406 – Motor Ventilation Adjustable 0 = Self-Ventilated Factory Range: 1 = Separate Ventilation Setting: 2 = Optimal Flux 3 = Extended Protection Properties: Access groups 01 PARAMETER GROUPS via HMI: 43 Motor Data Description: During the Oriented Start-up Routine, the value adjusted in P0406 changes the parameters related to the motor overload automatically, in the following manner: Table 11.2 - Motor overload protection modification in function of P0406 P0406...
  • Page 133: Adjustment Of The Parameters P0409 To P0412 Based On The Motor Data Sheet

    Vector Control 11.7.1 Adjustment of the Parameters P0409 to P0412 Based on the Motor Data Sheet Being in the possession of the motor equivalent circuit data, it is possible to calculate the value to be programmed in the parameters from P0409 to P0412, instead of using the self-tuning to obtain them. Input data: Motor data sheet: = Nominal voltage informed in the motor data, in Volts;...
  • Page 134 P412= T For conditions not included above, contact WEG. 11.8 VECTOR CONTROL [29] 11.8.1 Speed Regulator [90] The parameters related to the CFW-11 speed regulator are presented in this group. P0160 – Speed Regulator Configuration Adjustable 0 = Normal Factory...
  • Page 135: Vector Control [29]

    Vector Control P0161 – Speed Regulator Proportional Gain Adjustable 0.0 to 63.9 Factory Range: Setting: P0162 – Speed Regulator Integral Gain Adjustable 0.000 to 9.999 Factory 0.005 Range: Setting: Properties: PM and Vector Access groups 01 PARAMETER GROUPS via HMI: 29 Vector Control 90 Speed Regulator Description:...
  • Page 136 Vector Control 7. Adjust P0161 and P0162 according to the response type presented in the Figure 11.4 on page 11-17. a) Reduce the proportional gain (P0161) and/or increase the integral gain (P0162). b) Speed regulator is optimized. c) Increase the proportional gain and/or reduce the integral gain. In the sensorless vector control mode, the maximum typical values for proportional gain P0161 must not be greater than 9.0.
  • Page 137: Current Regulator [91]

    P0166 Differential gain actuation 0.00 Inactive 0.01 a 7.99 Active 11.8.2 Current Regulator [91] The parameters related to the CFW-11 current regulator are presented in this group. P0167 – Current Regulator Proportional Gain Adjustable 0.00 to 1.99 Factory 0.50 Range: Setting: P0168 –...
  • Page 138: Flux Regulator [92]

    Vector Control 11.8.3 Flux Regulator [92] The parameters related to the CFW-11 flux regulator are presented next. P0175 – Flux Regulator Proportional Gain Adjustable 0.0 to 31.9 Factory Range: Setting: P0176 – Flux Regulator Integral Gain Adjustable 0.000 to 9.999 Factory 0.020...
  • Page 139 Vector Control P0181 – Magnetization Mode Adjustable 0 = General Enable Factory Range: 1 = Run/Stop Setting: Properties: CFG and Encoder Access groups 01 PARAMETER GROUPS via HMI: 29 Vector Control 92 Flux Regulator Description: Table 11.4 - Magnetization Mode P0181 Action 0 = General Enable...
  • Page 140: I/F Control [93]

    Vector Control Description: This parameter defines the value of the maximum output voltage. Its standard value is defined in the condition of the nominal supply voltage. The voltage reference used in the regulator "Maximum output voltage" (see the Figure 11.1 on page 11-2 Figure 11.2 on page 11-4) is directly proportional to the voltage supply.
  • Page 141: Self-Tuning [05] And [94]

    Vector Control P0183 – Current in the I/f Mode Adjustable 0 to 9 Factory Range: Setting: Properties: Sless Access groups 01 PARAMETER GROUPS via HMI: 29 Vector Control 93 I/F Control Description: It defines the current to be applied to the motor when the inverter is operating in the I/f mode, i.e., with the motor speed below the value defined by P0182.
  • Page 142 Vector with encoder P0413 P0408 = 1 – No rotation: The motor stands still during the self-tuning. The P0410 value is obtained from a table, valid for WEG motors up to 12 poles. NOTE! Therefore P0410 must be equal to zero before initiating the self-tuning. If P0410≠0, the self-tuning routine will keep the existent value.
  • Page 143 The parameter P0413 (Mechanic time constant – Tm) will be adjusted to a value close to the motor mechanic time constant. Therefore, the motor rotor inertia (table data valid for WEG motors), the inverter rated voltage and current are taken into consideration.
  • Page 144 WEG motors, when P0408 = 1 (No rotation). When a standard WEG motor is not used and it is not possible to run the self-tuning with P0408 = 2 (Run for I then adjust P0410 with a value equal to the motor no load current, before initiating the self-tuning.
  • Page 145 1.2 / 1.3 0.9 / 1.0 NOTE! When adjusted via the keypad (HMI), this parameter may change automatically the following parameters: P0175, P0176, P0327 and P0328. For motors larger than 500 CV, contact WEG. P0413 – T Constant (Mechanical Time Constant) Adjustable 0.00 to 99.99 s...
  • Page 146: Torque Current Limitation [95]

    Vector Control Description: This parameter is automatically adjusted during the self-tuning. The P0413 setting determines the speed regulator gains (P0161 and P0162). When P0408 = 1 or 2, it must be observed: If P0413 = 0, the time constant T will be obtained in function of the inertia of the programmed motor (table value).
  • Page 147 Vector Control Description: These parameters limit the motor current component that produces "+" (P0169) or "-" (P0170) torque. The adjustment is expressed as a percentage of the motor nominal torque current. The positive torque occurs when the motor drives the load in the clockwise direction, or the load drives the motor in the counterclockwise direction.
  • Page 148: Dc Link Regulator [96]

    11-30. 11.8.7 DC Link Regulator [96] For the deceleration of high inertia loads with short deceleration times, the CFW-11 has available the DC Link Regulation function, which avoids the tripping of the inverter by overvoltage in the DC link (F022).
  • Page 149 Vector Control P0184 – DC Link Regulation Mode Adjustable 0 = With losses Factory Range: 1 = Without losses Setting: 2 = Enable/Disable DIx Properties: CFG, PM and Vector Access groups 01 PARAMETER GROUPS via HMI: 29 Vector Control 96 DC Link Regulator Description: It enables or disables the Optimal Braking function (Section 11.6 OPTIMAL BRAKING on page...
  • Page 150 Vector Control Description: This parameter defines the DC link voltage regulation level during the braking. During the braking, the time of the deceleration ramp is automatically extended, thus avoiding an overvoltage fault (F022). The setting of the DC link regulation can be done in two manners: 1.
  • Page 151: Droop Function [90]

    Vector Control 11.8.8 DROOP Function [90] The DROOP function is used in applications of load distribution, where two or more inverter/motor sets run a load that mechanically couples the motors, and in which little speed variations between the motors are acceptable. For the application of the DROOP function, it is recommended that the sets used (motors/inverters) be equivalent and present similar dynamic responses.
  • Page 152: Start-Up In The Vector Modes Sensorless And With Encoder

    Install the inverter: according to the chapter 3 – Installation and Connection of the CFW-11 user's manual, wiring all the power and control connections. b) Prepare the inverter and apply power: according to the section 5.1 - Prepare for Start-Up, of the CFW-11 user's manual.
  • Page 153 Parameters P0409 to P0412 Based on the Motor Data Sheet on page 11-15, of this manual. - Manually, copying the contents of the parameters from another CFW-11 inverter, which uses and identical motor. e) Setting of specific parameters and functions for the application: set the digital and analog inputs and outputs, HMI keys, etc., according to the application needs.
  • Page 154 Vector Control Seq. Action/Result Display Indication Seq. Action/Result Display Indication - Monitoring Mode. - In this moment the Oriented Ready 0rpm - Press "Menu" Start-up routine is initiated (right "soft key"). and the "Config" status is indicated at the top left part 13:48 Menu of the keypad (HMI).
  • Page 155 Vector Control Seq. Action/Result Display Indication Seq. Action/Result Display Indication - If necessary, change - If necessary, change the content of P0296 the content of P0402 according to the used line according to the rated Config 0rpm voltage. Therefore press motor speed.
  • Page 156 Vector Control Seq. Action/Result Display Indication At this point, the keypad (HMI) presents the option to run the "Self-Tuning". Whenever possible the Self- Tuning must be carried out. Config 0rpm - Thus, press "Select" to Motor Ventilation P0406: Self-Vent. access P0408 and then Run Self-Tuning P0408: No to select the...
  • Page 157: Functions Common To All The Control Modes

    Functions Common to All the Control Modes 12 FUNCTIONS COMMON TO ALL THE CONTROL MODES This section describes the functions that are common to all the CFW-11 inverter control modes (V/f, VVW, Sensorless, and Encoder). 12.1 RAMPS [20] The inverter RAMPS functions allow the motor to accelerate and decelerate in a faster or a slower manner.
  • Page 158 Functions Common to All the Control Modes open DIx - Run/Stop Time ramp DIx open Time P0102 P0103 P0100 P0101 Motor Speed Time Figure 12.1 - Second ramp actuation In this example, the commutation to the 2nd ramp (P0102 or P0103) is done by means of one of the digital inputs from DI1 to DI8, provided that it had been programmed for 2nd ramp function (refer to the Item 13.1.3 Digital Inputs [40] on page...
  • Page 159: Speed References [21]

    Functions Common to All the Control Modes P0105 – 1st/2nd Ramp Selection Adjustable 0 = 1 Ramp Factory Range: 1 = 2 Ramp Setting: 2 = DIx 3 = Serial/USB 4 = Anybus-CC 5 = CANopen/DeviceNet/Profibus DP 6 = SoftPLC 7 = PLC11 Properties: Access groups...
  • Page 160 Functions Common to All the Control Modes P0121 – Keypad Reference Adjustable 0 to 18000 rpm Factory 90 rpm Range: Setting: Properties: Access groups 01 PARAMETER GROUPS via HMI: 21 Speed References Description: When the HMI keys are active (P0221 or P0222 = 0), this parameter sets the value of the motor speed reference.
  • Page 161: Speed Limits [22]

    This parameter sets the highest speed allowed for the motor to operate, and must be adjusted as a percentage of the maximum speed limit (P0134). When the actual speed exceeds the value of P0134 + P0132 longer than 20 ms, the CFW-11 will disable the PWM pulses and indicate the fault (F150).
  • Page 162 Functions Common to All the Control Modes P0133 – Minimum Speed Reference Limit Adjustable 0 to 18000 rpm Factory 90 rpm Range: Setting: (75 rpm) P0134 – Maximum Speed Reference Limit Adjustable 0 to 18000 rpm Factory 1800 rpm Range: Setting: (1500 rpm) Properties:...
  • Page 163: Multispeed [36]

    Functions Common to All the Control Modes 12.4 MULTISPEED [36] The MULTISPEED function is used when one wishes to have up to 8 predefined fixed speeds, which are commanded through the digital inputs (DI4, DI5 and DI6). P0124 – Multispeed Reference 1 Adjustable 0 to 18000 rpm Factory...
  • Page 164 Functions Common to All the Control Modes Description: The Multispeed brings as advantages the stability of the predefined fixed references, and the immunity against electric noises (isolated digital inputs DIx). In order to activate the Multispeed function one must configure the parameter P0221 = 8 and/or P0222 = 8 (Reference Selection).
  • Page 165: Electronic Potentiometer [37]

    24 V at the digital inputs, whereas the decrease is done with the application of 0 V. In order to reset the reference, 24 V must be applied at the "INCREASE" input and 0 V at the "DECREASE" input, simultaneously while the CFW-11 inverter is disabled. Increase Digital Inputs...
  • Page 166: Zero Speed Logic [35]

    Functions Common to All the Control Modes 12.6 ZERO SPEED LOGIC [35] This function allows the configuration of a speed in which the inverter will enter a stop condition (disable itself). It is recommended to use this function when the commands Run/Stop, Direction of Rotation, LOC/REM and JOG are generated by the keyboard (HMI) or by the digital inputs (DIx).
  • Page 167: Flying Start/Ride-Through [44]

    Functions Common to All the Control Modes When the PID regulator is active (P0203 = 1) and in Automatic mode, for the inverter to leave the disable condition, besides the condition programmed in P0218, it is also necessary that the PID error (the difference between the Setpoint and the process variable) be higher than the value programmed in P0535.
  • Page 168: V/F Flying Start And Vvw

    Functions Common to All the Control Modes 12.7.1 V/f Flying Start and VVW In the V/f and VVW mode, the inverter imposes a fixed frequency at the start, defined by the speed reference, and applies a voltage ramp defined at the parameter P0331. The Flying Start function will be activated after the time adjusted in P0332 elapses (to allow the motor demagnetization), every time a "Run"...
  • Page 169 Functions Common to All the Control Modes P0327 – F.S. Current Ramp I/f Adjustable 0.000 to 1.000 s Factory 0.070 s Range: Setting: Description: It defines the time for the I/f current to change from 0 to (0.9 x P0401) at the beginning of the frequency scan (f), in order to minimize the generation of transients in the motor.
  • Page 170 Functions Common to All the Control Modes General Enable (with Run/Stop = on) or Run/Stop (with General Enable = on) H. Geral (c/ G/P=ON) ou G/P( c/ HG=ON) +24 V 24 v tempo time Vetorial Vector P134 P0134 P001 P0001 P329xP412 P0329xP0412 tempo...
  • Page 171: P0202 = 4

    Functions Common to All the Control Modes 12.7.2.2 P0202 = 4 During the time period when the motor is being magnetized, the identification of the motor speed occurs. Once the magnetization is finished, the motor will be operated starting from that speed until reaching the speed reference indicated in P0001.
  • Page 172: Vector Ride-Through

    Functions Common to All the Control Modes P0331 – Voltage Ramp Adjustable 0.2 to 60.0 s Factory 2.0 s Range: Setting: Properties: V/f and VVW Access groups 01 PARAMETER GROUPS via HMI: 44 FlyStart/RideThru Description: This parameter sets the necessary time for the output voltage to reach the rated voltage value. It is used by the Flying Start function as well as by the Ride-Through function (both in V/f and VVW mode), together with the parameter P0332.
  • Page 173 Functions Common to All the Control Modes Back" (t4) level, defined at the parameter P0323. The motor will reaccelerate, following the adjusted ramp, from the actual speed value to the value defined by the speed reference (P0001) (refer to the Figure 12.8 on page 12-17).
  • Page 174 Functions Common to All the Control Modes P0321 – DC Link Power Loss Adjustable 178 to 282 V Factory 252 V (P0296 = 0) 308 to 616 V 436 V (P0296 = 1) Range: Setting: 308 to 616 V 459 V (P0296 = 2) 308 to 616 V 505 V (P0296 = 3) 308 to 616 V...
  • Page 175: Dc Braking [47]

    Functions Common to All the Control Modes P0326 – Ride-Through Integral Gain Adjustable 0.000 to 9.999 Factory 0.128 Range: Setting: Properties: Vector Access groups 01 PARAMETER GROUPS via HMI: 44 FlyStart/RideThru Description: These parameters configure the vector mode Ride-Through PI controller, which is responsible for keeping the DC link voltage at the level set in P0322.
  • Page 176 Functions Common to All the Control Modes P0299 - DC-Braking Start Time Adjustable 0.0 to 15.0 s Factory 0.0 s Range: Setting: Properties: V/f, VVW and Sless Access groups 01 PARAMETER GROUPS via HMI: 47 DC Braking Description: This parameter sets the DC braking time at starting. INJECTION OF DIRECT CURRENT AT STARTING Motor Speed...
  • Page 177 Functions Common to All the Control Modes (a) V/f scalar Motor Speed P0300 P0301 Time DEAD TIME +24 V DIx – Run/Stop Open (b) VVW and Sensorless Vector DC Current Injection Motor Speed P0300 P0301 Time +24 V DIx – Run/Stop Open Figure 12.11 - (a) and (b) - DC braking operation at the ramp disabling (via ramp disable) Figure 12.12 on page 12-21...
  • Page 178 Functions Common to All the Control Modes During the braking process, if the inverter is enabled, the braking is interrupted and the inverter will operate normally again. ATTENTION! The DC Braking may continue active after the motor has already stopped. Be careful with the motor thermal sizing for short period cyclic braking.
  • Page 179: Skip Speed [48]

    Functions Common to All the Control Modes Description: This parameter adjusts the current level (DC braking torque) applied to the motor during the braking. The programmed current level is a percentage of the inverter rated current. This parameter works only in the Sensorless Vector control mode. 12.9 SKIP SPEED [48] The parameters of this group prevent the motor from operating permanently at speed values where, for instance, the mechanic system enters in resonance (causing exaggerated vibration or noise).
  • Page 180: Search Of Zero Of The Encoder

    Functions Common to All the Control Modes Description: This actuation of these parameters occurs as presented in the Figure 12.13 on page 12-24 next. The passage through the avoided speed range (2 x P0306) takes place by means of the acceleration/deceleration ramps.
  • Page 181 Functions Common to All the Control Modes P0192 – Status Encoder Zero Search Adjustable 0 = Off Factory Range: 1 = Finished Setting: Properties: RO V/f, VVW and Vector Access groups 00 ALL PARAMETERS via HMI: Description: On the inverter initialization, this parameter starts on zero. When the value is changed to 1 (Concluded), it indicates that the zero search function was executed, and this function returns to the state of Inactive, although P0191 continues equal to one (Active).
  • Page 182 Functions Common to All the Control Modes 12-26...
  • Page 183: Digital And Analog Inputs And Outputs

    Digital and Analog Inputs and Outputs 13 DIGITAL AND ANALOG INPUTS AND OUTPUTS This section presents the parameters for the configuration of the CFW-11 inputs and outputs, as well as the parameters for the command of the inverter in the Local or Remote Situations.
  • Page 184 Digital and Analog Inputs and Outputs P0230 – Analog Input Dead Zone Adjustable 0 = Off Factory Range: 1 = On Setting: Properties: Access groups 07 I/O CONFIGURATION 01 PARAMETER GROUPS via HMI: 38 Analog Inputs 38 Analog Inputs Description: This parameter acts only for the analog inputs (AIx) programmed as speed reference, and it defines if the Dead Zone at those inputs is On (1) or Off (0).
  • Page 185 Digital and Analog Inputs and Outputs P0231 – AI1 Signal Function P0236 – AI2 Signal Function P0241 – AI3 Signal Function Adjustable 0 = Speed Reference Factory 1 = N* Without Ramp Range: Setting: 2 = Maximum Torque Current 3 = Process Variable 4 = PTC 5 = Not Used 6 = Not Used...
  • Page 186 Digital and Analog Inputs and Outputs In order that the expressions which determine the total current and the maximum torque developed by the motor (Section 11.5 TORQUE CONTROL on page 11-7 Item 11.8.6 Torque Current Limitation [95] on page 11-28) remain valid, replace P0169, P0170 by P0018 to P0021.
  • Page 187 Digital and Analog Inputs and Outputs P0235 – AI1 Filter P0240 – AI2 Filter P0245 – AI3 Filter P0250 – AI4 Filter Adjustable 0.00 to 16.00 s Factory 0.00 s Range: Setting: Properties: Access groups 07 I/O CONFIGURATION 01 PARAMETER GROUPS via HMI: 38 Analog Inputs 38 Analog Inputs...
  • Page 188 Digital and Analog Inputs and Outputs The AIx’ internal value is the result of the following equation: Alx' = Alx + OFFSET x 10 V x Gain For instance: AIx=5 V, OFFSET=-70 % and Gain=1.000: Alx' = 5 + (-70) x 10 V x1 = –2 V AIx’=-2 V means that the motor will rotate in the reverse direction with a reference in module equal to 2 V, provided that the AIx function is "Speed Reference".
  • Page 189: Analog Outputs [39]

    Inverse reference is obtained with the options 2 and 3, i.e., maximum speed is obtained with minimum reference. 13.1.2 Analog Outputs [39] In the CFW-11 standard configuration are available 2 analog outputs (AO1 and AO2), and 2 more (AO3 and AO4) can be added with the IOA-01 accessory. The parameters related to those outputs are described next.
  • Page 190 Digital and Analog Inputs and Outputs P0251 – AO1 Function P0254 – AO2 Function Adjustable 0 = Speed Reference Factory P0251 = 2 1 = Total Reference Range: Setting: P0254 = 5 2 = Real Speed 3 = Torque Current Reference 4 = Torque Current 5 = Output Current 6 = Process Variable...
  • Page 191 Encoder Speed P0696 Value P0697 Value P0698 Value P0699 Value PLC11 Id* Current Exclusive WEG Use 24 to 71 24 to 71 * Factory Setting P0252 – AO1 Gain P0255 – AO2 Gain P0258 – AO3 Gain P0261 – AO4 Gain Adjustable 0.000 to 9.999...
  • Page 192 Digital and Analog Inputs and Outputs Function AO1 - P0251 AO2 - P0254 AO3 - P0257 AO4 - P0260 Speed Reference Total Reference Real Speed Torque Current Reference Torque Current Output Current Value Process Variable (PID) AO1 - P0014 AO2 - P0015 Active Current AO3 - P0016 AO4 - P0017...
  • Page 193 Digital and Analog Inputs and Outputs Table 13.4 - Full scale SCALE OF THE ANALOG OUTPUT INDICATIONS Variable Full Scale (*) Speed Reference Total Reference P0134 Real Speed Encoder Speed Torque Current Reference Torque Current 2.0 x I nomHD Torque Current > 0 Motor Torque 2.0 x I Output Current...
  • Page 194: Digital Inputs [40]

    -10 V to +10 V . 13.1.3 Digital Inputs [40] The CFW-11 has 6 digital inputs in the standard version, and 2 more can be added with the IOA-01 and IOB-01 accessories. The parameters that configure those inputs are presented next.
  • Page 195 Digital and Analog Inputs and Outputs The indication is done by means of the numbers 1 and 0, representing respectively the "Active" and "Inactive" states of the inputs. The state of each input is considered as one digit in the sequence where DI1 represents the least significant digit. Example: In case the sequence 10100010 is presented on the keypad (HMI), it will correspond to the following status of the DIs: Table 13.8 - Digital inputs status...
  • Page 196 Digital and Analog Inputs and Outputs Table 13.9 - Digital input functions P0263 P0264 P0265 P0266 P0267 P0268 P0269 P0270 Functions (DI1) (DI2) (DI3) (DI4) (DI5) (DI6) (DI7) (DI8) Not used 0, 13 and 23 0, 13 and 23 0*, 13 and 23 0* and 23 0 and 23 0 and 23 0*, 13 and 23 0*, 13 and 23...
  • Page 197 Digital and Analog Inputs and Outputs When Torque is selected, the speed regulator parameters P0161 and P0162 become inactive (*). Thus, the Total Reference becomes the input of the Torque Current Regulator. Refer to the Figure 11.1 on page 11-2 Figure 11.2 on page 11-4.
  • Page 198 Chapter 20 PID REGULATOR [46] on page 20-1, for more details. PLC use: When this option is selected it will not take any action for the CFW-11. It can be used as a remote input for the PLC11 board or for communication networks.
  • Page 199 Fast Stop, Forward Run or Reverse Run must be in the ON Stop, Forward Run or Reverse Run must be in the ON state, state, so that the CFW-11 operates as described above. so that the CFW-11 operates as described above.
  • Page 200 Digital and Analog Inputs and Outputs (h) JOG JOG Speed (P0122) Motor speed Acceleration ramp Deceleration ramp Time 24 V Run/Stop Open Time 24 V DIx - JOG Open Time 24 V General enable Open Time (i) JOG + and JOG - JOG+ (P0122), JOG- (P0123) Speed Motor speed Time...
  • Page 201 Digital and Analog Inputs and Outputs (k) 3-WIRE START / STOP 24 V DIx - Start Open Time 24 V DIx - Stop Open Time Motor speed Time (l) FWD Run / REV Run 24 V DIx - Forward Open Time 24 V DIx - Reverse...
  • Page 202: Digital Outputs / Relays [41]

    13.1.4 Digital Outputs / Relays [41] The CFW-11 has 3 relay digital outputs as standard on its control board, and 2 more digital outputs of the open collector type that can be added with the accessories IOA-01 or IOB-01. The next parameters configure the functions related to those outputs.
  • Page 203 Digital and Analog Inputs and Outputs Table 13.11 - Digital output functions P0275 P0276 P0277 P0278 P0279 Functions (DO1) (DO2) (DO3) (DO4) (DO5) 0, 29, 37, 38, 39, 0, 29, 37, 38, 39, Not Used 0 and 29 40, 41 and 42 40, 41 and 42 N* >...
  • Page 204 - P0695 Value: it means that the state of the digital output will be controlled by P0695, which is written via the network. Refer to the CFW-11 Serial communication manual for more details on this parameter. - Forward: it means that when the motor is rotating in the forward direction the DOx = saturated transistor and/or relay with the coil energized, and when the motor is rotating in the reverse direction, the DOx = open transistor and/or relay with the coil not energized.
  • Page 205 Digital and Analog Inputs and Outputs N = P0002 (Motor Speed). N* = P0001 (Speed Reference). Nx = P0288 (Nx Speed) – It is a reference point of the speed selected by the user. Ny = P0289 (Ny Speed) – It is a reference point of the speed selected by the user. Ix = P0290 (Ix Current) –...
  • Page 206 Digital and Analog Inputs and Outputs (e) N = 0 (Zero) Speed (f) Is > Ix Speed P0291 Ix (P0290) Time Relay/ Relay/ Transistor OFF Transistor (g) Is < Ix (h) Torque > Tx Motor Torque (P0009) Ix (P0290) Tx (P0293) Time Time Relay/...
  • Page 207 Digital and Analog Inputs and Outputs (m) Process Variable < PVy (l) Process Variable > PVx VPx (P0533) Time VPy (P0534) Time Process Process Variable Variable Relay/ Relay/ Transistor Transistor (n) Pre-Charge Ok (o) Time enabled > Hx 6553 h DC Link Hx (P0294) Pre-charge...
  • Page 208 Digital and Analog Inputs and Outputs P0281 – Fx Frequency Adjustable 0.0 to 300.0 Hz Factory 4.0 Hz Range: Setting: Properties: Access groups 07 I/O CONFIGURATION 01 PARAMETER GROUPS via HMI: 41 Digital Outputs 41 Digital Outputs Description: It is used in the digital output and relay functions: F>Fx and F>Fx P0282 –...
  • Page 209 Digital and Analog Inputs and Outputs P0287 – Hysteresis for Nx and Ny Adjustable 0 to 900 rpm Factory 18 rpm Range: Setting: (15 rpm) Properties: Access groups 07 I/O CONFIGURATION 01 PARAMETER GROUPS via HMI: 41 Digital Outputs 41 Digital Outputs Description: It is used in the N >...
  • Page 210 Digital and Analog Inputs and Outputs Description: It specifies the value in rpm, ± 1 % of the motor rated speed (hysteresis), below which the actual speed will be considered null for the Zero Speed Disable function. This parameter is also used by the functions of the digital and relay outputs, and by the PID regulator. The hysteresis is ±...
  • Page 211: Local And Remote Command

    Digital and Analog Inputs and Outputs 13.2 LOCAL AND REMOTE COMMAND In those parameter groups one can configure the origin of the main inverter commands when in the LOCAL or in the REMOTE situation, as the Speed Reference, Speed Direction, Run/Stop and JOG. P0220 –...
  • Page 212 Digital and Analog Inputs and Outputs Description: They define the origin of the Speed Reference in the LOCAL situation and in the REMOTE situation. Some notes about the options for those parameters: The AIx’ designation refers to the analog signal obtained after the addition of the AIx input to the offset and its multiplication by the applied gain (refer to the Item 13.1.1 Analog Inputs [38] on page 13-1).
  • Page 213 Digital and Analog Inputs and Outputs P0224 – Run/Stop Selection – LOCAL Situation P0227 – Run/Stop Selection - REMOTE Situation Adjustable Factory P0224 = 0 0 = Keys Range: Setting: P0227 = 1 1 = DIx 2 = Serial/USB 3 = Anybus-CC 4 = CANopen/DeviceNet/Profibus DP 5 = SoftPLC 6 = PLC11...
  • Page 214 Digital and Analog Inputs and Outputs Description: It defines the motor stop mode when the inverter receives the "Stop" command. The Table 13.12 on page 13-32 describes the options of this parameter. Table 13.12 - Stop mode selection P0229 Description 0 = Ramp to Stop The inverter will apply the ramp programmed in P0101 and/or P0103 1 = Coast to Stop...
  • Page 215 Digital and Analog Inputs and Outputs (*) Valid only for P0202 = 3 and 4. Figure 13.8 - Speed Reference block diagram 13-33...
  • Page 216: 3-Wire Command [33]

    Once the FWD Run input has been released (0 V) and +24 V has been applied at the input programmed for REV Run (DIx = 5), the CFW-11 will activate the motor in the reverse direction until it reaches the speed reference.
  • Page 217: Dynamic Braking

    This function is not available in inverters with frames F, G and H. The Dynamic Braking function can only be used if a braking resistor has been connected to the CFW-11, and if the parameters related to it have been adjusted properly.
  • Page 218 Dynamic Braking The next table presents the overvoltage trip level. Table 14.1 - Overvoltage (F022) trip levels Inverter V P0296 F022 220/230 V > 400 V 380 V 400/415 V > 800 V 440/460 V 480 V 500/525 V 550/575 V >...
  • Page 219 Dynamic Braking P0155 – Dynamic Braking Resistor Power Adjustable 0.02 to 650.00 kW Factory 2.60 kW Range: Setting: Properties: Access groups 01 PARAMETER GROUPS via HMI: 28 Dynamic Braking Description: This parameter adjusts the trip level of the braking resistor overload protection. It must be set according to the used braking resistor rated power (in kW).
  • Page 220 Dynamic Braking 14-4...
  • Page 221: Faults And Alarms

    The alarm works as a warning to the user that critical operation conditions are occurring and a fault may occur if the situation does not change. Refer to the CFW-11 user's manual chapter 6 - Troubleshooting and Maintenance and the section Quick Parameter Reference, Faults and Alarms of this manual to obtain more information regarding the Faults and Alarms.
  • Page 222: Motor Overtemperature Protection

    Faults and Alarms NOTE! In order to assure the conformity of the CFW-11 motor overload protection with the UL508C standard, observe the following: The "TRIP" current is equal to 1.25 times the motor nominal current (P0401) adjust in the "Oriented Start-up" menu.
  • Page 223 Faults and Alarms (a) AO1, AI1 XC1: Program P0231 = 4. Set S1.4 = OFF (0 to 10 V). Program P0251 = 13. Set S1.1 = OFF (4 to 20 mA, 0 to 20 mA). CC11 (b) AO2, AI2 Program P0236 = 4. Set S1.3 = OFF (0 to ±...
  • Page 224: Protections [45]

    Faults and Alarms 15.3 PROTECTIONS [45] The parameters related to motor and inverter protections are found in this group. P0030 – U Arm IGBT Temperature P0031 – V Arm IGBT Temperature P0032 – W Arm IGBT Temperature P0033 – Rectifier Temperature P0034 –...
  • Page 225 (Motor Ventilation Type) or P0298 (Inverter Application) are set during the "Oriented Start-up" routine (refer to this parameter description in the section 11.7 – Motor Data of CFW-11 Programming Manual V3.1X). The overload current is given as a function of the speed being applied to the motor, according to the overload curve.
  • Page 226 Faults and Alarms P0159 – Motor Thermal Class Adjustable 0 = Class 5 Factory Range: 1 = Class 10 Setting: 2 = Class 15 3 = Class 20 4 = Class 25 5 = Class 30 6 = Class 35 7 = Class 40 8 = Class 45 Properties:...
  • Page 227 Faults and Alarms Example: For a motor with the following characteristics, = 10.8 A = 4 s (hot motor blocked rotor time) = 7.8 ⇒ I = 7.8 x 10.8 A= 84.2 A SF = 1.15 one gets, 84.2 Overload Current = x 100 = 678 % x SF 10.8 x 1.15...
  • Page 228 Faults and Alarms Overload Time 100000 10000 1000 Class 45 Class 40 Class 35 Class 30 Class 25 Class 20 Class 15 Class 10 Class 5 Current x In for F.S. = 1.00 Current x In for F.S. = 1.15 (b) - Hot motor overload curves for loads of the HD and ND types Figure 15.3 - (a) and (b) - Cold and hot motor overload curves for loads of the HD and ND types For the previous example, by plotting the 678 % value (x axis) of the Overload Current with the 4 seconds (y axis) of the Overload...
  • Page 229 Faults and Alarms NOTE! The faults F051, F078, F156, F301, F304, F307, F310, F313, F316, F319, F322, F325, F328, F331, F334, F337, F340 and F343 allow a conditional Reset, i.e., the Reset will only occur if the temperature gets back to the normal operation range. If after Auto-Reset, the same fault is repeated three times consecutively, the Auto-Reset function will be disabled.
  • Page 230 P0349 and the inverter continues operating The trip level of the overload protection is calculated internally by the CFW-11, taking into account the motor current, its thermal class and its service factor. Refer to the parameter P0159 in this section.
  • Page 231 Faults and Alarms P0350 – Inverter Overload Protection (IGBTs) Adjustable 0 = Fault is active, with switching frequency reduction Factory Range: 1 = Fault and alarm are active, with switching frequency reduction Setting: 2 = Fault is active, without switching frequency reduction 3 = Fault and alarm are active, without switching frequency reduction Properties: Access groups...
  • Page 232 Faults and Alarms Description: This parameter is useful when the motor is equipped with PTC type temperature sensors, allowing the configuration of the protection level for the motor overtemperature function. The details on the actuation of the available options are in the Table 15.4 on page 15-12.
  • Page 233 Faults and Alarms Description: The CFW-11 is equipped with two fans: an internal fan and a heatsink fan, and the activation of both will be controlled via software by means of the inverter programming. The options available for the setting of this parameter are the following: Table 15.5 - Options of the parameter P0352...
  • Page 234 Faults and Alarms Description: The overtemperature protection is carried out by means of the measurement of the temperature with the IGBTs and power board internal air NTCs, being able to generate alarms and faults. In order to configure the desired protection, set P0353 according to the table below. Table 15.6 - Options of the parameter P0353 P0353 Action...
  • Page 235 Faults and Alarms Description: This parameter allows disabling the actuation of F185 fault – Fault in the preload contactor. If P0355 = 0, the Fault in the preload contactor will remain deactivated. F185 fault will not be generated. When the inverter is a frame size E with DC power supply it’s necessary to adjust P0355 = 0. P0356 –...
  • Page 236 Faults and Alarms P0358 – Encoder Fault Configuration Adjustable 0 = Off Factory Range: 1 = F067 ON Setting: 2 = F065, F066 active 3 = All active Properties: CFG and Encoder Access groups 01 PARAMETER GROUPS via HMI: 45 Protections Description: This parameter allows disabling the fault detection by software: a) F067 –...
  • Page 237 Faults and Alarms P0360 – Temperature Imbalance Configuration Adjustable 0 = Fault/Alarm Factory Range: 1 = Fault Setting: Properties: FRAME H and CFG Access groups 01 PARAMETER GROUPS via HMI: 45 Protections Description: This parameter allows choosing whether showing or not the alarm of temperature imbalance of the power modules. If defined as 1, only fault F062 will occur.
  • Page 238 Faults and Alarms P0810 – Temperature V-B4/IGBT V4 P0811 – Temperature W-B4/IGBT W4 P0812 – Temperature U-B5/IGBT U5 P0813 – Temperature V-B5/IGBT V5 P0814 – Temperature W-B5/IGBT W5 Adjustable -20.0 °C to 150.0 °C Factory Range: Setting: Properties: Access groups 01 PARAMETER GROUPS 09 READ ONLY PARAMETERS via HMI:...
  • Page 239: Motor Overtemperature Protection Using The Ioe-01, Ioe-02 Or

    Faults and Alarms P0834 - DIM1 and DIM2 Status Adjustable Bit 0 = DIM1 Factory Range: Bit 1 = DIM2 Setting: Properties: CFW-11M and RO Access groups 01 PARAMETER GROUPS 09 READ ONLY PARAMETERS via HMI: 40 Digital Inputs Description: Through this parameter it is possible to visualize the status of the 2 digital inputs of the Modular Drive interface board.
  • Page 240: Ptc Type Temperature Sensor

    Faults and Alarms Description: These parameters allow selecting the type of desired action, temperature fault, temperature alarm or broken cable alarm. The rupture of the cable that connects the sensor to the IOE-0x module may cause any of those actions, depending on the selected option.
  • Page 241: Pt100 Or Kty84 Temperature Sensor Type

    Faults and Alarms 15.4.2 PT100 or KTY84 Temperature Sensor Type The parameters described in this section will be shown on the HMI when the IOE-02 or IOE 03 optional module is connected into the slot 1 (XC41 connector). Refer to the Figure 3.1 on page 3-2.
  • Page 242 Faults and Alarms Description: This parameter indicates, in Celsius degrees, the highest temperature among the PT100 or KTY84 used sensors. NOTE! If any of the temperature fault/alarm configuration parameters, P0374, P0377, P0380, P0383 and/or P0386, is programmed with the "Inactive" option, the respective read-only parameter, P0388, P0389, P0390, P0391 and/or P0392, indicates 0 (zero), not showing the actual sensor temperature.
  • Page 243: Read Only Parameters [09]

    Read Only Parameters [09] 16 READ ONLY PARAMETERS [09] In order to facilitate the visualization of the main reading variables of the inverter, the group [09] - "Read Only Parameters" can be accessed directly. It is important to point out that all the parameters of that group can only be visualized on the keypad (HMI) display, and that they do not allow changes by the user.
  • Page 244 Read Only Parameters [09] P0003 – Motor Current Adjustable 0.0 to 4500.0 A Factory Range: Setting: Properties: Access groups 09 READ ONLY PARAMETERS via HMI: Description: It indicates the inverter output current in Amps (A), by means of 1.0 second filter. P0004 –...
  • Page 245 Read Only Parameters [09] Description: It indicates one of the 8 possible inverter states. The description of each state is presented in the next table. In order to facilitate the visualization, the inverter status is also showed on the top left corner of the keypad (HMI) (Figure 5.3 on page 5-10 –...
  • Page 246 Read Only Parameters [09] x 100 x Y P0009 = P0410 x P0178 2 0.5 1) P0202 ≠ 3: I = P0401 in V/f or VVW the adjusts are: P0178 = 100 % and P0190 = 0.95 x P0400 2) P0202 = 3: x P0178 2 0.5 = P0401...
  • Page 247 Read Only Parameters [09] P0011 – Cos Phi of the Output Adjustable 0.00 to 1.00 Factory Range: Setting: Properties: Access groups 09 READ ONLY PARAMETERS via HMI: Description: This parameter indicates the value of the cosine of the angle between the voltage and output current. The electric motor are inductive loads and, therefore, consumes reactive power.
  • Page 248 Read Only Parameters [09] P0030 – Temperature IGBTs U P0031 – Temperature IGBTs V P0032 – Temperature IGBTs W P0033 – Temperature of the Rectifier Adjustable -20.0 to 150.0°C Factory Range: Setting: Properties: Access groups 01 PARAMETER GROUPS via HMI: 45 Protections 09 Read only Description:...
  • Page 249 Read Only Parameters [09] P0036 – Heatsink Fan Speed Adjustable 0 to 15000 rpm Factory Range: Setting: Properties: Access groups 09 READ ONLY PARAMETERS via HMI: Description: It indicates the heatsink fan actual speed, in revolutions per minute (rpm). NOTE! This parameter has no function in mechanics of Modular Drive.
  • Page 250 Read Only Parameters [09] Description: This parameter shows the counting of the pulses of the encoder. The counting can be increased from 0 to 40000 (Hourly turn) or decreased from 40000 to 0 (rotate Counterclockwise). This parameter can be visualized in the analogical exits when P0257 = 49 or P0260 = 49.
  • Page 251 Read Only Parameters [09] P0044 – kWh Counter Adjustable 0 to 65535 kWh Factory Range: Setting: Properties: Access groups 09 READ ONLY PARAMETERS via HMI: Description: It indicates the energy consumed by the motor. It indicates up to 65535 kWh, and then it gets back to zero. By setting P0204 = 4, the value of the parameter P0044 is reset to zero.
  • Page 252: Fault History [08]

    NOTE! If the fault occurs simultaneously with the CFW-11 power up or reset, the parameters regarding this fault, as date, hour, motor speed, etc., may contain invalid information.
  • Page 253 Read Only Parameters [09] P0050 – Last Fault P0054 – Second Fault P0058 – Third Fault P0062 – Fourth Fault P0066 – Fifth Fault P0070 – Sixth Fault P0074 – Seventh Fault P0078 – Eighth Fault P0082 – Ninth Fault P0086 –...
  • Page 254 Read Only Parameters [09] P0083 – Ninth Fault Day/Month P0087 – Tenth Fault Day/Month Adjustable 00/00 to 31/12 Factory Range: Setting: Properties: Access groups 08 FAULT HISTORY via HMI: Description: They indicate the day and the month of the last to the tenth fault occurrence. P0052 –...
  • Page 255 Read Only Parameters [09] P0065 – Fourth Fault Time P0069 – Fifth Fault Time P0073 – Sixth Fault Time P0077 – Seventh Fault Time P0081 – Eighth Fault Time P0085 – Ninth Fault Time P0089 – Tenth Fault Time Adjustable 00:00 to 23:59 Factory Range:...
  • Page 256 Read Only Parameters [09] P0092 – Speed at the Moment of the Last Fault Adjustable 0 to 18000 rpm Factory Range: Setting: Properties: Access groups 08 FAULT HISTORY via HMI: Description: It is the record of the motor speed at the moment of the last fault occurrence. P0093 –...
  • Page 257 Read Only Parameters [09] P0096 – DIx Status at the Moment of the Last Fault Adjustable Bit 0 = DI1 Factory Bit 1 = DI2 Range: Setting: Bit 2 = DI3 Bit 3 = DI4 Bit 4 = DI5 Bit 5 = DI6 Bit 6 = DI7 Bit 7 = DI8 Properties:...
  • Page 258 Read Only Parameters [09] P0800 – Temperature U-B1/IGBT U1 P0801 – Temperature V-B1/IGBT V1 P0802 – Temperature W-B1/IGBT W1 P0803 – Temperature U-B2/IGBT U2 P0804 – Temperature V-B2/IGBT V2 P0805 – Temperature W-B2/IGBT W2 P0806 – Temperature U -B3/IGBT U3 P0807 –...
  • Page 259 Read Only Parameters [09] P0817 – Current W-B1/IGBT W1 P0818 – Current U-B2/IGBT U2 P0819 – Current V-B2/IGBT V2 P0820 – Current W-B2/IGBT W2 P0821 – Current U-B3/IGBT U3 P0822 – Current V-B3/IGBT V3 P0823 – Current W-B3/IGBT W3 P0824 – Current U-B4/IGBT U4 P0825 –...
  • Page 260 Read Only Parameters [09] Description: This reading parameter indicates the current (A) of the IGBTs of each phase. In a modular drive, this information is shown for each Book, and for frame H it is shown for each IGBT module. P0834 –...
  • Page 261: Communication [49]

    For the exchange of information through communication networks, the CFW-11 has several standardized communication protocols, like MODBUS, CANopen, DeviceNet, and Ethernet/IP . For more details regarding the inverter configuration for operating with those protocols, refer to the CFW-11 communication manuals. The parameters regarding the communication are explained next.
  • Page 262: Anybus-Cc Interface

    P0722 – CANopen Node Status Those are parameters for the configuration and operation of the CAN interface. For a detailed description, refer to the CANopen communication manual or to the DeviceNet communication manual, available in www.weg.net. 17.3 ANYBUS-CC INTERFACE P0686 – Anybus-CC Control Word P0687 –...
  • Page 263: Profibus Dp Interface

    P0739 – Anybus Writing Word #8 Those are parameters for the configuration and operation of the Anybus-CC interface. For a detailed description, refer to the Anybus-CC communication manual, available in www.weg.net. 17.4 PROFIBUS DP INTERFACE P0740 - Profibus Comm. Status P0741 –...
  • Page 264: Communication States And Commands

    P0699 – Analog Outputs Value 4 P0799 – I/O Update Delay Those parameters are used for monitoring and controlling the CFW-11 inverter by means of communication interfaces. For a detailed description, refer to the communication manual of the used interface. These manuals are available in www.weg.net.
  • Page 265: Softplc [50]

    The SoftPLC function allows the frequency inverter to assume PLC (Programmable Logical Controller) functions. For more details regarding the programming of those functions in the CFW-11, refer to the CFW-11 SoftPLC manual. The parameters related to the SoftPLC are described next.
  • Page 266: Digital Outputs [41]

    SoftPLC [50] Description: By means of this parameter, it is possible to visualize the status of the 8 digital inputs (DI9 to DI16) of the IOC-01, IOC-02 or IOC-03 module. The indication is done by means of the numbers 1 and 0, representing respectively the "Active" and "Inactive" states of the inputs.
  • Page 267: Trace Function [52]

    19.1 TRACE FUNCTION The trace function is used to record variables of interest from the CFW-11 (as current, voltage, speed) when a particular event occurs in the system (e.g.: alarm/fault, high current, etc.). This system event, for starting the data recording process, is called "trigger".
  • Page 268 Trace Function [52] Description: It defines the value for comparison with the variable selected in P0550. The full range of the variables selectable as trigger is presented in the next table. Table 19.1 - Full scale of the variables selectable as trigger Variable Full Scale Speed Reference...
  • Page 269 Trace Function [52] - If P0552≠6 and any DI is configured for "Trace Function", the trigger will never occur as a result of the DI activation. - These three programming options do not prevent the inverter from being enabled. P0553 – Trace Sampling Period Adjustable 1 to 65535 Factory Range: Setting: Properties: Access groups 01 PARAMETER GROUPS via HMI: 52 Trace Function Description: It defines the sampling period (time between two sampling points) as a 200 µs multiple.
  • Page 270 Trace Function [52] P0560 – Trace Available Memory Adjustable 0 to 100 % Factory Range: Setting: Properties: Access groups 01 PARAMETER GROUPS via HMI: 52 Trace Function Description: It shows the amount of memory available for storing Trace Function points. The range from 0 to 100 % indicates that from 0 to 15 KB are available for the Trace Function.
  • Page 271 Trace Function [52] Description: They select the signals that will be recorded at the channels 1 to 4 of the Trace Function. The options are the same that are available at P0550. By selecting the "Not Selected" option, the total memory available for the Trace function is distributed between the active channels.
  • Page 272 Trace Function [52] Description: P0572 to P0575 record the date and hour of the trigger occurrence. These parameters and the points acquired by the Trace Function are not saved when the inverter is powered off. There are two possibilities for P0572 to P0575 being null: - No acquisition was performed after the inverter power on, or.
  • Page 273: Pid Regulator [46]

    20 PID REGULATOR [46] 20.1 DESCRIPTION AND DEFINITIONS The CFW-11 has the special function PID REGULATOR, which can be used to control a closed loop process. This function places a proportional, integral and derivative regulator, superposed to the normal CFW-11 speed control.
  • Page 274 PID Regulator [46] Figure 20.1 - PID Regulator function block diagram 20-2...
  • Page 275: Commissioning

    PID Regulator [46] 20.2 COMMISSIONING Before doing a detailed description of the parameters related to this function, a step by step guide for putting the PID into operation will be presented. NOTE! In order that the PID function works properly, it is fundamental to verify if the inverter is configured correctly to drive the motor at the desired speed.
  • Page 276 PID Regulator [46] (a) Direct Process Variable P0040 Direct PID (P0527 = 0) Set Point P0041 ed = P0041 - P0040 (%) P0535 (b) Reverse Process Variable Reverse PID (P0527 = 1) P0040 P0535 er = P0040 - P0041 (%) P0041 Set Point (c) Sleep Mode...
  • Page 277 PID Regulator [46] Example: - Full scale of the transducer (maximum output value) = 25 bar (FS = 25); - Operation range (range of interest) = 0 to 15 bar (OR = 15). Opting to maintain P0237 = 1.000 and P0239 = 0 (factory setting), which is the most common for most of the applications: - P0525 = 50 % (Keypad PID setpoint) will be equivalent to the used sensor full scale value, i.e., 0.5 x FS = 12.5 bar.
  • Page 278 PID Regulator [46] Example: Given a pressure transducer with a 4 to 20 mA output and a full scale of 25 bar (i.e., 4 mA = 0 bar and 20 mA = 25 bar) and P0237=2.000. If it is wished to control 10 bar, the following setpoint must be entered: x 2 x 100 % = 80 % Setpoint (%) = In case the setpoint is defined via analog input (AI1 for instance), P0231 must be configured = 0 (AI1 Signal Function:...
  • Page 279 PID Regulator [46] As a summary of this guide, a schematic of the connections of the CFW-11 for the PID regulator application, as well as the setting of the parameters used in this example, are presented next. 4-20 mA Pressure...
  • Page 280: Sleep Mode

    PID Regulator [46] 20.3 SLEEP MODE The sleep mode is a useful resource for saving energy when using the PID regulator. Refer to the Figure 20.2 on page 20-4. In many PID applications energy is wasted by keeping the motor turning at the minimum speed when, for instance, the pressure or the tank level keeps increasing.
  • Page 281: Connection Of A 2-Wire Transducer

    Transducer AI2- PE R S T U V W PE Figure 20.5 - Connection of a 2-wire transducer to the CFW-11 20.6 PARAMETERS The parameters related to the PID Regulator [46] are now described in a detail form. P0040 – PID Process Variable Adjustable 0.0 to 100.0 %...
  • Page 282 PID Regulator [46] P0203 – Special Function Selection Adjustable 0 = None Factory Range: 1 = PID Regulator Setting: Properties: Access groups 01 PARAMETER GROUPS via HMI: 46 Regulador PID Description: It enables the use of the PID Regulator special function, when set to 1. When P0203 is changed to 1, the following parameters are changed automatically: P0205 = 10 (Reading Parameter Selection 1).
  • Page 283 PID Regulator [46] Table 20.3 - Suggestions for PID regulator gain settings Gains Quantity Proportional Integral Differential P0520 P0521 P0522 Pneumatic system pressure 0.043 0.000 Pneumatic system flow 0.037 0.000 Hydraulic system pressure 0.043 0.000 Hydraulic system flow 0.037 0.000 Temperature 0.004 0.000...
  • Page 284 PID Regulator [46] Description: It selects the regulator feedback input (process variable). After choosing the feedback input, the function of the selected input must be programmed at P0231 (for AI1), P0236 (for AI2), P0241 (for AI3) or P0246 (for AI4). P0525 –...
  • Page 285 PID Regulator [46] P0528 – Process Variable Scale Factor Adjustable 1 to 9999 Factory 1000 Range: Setting: P0529 – Process Variable Decimal Point Adjustable 0 = wxyz Factory Range: 1 = wxy.z Setting: 2 = wx.yz 3 = w.xyz Properties: Access groups 01 PARAMETER GROUPS via HMI:...
  • Page 286 PID Regulator [46] P0530 – Process Variable Engineering Unit 1 P0531 – Process Variable Engineering Unit 2 P0532 – Process Variable Engineering Unit 3 Adjustable 32 to 127 Factory P0530 = 37 Range: Setting: P0531 = 32 P0532 = 32 Properties: Access groups 01 PARAMETER GROUPS...
  • Page 287 PID Regulator [46] P0535 – Wake Up Band Adjustable 0 to 100 % Factory Range: Setting: Properties: Access groups 01 PARAMETER GROUPS via HMI: 46 PID Regulator Description: The parameter P0535 works together with the parameter P0218 (Condition to Leave the Zero Speed Disable), giving the additional condition for leaving the Zero Speed Disable.
  • Page 288: Academic Pid

    PID Regulator [46] 20.7 ACADEMIC PID The controller implemented in the CFW-11 is of the academic type. The equations that characterize the Academic PID, which is the base of this function algorithm, are presented next. The transfer function in the Academic PID regulator frequency dominion is:...
  • Page 289: Pm Vector Control

    PMSM for industrial applications have sinusoidal CEMF and feeding current, so that the developed torque is smooth. The CFW-11 is prepared to drive Wmagnet line motors, which present a salient pole construction (interior magnets).
  • Page 290: Sensorless Pm - P0202 = 7

    PM Vector Control 21.2.1 Sensorless PM - P0202 = 7 The Sensorless PM control uses two rotor position estimation methods, the method for low speed injects a signal with a frequency of ±1 kHz, which causes an increase in the acoustic noise, and the method for higher speeds is based on the output voltages and currents.
  • Page 291: Pm With Encoder - P0202 = 6

    PM Vector Control 21.2.2 PM with Encoder - P0202 = 6 The PM with encoder control presents the advantages described for the Sensorless control, plus a speed control accuracy of 0.01 % (by using the 14-bit analog reference via IOA-01, or by digital references via HMI, Profibus DP , DeviceNet).
  • Page 292: Modified Functions

    Refer to the allowed current for switching frequencies different from the default, in the tables available in chapter 8 - Technical Specifications, of the CFW-11 user's manual. The inverter switching frequency can be adjusted according to the needs of the application.
  • Page 293: Motor Data [43] And Self-Tuning [05] And [94]

    PM Vector Control Torque control range: 10 % to 180 %. Accuracy: ± 5 % of the rated torque. When the speed regulator is positively or negatively saturated, then P0169 and P0170 limit the torque current, respectively. The torque, in percentage, at the motor shaft (showed at P0009) is given by: Iq* x P0401 motor Where Iq* (in Volts) is the value read at the analog outputs AO1...
  • Page 294 PM Vector Control P0401 – Motor Rated Current P0402 – Motor Rated Speed Adjustable 0 to 18000 rpm Factory 1750 rpm Range: Setting: (1458 rpm) Properties: Access groups 01 PARAMETER GROUPS via HMI: 43 Motor Data Description: Adjust it according to the used motor nameplate data. For PM motor control the adjustable range goes from 0 to 18000 rpm.
  • Page 295 PM Vector Control Description: Value obtained from the motor data sheet. If this information is not available, use the factory setting. P0430 – PM Type Adjustable 0 = Factory Setting Factory Range: 1 = Cooling Tower Setting: Properties: CFG and PM Access groups 01 PARAMETER GROUPS via HMI:...
  • Page 296 PM Vector Control P0442 – Inductance Lq - CT P0443 – Inductance Lq - CT Adjustable 0.0 to 400.0 mH Factory 0.0 mH Range: Setting: Properties: CFG and PM Access groups 01 PARAMETER GROUPS via HMI: 43 Motor Data Description: Adjust them according to the motor nameplate data.
  • Page 297: Pm Vector Control [29]

    P0007. 21.7 PM VECTOR CONTROL [29] 21.7.1 Speed Regulator [90] The parameters related to the CFW-11 speed regulator are presented in this group. P0160 – Speed Regulator Configuration P0161 – Speed Regulator Proportional Gain P0162 – Speed Regulator Integral Gain P0163 –...
  • Page 298: Flux Regulator [92]

    PM Vector Control P0439 – Iq Current Regulator Integral Gain P0441 – Id Current Regulator Integral Gain Adjustable 0 to 1.999 Factory 0.005 Range: Setting: Properties: Access groups 01 PARAMETER GROUPS via HMI: 29 Vector Control 92 Flux Regulator Description: Parameters P0438, P0439, P0440 and P0441 are automatically set as a function of parameter P0402.
  • Page 299: Torque Current Limitation [95]

    Parameters P0171, P0172 and P0173 are inactive. 21.7.5 DC Link Regulator [96] For the deceleration of high inertia loads with short deceleration times, the CFW-11 has available the DC Link Regulation function, which avoids DC link overvoltage (F022) inverter tripping.
  • Page 300: Flying Start/Ride-Through [44]

    PM Vector Control Description: It enables or disables the Without losses function of the DC Link Regulator, according to the next table. Table 21.1 - DC Link Regulation Modes P0184 Action 0 = With losses INACTIVE. If it is used, F022 (overvoltage) may occur during the speed reduction (Optical Braking) Automatic control of the deceleration ramp.
  • Page 301: Dc Braking [47]

    Read the entire CFW-11 user's manual before installing, powering up or operating the inverter. Sequence for the installation, verification, and start-up: a) Install the inverter according to the CFW-11 user's manual chapter 3 - Installation and Connection - wiring all the power and control connection.
  • Page 302 Basic Application [04] parameter group, refer to the item 5.2.3 - Setting Basic Application Parameters, of the CFW-11 user's manual. - That require only the digital and analog inputs and outputs with programming different from the factory settings, use the Menu "I/O Configuration"...
  • Page 303 PM Vector Control - Motor vibration (it generally occurs when P0202 = 7) 1. Decrease the id proportional gain (P0440) in steps of 0.05 down to the minimum of 0.2. 2. Decrease reduce the iq proportional gain (P0438) in steps of 0.05 down to the minimum of 0.5. 3.
  • Page 304 PM Vector Control Seq. Action/Result Display Indication Seq. Action/Result Display Indication - Set the content of P0202 Ready 0rpm - Monitoring Mode. pressing "Selec.". - Press "Menu" - Next press until Config 0rpm (right "soft key"). selecting the option: "[007] Language P0201: English 13:48...
  • Page 305 PM Vector Control Seq. Action/Result Display Indication Seq. Action/Result Display Indication - If necessary, change - Set P0409 according to the content of P0401 the motor data sheet. Config 0rpm according to the rated Therefore, press "Selec.". Config 0rpm Encoder Pulses Number motor current.
  • Page 306: Faults And Alarms

    PM Vector Control 21.9 FAULTS AND ALARMS When the control mode is PM with encoder (P0202 = 6), fault reset will only be accepted with stopped motor. Except for the F079 (Encoder fault) reset, which could occur with the motor shaft in movement; however, the motor must be stopped in order to avoid operation problems after the fault reset.
  • Page 307 WEG Drives & Controls - Automação LTDA. Jaraguá do Sul - SC - Brazil Phone 55 (47) 3276-4000 - Fax 55 (47) 3276-4020 São Paulo - SP - Brazil Phone 55 (11) 5053-2300 - Fax 55 (11) 5052-4212 automacao@weg.net www.weg.net...

Table of Contents